SUB-05-0058-YL Bella Housa final punchlist FOR CLUB HOUSE
Randy and I met with Merle Hom of Bella Housa today and went over
problems with their STEP System for the clubhouse along with a
representative with pichler Construction. Apparently the Punchlist for
the sewer dept. didn’t get distributed. (It may be our fault, who knows)
bottom line here is the punch list for the clubhouse STEP system
Jim Doty
Plant Manager
City of Yelm Water Reclamation Facility
931 N.P. Road
Mail:
105 Yelm Ave. W.
Yelm, WA 98597
Ph. (360)458-8411
Fax (360)458-8166
<DC90029353CCCD468AA2A2858FFCD8F589E753@server1.ci.yelm.wa.us>
SUB-05-0058-YL Bella Housa final punchlist FOR CLUB HOUSE.EML
Steve Harrington
11.0
Bella Housa punch list Sept 9, 2008
Bella Housa punch list Sept 9, 2008
Karen Bennett
EX
/O=CITYOFYELM/OU=FIRST ADMINISTRATIVE GROUP/CN=RECIPIENTS/CN=KarenB
KarenB@ci.yelm.wa.us
458-3835
Community Development
Karen Bennett
Karen Bennett
KarenB
Tim Peterson
EX
/O=CITYOFYELM/OU=FIRST ADMINISTRATIVE GROUP/CN=RECIPIENTS/CN=Tim
tim@ci.yelm.wa.us
458-8499
Public Works
Tim Peterson
Tim Peterson
tim
Steve Harrington
EX
/O=CITYOFYELM/OU=FIRST ADMINISTRATIVE GROUP/CN=RECIPIENTS/CN=Steveh
steveh@ci.yelm.wa.us
458-8423
Community Development
Steve Harrington
Steve Harrington
steveh
Bella Housa punch list Sept 9, 2008.doc
CITY OF YELM SEWER DEPT.
Sept 9, 2008
Re: Bella Housa Punch list
The Pump Control panel needs to be mounted 5’ from the top of the panel to finished grade.
The electrical system for the sewer pumps etc. must be approved by L&I.
The Pump Control Panel needs to have a City of Yelm Sewer Dept sticker in the front.
The Pump Control panel needs to have a remote disconnect per L&I.
The wires serving the pumps and controls from the Pump Control Panel need to be different colors for ease of tracing electrical problems in the future.
No wire nut connections are allowed within the “J” box in the tank riser. Heat shrink butt connectors only.
The float tree must not be glued in place.
A surge arrester is required to be installed with this system.
It must be proven by Potholing or otherwise satisfactory to the sewer dept. that conduit (2) from control panel to tank connections is complete and intact.
House breaker panel needs 3 breakers with separate power and neutral wires to control panel. 2-20 amp motor circuits and one 10 amp control circuit. Tying circuits together is not accepted!