Rosemont Sewer reviewYelm Sewer Department
3/10/2003
Review Rosemont assisted living
The connecting pipe between the 10000 gal. STEP tank and the pump tank shows this pipe coming from the middle of the 10000 gal tank. This needs to be corrected on the drawings.
Grease trap size needs to be shown and approved by the sewer dept.
What is the location of the nearest hose bib for maintenance
Based on the size of this tank I assume that this is not a simplex system and more than 1 pump will be required, only 1 pump is specified.
A cut sheet of these proposed tanks from Xerxes is required for approval