FW Rainier View Estates Civil Review #2IPM.Note
FW: Rainier View Estates Civil Review #2
FW:
Roberta Allen
Jim Gibson
Roberta Allen
EX
/O=CITYOFYELM/OU=FIRST ADMINISTRATIVE GROUP/CN=RECIPIENTS/CN=GIBSON
Rainier View Estates Civil Review #2
EX
/O=CITYOFYELM/OU=FIRST ADMINISTRATIVE GROUP/CN=RECIPIENTS/CN=R_ALLEN
EX
/O=CITYOFYELM/OU=FIRST ADMINISTRATIVE GROUP/CN=RECIPIENTS/CN=R_ALLEN
Jim Gibson
EX
/O=CITYOFYELM/OU=FIRST ADMINISTRATIVE GROUP/CN=RECIPIENTS/CN=GIBSON
Roberta Allen
Rainier View Estates Civil Review #2
Roberta - This should have been routed to you.
Jim Gibson P.E.
City of Yelm, Development Review Engineer
PO Box 479 Yelm,WA. 98597
Ph. 360.458.8438 Fx. 360.458.3144
jimg@ci.yelm.wa.us
________________________________
From: Jon Yanasak
Sent: Tuesday, July 24, 2007 1:14 PM
To: Jim Gibson
Cc: Tim Peterson
Subject: Rainier View Estates Civil Review #2
Here you go --
Jon Yanasak
City of Yelm
Water Reclamation Facility Mgr..
PO Box 479
Yelm Wa 98597
PH 360-458-8411
FX 360-458-8166
jony@ci.yelm.wa.us <mailto:jony@ci.yelm.wa.us>
<DC90029353CCCD468AA2A2858FFCD8F5329C99@server1.ci.yelm.wa.us>
FW%3A Rainier View Estates Civil Review %232.EML
Roberta Allen
Roberta Allen
11.0
Rainier View Estates Civil Review # II July 24, 2007
Rainier View Estates Civil Review _ II July 24, 2007
Roberta Allen
EX
/O=CITYOFYELM/OU=FIRST ADMINISTRATIVE GROUP/CN=RECIPIENTS/CN=R_allen
r_allen@ci.yelm.wa.us
r_allen
Roberta Allen
Roberta Allen
R_ALLEN
Rainier View Estates Civil Review # II July 24, 2007.doc
CITY OF YELM SEWER DEPARTMENT
July 24, 2007
Re: Rainier View Estates Civil Review # II
The 2 gate valves shown by the 45 degree bends should be eliminated. Only 1 gate valve should be provided for this project and it should be located at the mid point of the pipeline.
All fittings should be Slip X Slip with thrust blocks. No MJ fittings are allowed.
If pavement is to be placed for the driveways for lots 8 and 11 during this project, the service lines and toning wire will need to be installed.
Vertical 22 ½ degree bends are shown on the drawings in the 2” main. These are shown as MJ fittings. No MJ fittings are allowed. And all bends need thrust blocking. I suspect that these
bends could be accomplished with a slight deflection of the pipe.