Loading...
SUB-05-0058-YL As_Built Review letter 2 3-24-09 City of Yelm Community Development Department 105 Yelm Avenue West P.O. Box 479 Yelm, WA 98597   March 24, 2009 SCA Consulting Group Steve Chamberlain 4200 6th Avenue, Suite 301 Lacey, WA 98503 RE: Bella Housa Village – SUB-05-0058-YL As-Built Review of Civil – Site Construction Documents Mr. Chamberlain: The City of Yelm has completed the initial review of the As-Built Plans. Your application included: As-Built Plans We have reviewed the as-built plans for compliance with the City of Yelm Development Guidelines, and general standards of civil engineering practice. The following comments need to be addressed before the plans may be approved for construction. Our comments are summarized below: Water: Sheet 8 Note 16, Irrigation service has a Double Check Valve Assembly installed not a Reduced Pressure Backflow Assembly. Please revise. Sewer: The Air Release Assembly originally scheduled (and shown on this copy of the As Builts) to be installed at STA. # 7+ 42.9 was instead installed at STA. # 6+68.00. Please revise. Landscaping Plans: Final landscape plans have not been included. Additional Comments: Please add the all street signs and striping to plans. Please review and revise the plans to address the above referenced comments. When the project is resubmitted you will need to submit 1 set of plans for signature. If you have any additional questions or comments please do not hesitate to call or contact me at steveh@ci.yelm.wa.us Community Development Department Respectfully, Steve Harrington Engineering / Civil Inspector