05-0458 Water Review 1b 111407 From: Edward Smith
Sent: Wednesday, November 14, 2007 11:06 AM
To: Tim Peterson
Cc: Deonne Hardy; Kevin Ray; Jim Gibson; Steve Harrington
Subject: Forrester Heights Booster Station #2 Plan Review Public Works.doc
Forrester Heights Booster Station review from water department
??? City of Yelm Public Works Department
901 Rhoton Road
P.O. Box 479
Yelm, WA 98597
(360) 458-8406 Fax: (360) 458-8417
Public Works Inspection Report
Date: 13/November /2007 Page 1
Location: Forrester Heights Booster Station Department: Water
Contractor: Rep:
1. The gate valves on the existing ten inch main stub outs are on the tees in the street.
2. The building is too small – No access to the control panels with out stepping over the piping.
3. The building needs to have a floor drain.
4. Need to install a Ball Valves Curb Stop on the hose bib stub out.
5. The building must have a chain link fence around the building.
6. Why in the main being reduce to a six inch when the manifolds on the pump station are eight inch manifolds?
7. The Booster station needs to be tied into the City of Yelm’s telemeters system.
8. Is the city of Yelm paying for water system improvements review, from DOH, for this booster station?
Reviewed by: Edward Smith, John I
Signed by: Edward Smith