Loading...
20190025 New Heating_System_Sizing_WorksheetSimple Heating System Size: Washington State Project Information Contact Information Heating System Type: To see detailed instructions for each section, place your cursor on the word "Instructions". Design Temperature Instructions Design Temperature Difference (∆T) 53 ∆T = Indoor (70 degrees) - Outdoor Design Temp Area of Building Conditioned Floor Area Instructions Conditioned Floor Area (sq ft) 2,652 Average Ceiling Height Conditioned Volume Instructions Average Ceiling Height (ft) 8.5 22,542 Glazing and Doors U-Factor X Area = UA Instructions 0.280 366 102.48 Skylights U-Factor X Area = UA Instructions 0.50 --- Insulation Attic U-Factor X Area = UA Instructions 0.026 1,640 42.64 Single Rafter or Joist Vaulted Ceilings U-Factor X Area UA Instructions ---________ Above Grade Walls (see Figure 1)U-Factor X Area UA Instructions 0.056 2,351 131.66 Floors U-Factor X Area UA Instructions 0.025 1,637 40.93 Below Grade Walls (see Figure 1)U-Factor X Area UA Instructions 0.028 ________ Slab Below Grade (see Figure 1)F-Factor X Length UA Instructions 0.303 --- Slab on Grade (see Figure 1)F-Factor X Length UA Instructions --- ________ Location of Ducts Instructions Duct Leakage Coefficient 1.10 Sum of UA 317.70 Envelope Heat Load 16,838 Btu / Hour Sum of UA X ∆T Air Leakage Heat Load 12,903 Btu / Hour Volume X 0.6 X ∆T X .018 Building Design Heat Load 29,741 Btu / Hour Air Leakage + Envelope Heat Loss Building and Duct Heat Load 32,715 Btu / Hour Ducts in unconditioned space: Sum of Building Heat Loss X 1.10 Ducts in conditioned space: Sum of Building Heat Loss X 1 Maximum Heat Equipment Output 45,801 Btu / Hour Building and Duct Heat Loss X 1.40 for Forced Air Furnace Building and Duct Heat Loss X 1.25 for Heat Pump This heating system sizing calculator is based on the Prescriptive Requirements of the 2015 Washington State Energy Code (WSEC) and ACCA Manuals J and S. This calculator will calculate heating loads only. ACCA procedures for sizing cooling systems should be used to determine cooling loads. Please fill out all of the green drop-downs and boxes that are applicable to your project. As you make selections in the drop-downs for each section, some values will be calculated for you. If you do not see the selection you need in the drop-down options, please call the WSU Energy Extension Program at (360) 956-2042 for assistance. Plan 2652 Rueppell Above Grade Below Grade Figure 1. All Other Systems Heat Pump (07/01/13)