05-0458 E-mail request for review routing 062408Clean??? Clean DocumentEmail false false false MicrosoftInternetExplorer4 From: Grant Beck
Sent: Wednesday, June 25, 2008 8:51 AM
To: Karen Bennett
Subject: FW: Forrester Heights Submittal Information
Attachments: KPFF Engineering Forrester Heights Boosterpaq Submittal Information.pdf
Karen - Please route this as a civil plan submission for Forrester Heights (it was a Jim project, so he may have been outside the process on this one). It needs to go to:
Tim P. Jon Y. Jim D. Mike Ollivant at Parametrix The other guy at Parametrix that is helping Mike... I think is name is Ike something. Email distribution is fine... there
are no large plans with this one. Thanks! Grant
From: Clint Pierpoint [mailto:clint.pierpoint@kpff.com]
Sent: Tuesday, June 24, 2008 4:41 PM
To: Grant Beck
Cc: 'RGD'; Steve Chamberlain
Subject: FW: Forrester Heights Submittal Information
Grant,
Attached is the technical specification submittal for the Forrester Booster Station.
Please let me know how may hard copies, if any, you would like me to submit for final approval.
Thank you for attention to this matter,
Clinton D. Pierpoint | Associate
KPFF Consulting Engineers
4200 Sixth Avenue, Suite 309
Lacey,
Washington 98503
O: (360) 292-7230 M: (360) 790-6832
F:
(360) 292-7231clint.pierpoint@kpff.com
www.kpff.com
From: Mike Hoskison [mailto:mhoskison@pumptechnw.com]
Sent: Monday, June 23, 2008 12:36 AM
To: Clint Pierpoint
Cc: ben.enfield@kpff.com
Subject:
Forrester Heights Submittal Information
Hello Clint,
I have attached the submittal information for the Forrester Heights Grundfos Boosterpaq packaged station. This custom Grundfos packaged station contains two separate pressure
boosting systems all packaged on one skid.
The first system contains one Grundfos model CRE20-3 7.5 hp vertical multi stage centrifugal pump with a variable drive built into the motor. This system is designed for a duty
point of 117 gpm @ 114 Ft. TDH at the pump discharge.
The second system contains three Grundfos model CR90-1 pumps each with a dedicated variable drive located in the control panel. Two of the three pumps are designed for the duty
point of 750 gpm @ 45 Ft. TDH at the pump discharge. The third pump in the system is for emergency stand by.
Please do not hesitate to contact me if you have any questions.
Thanks!
Mike Hoskison
PumpTech Inc.
(425) 864-1963