05-0531 Water Review no 1 040507 From: Edward Smith
Sent: Thursday, April 05, 2007 4:12 PM
To: Tim Peterson
Cc: Deonne Hardy; Jim Gibson; Kevin Ray; Steve Harrington
Subject: Rainier View Estates Plan Review Public Works.doc
.????? City of Yelm Public Works Department
901 Rhoton Road
P.O. Box 479
Yelm, WA 98597
(360) 458-8406 Fax: (360) 458-8417
Public Works Inspection Report
Date: 4/5/07 Page
1
of
1
Location: Rainier View Estates Department: Water
Contractor: Rep:
1. The well must be decommissioned PER DOH and DOE regulations and a copy of the report sent to the City of Yelm Water Department. 2. At lot 14 the water meter
and the sewer air release are to close. They must have ten feet of separation. 3. The water meters for lots 10 and 8, 11 and 12 are too close to the sewer for lots 8 and
11.They must have ten feet of separation. 4. The sewer service for lot five is too close to the water meter for lot five. They must have ten feet of separation.
5. The sewer service for lot four is too close to the water meter for lot four. They must have ten feet of separation.
6. The storm tract irrigation system will require a Double Check Valve Assembly behind the water meter.
7. The sewer service for lot one is too close to the water meter for lot one. They must have ten feet of separation.
8. The air/release at the end of main at station 6 + 82.46 is not needed.
9. At station 6 +84.5 the blow off at the end of the main will need the same size gate valve on the main.
10. The sewer service for lot 22 is too close to the water meter for lot 22. They must have ten feet of separation.
11. Can we move the eight inch Tee to station 4 + 90 and omit the 90degree bend?
Use the Tee for the fire hydrant run also. They will need to add some adaptors to the Tee. (8” X 8” X 8” FL Tee, FL X Fl x FL,)(8’ FL X 6’ FL INCREASER,)(6 INCH GATE VALVE FOR
THE FIRE HYDRANT) and (8”MJ X FL ADAPTORS)
12. We would like to see C900 – Class 150 PVS pipe, not DI. pipe
Reviewed by: John I, And Edward Smith
Signed by: Edward Smith