05-0540 Sewer #1 072408CITY OF YELM SEWER DEPARTMENT
July 24, 2008
Re: Punch list McCammant 4-Plexes
Bldg “A”
Green riser lids need to be installed on all risers.
A 3rd neutral wire needs to be installed between the house breaker panel and the pump Control Panel.
The Pump Control Panel has a broken mount on the Motor Starter and must be replaced.
A surge arrester needs to be installed in the Pump Control Panel per our spec.
The float wiring needs to be corrected so each float does what it is designed to do.
The wires in the “J” box within the vault have multiple cuts in the insulation. Connections need to be re-done.
The Side Sewer “Clean-Outs” have been buried and must be found and brought up to grade.
Bldg “B”
Green riser lids need to be installed on all risers.
A 3rd neutral wire needs to be installed between the house breaker panel and the pump Control Panel.
A surge arrester needs to be installed in the Pump Control Panel per our spec.
The Side Sewer “Clean-Outs” have been buried and must be found and brought up to grade.
The wires in the “J” box within the vault have multiple cuts in the insulation. Connections need to be re-done.
The float wiring needs to be corrected so each float does what it is designed to do.