05-0458 Forrester Booster Pump Review No 2 113007 From: Jim Gibson Sent: Friday, November 30, 2007 2:32 PM To: 'Clint Pierpoint'; 'rgdinc@fairpoint.net' Cc: 'Mike Ollivant'; 'Randy Raymond'; Tim Peterson Subject: Forrester Estates Booster Pump Review No. 2 Attachments: Forrester Heights Booster Station Rev 2.pdf Clint - I have attached a letter from Parametrix as part of the second review on the booster pump station.  I also have the following comments from the Public Works Department.  Some of the comments are listed in both reviews.  At the bottom of the letter Parametrix suggests a meeting between the applicant, City and themselves to discuss the comments.  I will be contacting you in the next week or so to facilitate these meeting. Public Works Comments: The gate valves on the existing ten inch main stub outs are on the tees in the street. The building is too small – No access to the control panels with out stepping over the piping. The building needs to have a floor drain. Need to install a Ball Valves Curb Stop on the hose bib stub out. The building must have a chain link fence around the building. Why is the main being reduce to a six inch when the manifolds on the pump station are eight inch manifolds? The Booster station needs to be tied into the City of Yelm’s telemeters system. Jim Gibson P.E. City of Yelm, Development Review Engineer PO Box 479  Yelm,WA. 98597 Ph. 360.458.8438 Fx. 360.458.3144 jimg@ci.yelm.wa.us