McCammant 4 Plexes Punch ListIPM.Note
McCammant 4 Plexes Punch List
Steve Harrington
Jon Yanasak
Steve Harrington
EX
/O=CITYOFYELM/OU=FIRST ADMINISTRATIVE GROUP/CN=RECIPIENTS/CN=JONY
McCammant 4 Plexes Punch List
EX
/O=CITYOFYELM/OU=FIRST ADMINISTRATIVE GROUP/CN=RECIPIENTS/CN=STEVEH
EX
/O=CITYOFYELM/OU=FIRST ADMINISTRATIVE GROUP/CN=RECIPIENTS/CN=STEVEH
Jon Yanasak
EX
/O=CITYOFYELM/OU=FIRST ADMINISTRATIVE GROUP/CN=RECIPIENTS/CN=JONY
Tim Peterson
Steve Harrington
McCammant 4 Plexes Punch List
00000002SERVER1/o=CITYOFYELM/ou=first administrative group/cn=Recipients/cn=jonyMicrosoft Exchange Server
00000002SERVER1/o=CITYOFYELM/ou=first administrative group/cn=Recipients/cn=jonyMicrosoft Exchange Server
Steve, here you go ----
Jon Yanasak
City of Yelm Sewer Dept. Mgr
Po Box 479
Yelm Wa 98597
Phone 360-458-8411
Fax 360-458-8166
jony@ci.yelm.wa.us
<DC90029353CCCD468AA2A2858FFCD8F5397F03@server1.ci.yelm.wa.us>
McCammant 4 Plexes Punch List.EML
Steve Harrington
11.0
Microsoft Exchange Server
00000002SERVER1/o=CITYOFYELM/ou=first administrative group/cn=Recipients/cn=jony
McCammant 4Plexes Punch List July 24, 2008
McCammant 4Plexes Punch List July 24, 2008
Steve Harrington
EX
/O=CITYOFYELM/OU=FIRST ADMINISTRATIVE GROUP/CN=RECIPIENTS/CN=Steveh
steveh@ci.yelm.wa.us
steveh
458-8423
Community Development
Steve Harrington
Steve Harrington
Tim Peterson
EX
/O=CITYOFYELM/OU=FIRST ADMINISTRATIVE GROUP/CN=RECIPIENTS/CN=Tim
tim@ci.yelm.wa.us
tim
458-8499
Public Works
Tim Peterson
Tim Peterson
McCammant 4Plexes Punch List July 24, 2008.doc
CITY OF YELM SEWER DEPARTMENT
July 24, 2008
Re: Punch list McCammant 4-Plexes
Bldg “A”
Green riser lids need to be installed on all risers.
A 3rd neutral wire needs to be installed between the house breaker panel and the pump Control Panel.
The Pump Control Panel has a broken mount on the Motor Starter and must be replaced.
A surge arrester needs to be installed in the Pump Control Panel per our spec.
The float wiring needs to be corrected so each float does what it is designed to do.
The wires in the “J” box within the vault have multiple cuts in the insulation. Connections need to be re-done.
The Side Sewer “Clean-Outs” have been buried and must be found and brought up to grade.
Bldg “B”
Green riser lids need to be installed on all risers.
A 3rd neutral wire needs to be installed between the house breaker panel and the pump Control Panel.
A surge arrester needs to be installed in the Pump Control Panel per our spec.
The Side Sewer “Clean-Outs” have been buried and must be found and brought up to grade.
The wires in the “J” box within the vault have multiple cuts in the insulation. Connections need to be re-done.
The float wiring needs to be corrected so each float does what it is designed to do.