Here is a recap of our conversation on October 22, 2003. Please forward this to your engineer, and have him call if he has questions.
Concerns on original site plan:
Storm swale must be at least 5-feet from property line
Underground storm galleries must be at least 10 feet from property line
Perimeter landscape buffer is must be 8 feet
Using the alley as an ingress/egress would require improving the alley
Fire coverage requires either a hydrant or 20 foot paved fire lane around the bldg.
90 degree parking with 2-way travel requires a 23-foot travel lane & 9’x20’ stalls.
Options to consider:
1. The City would accept a slight variation from above to include:
Reducing the Landscape buffer on the west side to 5-feet
Allow 2-way drive lane to be 22-feet
Storm swale must be located elsewhere on the property, or stormwater completely underground.
Alley to be one-way exit only.
2. Provide a one way drive isle around the building, utilizing the two driveway accesses, making each a one-way only. This would allow for a 12 foot drive lane, and 45 degree angled
parking. To achieve the desired number of parking stalls, stalls would be located behind the building as well.
Please have your engineer review our development guidelines. They are located on our website: www.ci.yelm.wa.us - go to the community development section and the guidelines are
located on the left side of the page. They explain the requirements of the Presubmission notes, which I have included as an attached file. The City also uses the Washington State Department
of Ecology 1992 Stormwater Manual.