20190049 2108-2 HeatingSimple Heating System Size: Washington State Project Information Contact Information Heating System Type: To see detailed instructions for each section, place your cursor on the word "Instructions". Design Temperature Instructions Design Temperature Difference (∆T)53 ∆T = Indoor (70 degrees) - Outdoor Design Temp Area of Building Conditioned Floor Area Instructions Conditioned Floor Area (sq ft)2,108 Average Ceiling Height Conditioned Volume Instructions Average Ceiling Height (ft)9.0 18,972 Glazing and Doors U-Factor X Area =UA Instructions 0.30 407 122.10 Skylights U-Factor X Area =UA Instructions 0.50 0 --- Insulation Attic U-Factor X Area =UA Instructions 0.026 1,237 32.16 Single Rafter or Joist Vaulted Ceilings U-Factor X Area UA Instructions 0.027 ________ Above Grade Walls (see Figure 1)U-Factor X Area UA Instructions 0.056 2,407 134.79 Floors U-Factor X Area UA Instructions 0.025 871 21.78 Below Grade Walls (see Figure 1)U-Factor X Area UA Instructions ---0 --- Slab Below Grade (see Figure 1)F-Factor X Length UA Instructions ---0 ________ Slab on Grade (see Figure 1)F-Factor X Length UA Instructions ---0 ________ Location of Ducts Instructions Duct Leakage Coefficient 1.00 Sum of UA 310.83 Envelope Heat Load 16,474 Btu / Hour Sum of UA X ∆T Air Leakage Heat Load 10,860 Btu / Hour Volume X 0.6 X ∆T X .018 Building Design Heat Load 27,334 Btu / Hour Air Leakage + Envelope Heat Loss Building and Duct Heat Load 27,334 Btu / Hour Ducts in unconditioned space: Sum of Building Heat Loss X 1.10 Ducts in conditioned space: Sum of Building Heat Loss X 1 Maximum Heat Equipment Output 38,267 Btu / Hour Building and Duct Heat Loss X 1.40 for Forced Air Furnace Building and Duct Heat Loss X 1.25 for Heat Pump This heating system sizing calculator is based on the Prescriptive Requirements of the 2015 Washington State Energy Code (WSEC) and ACCA Manuals J and S. This calculator will calculate heating loads only. ACCA procedures for sizing cooling systems should be used to determine cooling loads. The glazing (window) and door portion of this calculator assumes the installed glazing and door products have an area weighted average U-factor of 0.30. The incorporated insulation requirements are the minimum prescriptive amounts specified by the 2015 WSEC. Please fill out all of the green drop-downs and boxes that are applicable to your project. As you make selections in the drop-downs for each section, some values will be calculated for you. If you do not see the selection you need in the drop-down options, please call the WSU Energy Extension Program at (360) 956-2042 for assistance. 2108-2 Level Design LLC 253-284-3170 Above Grade Below Grade Figure 1. All Other Systems Heat Pump (07/01/13)