20080057 Fire Sprinkler Final 082409~ ~ { ,.
~~ ~~ TOWNZEN & ASSOCIATES
~~. ` FIRE 8~ BUILDING CODE SOLUTIONS
Inspection Report
Proiect:
Tahoma Apartments
Date:
8/24/09
Jurisdiction:
City of Yelm
Inspection Tvpe:
Fire Alarm and Fire Sprinkler Final
I nspector:
Les Townzen
Comments:
The following corrections are required before final approval can be given for occupancy.
Buildinq B:
1. There missing heads in the following locations:
a. The riser room
b. Unit 13 by the bathroom
c. Unit 3
d. Unit 10
2. The head outside of the patio in unit 11 is not trimmed out.
3. Contractor to verify all heads have not been painted.
Buildinq C:
1. The following units have painted heads:
a. 47, 46, 45, 66, 36, 40, 39, 38, 37
2. The flowing units have heads missing.
a. The riser room
b. Unit 33
Site issues:
1. Provide the protective caps for the fire department connections.
2. Provide signage for the riser room doors that indicate "fire sprinkler riser" and "fire alarm
control panel".
3. Provide pad lock for the sprinkler post indicating valves.
4. The Knox box is to contain the following keys:
a. Both locks on the riser room doors.
b. Master unit keys
c. Key for the pull stations
d. Key for the fire alarm control panel and the bypass key.
5. Remove the handles from the backflow preventer and place them in the spare head box
within the riser room.
If you have any questions, please call.
Les Townzen, CFPS
President