From: Steve Harrington
Sent: Friday, July 27, 2007 9:42 AM
To: Roberta Allen
Cc: Jim Gibson
Subject: McCammant Fourplexes
Roberta: Here are my comments for the McCammant Fourplexes.
Item # 4 Water: 1. Please show sizing criteria to show how a 1 ½” to 2” fire line is going to be adequate for a fire sprinkler system for these units. Please include fire protection
system drawings.
2. Please provide info showing the 2 - 2” water meters are going to be Master Meters or if they will have meters for each unit. If these are going to be Master Meters, they will also
be required to
have double check valve assemblies installed behind the meters.
Item # 10 Sewer: 1. Please revise sewer connection note on sheet 1 of 5 on the drawing referring “SEE DETAIL # 7- ? This will need to show the complete number of the detail being called
out.
Item # 11 Sewer: 1. The location of the step sewer Carson Boxes must be shown on plans.
Item # 18 Storm Treatment: 1. The Bay Saver Separation Storm Treatment Device, currently is not approved for use in the City of Yelm. Please look at other storm treatment devices such
as AquaShield (AquaSwirl) which are currently approved for use in the City of Yelm. Please size your storm treatment adequately for the size of your project.
Item # 20 Storm Treatment: 1. Please show infiltration gallery plan and profile for paved parking area, be sure to size accordingly for intended use to handle parking, drainage and
other run off.
Item # 24 Storm Treatment: 1. Please see City of Yelm Standard 7-20 for Typical End of Line Clean Out.
Item # 26 Storm Treatment: 1. We have not received any revised plans for Landscape.
Item # 29 Storm Treatment: 1. Plans need to show the location of the Fire Department Connection (FDC). Also needed are the criteria showing that the fire protection system is adequate
for these buildings.
All Sheets: Please revise title box on all sheets to read the proper title for what is being show on that plan sheet.
<DC90029353CCCD468AA2A2858FFCD8F528F883@server1.ci.yelm.wa.us>
FW%3A McCammant Fourplexes.EML
Steve Harrington