PW-water punchlist no 1 113006.doc From: Deonne Hardy Kevin Ray Kevin Ray 4 21 2006-11-30T22:53:00Z 2006-10-19T23:13:00Z 2006-11-30T22:54:00Z 1 625 3566 29 8 Subject: Mountain Shadow first punch list walk through Date: 18/October/2006 1           Clean off and set all meter boxes to final grade. 2.         Need to move the irrigation meter setter and Double Check Valve Assembly back to the curb, next to lot 36 meter box, and the setter must be bedded in sand. 3.          At lot 36, need to replace the meter box lid with one without a hole in the lid, and lower the meter setter. 4.         There is no wire in the valve housing for the ten inch gate valve at station 50 + 08.5. Canal Rd. and Cary ’s St. 5.          The center valve housing, on the eight inch gate valve at station 50 + 08.5, the wire is to short. 6.         Lots 43 and 44 need the meter setters center in the box and check the clearance with a meter body. 7.         Lots 50 and 51 need too lower meter setters and center them in the box and check the clearance with a meter body. 8.         Need too reposition the blow off box at end of Cary ’s Street and replace lid with a solid traffic bearing lid. 9.       Lots 28 and 29 need too straighten meter setters and center in the box and check the clearance with a meter body. 10.       Lots 26 and 27 meter setters need to be raised and centered in the box and checked for clearance. 11.       Lots 53 and 55 need meter setters lowered. 12.       Need to uncover the air/release at station 28 + 20.00 and expose the top and at six inches down on the body, leaking repair 13.       Need the Stroz’s fitting screws tightened on the fire hydrant at station 25 +83.82. 14.       Lots 22 and 23 the meter setter’s need too be raised and center in meter box and check the clearance with a meter body. 15.       Lots 58 and 59 need meter setter’s center in meter box and checked with a meter body. 17.               Lots 60 and 61 need the box to be cleaned out. 18.               Lots 20 and 21 needs meter setters straighten and checked with a meter body. 19.               Clean out box for air release a station 23 + 55.07 and expose the top and at least six inches of the body. Replace the lid with one that does not have a reader hole in lid, leaking repair 20.               Lots 62 and 63 the meter box needs to be cleaned out. 21.               At lots 18 and 19 straighten and center meter setters in the box and check clearance with meter body. 22.               Lot 17 needs meter setter straightened. 23.               Need to check clearance for setters using a meter body lots 70 and 71. 24.               At lot 71 the water and sewer does not have ten feet separation. 25.               The ten inch gate valve at station 19 + 91.50 needs to be cleaned out. Canal Rd. and Thea Rosa Dr. – East side valve has no wire. 26.               There is no wire in ten inch gate valve on west side at Canal Rd. and Thea Rosa Dr. 27.               At the eight inch gate valve, at Thea Rosa and Canal Rd., the wire is inside riser pipe. 28.               The ten inch gate valve at Canal Rd. and Canal Ct. to the end of line has no wire. 29.               Need to clean out the meter box at lot 72. 30.               Lots 73 and 74 need to center meter setters in the box and check the clearance with meter body. 31.               The air /release at station 12 + 40 need to be cleaned off the top and down six inches on the body. Need to replace the lid with one without a hole. Leaking repair 32.               Need to clean out the box for the blow off on Canal Ct. at station13 + 25.00 33.               The wire is inside valve box riser for blow off at station 13 + 25.00. 34.               Lots 79 and 80 the meter need to be raised, centered and check the clearance with meter body. 35.               Lower meter setter for the irrigation and   must be bedded in sand at the end of Canal Ct. Make sure box is at final grade 36.               There is no Double Check Valve Assembly for the irrigation at the end of Canal Ct. 37.               The blow off at the end of the line on Canal Ct will not shut off. This needs to be repaired or replaced. Lid for gate valve is missing 38.               Need to straighten meter setters, center in box and check clearance with meter body on lots 1, 2, 3 and 4. 39.               Need to raise meter setter , square and center in the box’s and check clearance with a meter body on lots 7,8,9,10,11,12,13,14,15 and 16. 40.               The Double Check Valve Assembly’s for irrigation must be tested by a certified tester before water is left on to meters. 41.               Copies of the well abandonment reports must be provided to the water department. 42.               Good bacterial samples results have been received .