08-0045 Fire Alarm System 013108 (2)Kirby Electric Inc.
4826 "B" St. NW Ste. 101
Auburn, WA 98001
x1jyffy
EL E C T R / CFnc_
CahhM ER CIAL•I N d USTR IAL
SUBMITTALS FOR
CREEK ST. PLAZA BLDG. A
1304 YELM AVE. SE
YELM, WA
PROPOSAL
Telephone (253) 859 -2000
Fax (253) 859 -2363
FIRE ALARM SYSTEM
SILENT KNIGHT 5700 ADRESSABLE PANEL
SILENT KNIGHT ADRESSABLE SMOKE DETECTOR
SILENT KNIGHT ADRESSABLE PULL STATION
SYSTEM SENSOR HORN /STORBES
SYSTEM SENSOR STROBE ONLY
SYSTEM SENSOR MODULE
PLANS
BATTERY CALCULATIONS
VOLTAGE DROP CALCULATIONS
January 30, 2007
DEREK MCCOY
KIRBY ELECTIC
4826 B ST. NW, STE. 101
AUBURN, WA 98001
253,859.2000
RECEIVED
JAN 31 2008
r�
�J
E,
Intel 11 Knight` Model 5700
Single Loop Addressable
Fire Alarm Control System
The affordable addressable fire alarm
control panel solution.
IntelliKnight Model 5700 is a 50 point class leading single loop
addressable fire alarm control/communicator system. 5700 provides you
with the revolutionary value and performance of addressable sensing
technology combined with exclusive, built -in digital communication,
distributed intelligent power, that includes an easy to use interface. Powerful features such as drift compensation
and maintenance alert are delivered in this powerful FACP from Silent Knight.
For more information about the IntelliKnight system, or to locate your nearest source, please call
1- 800 -446 -6444, or in Minnesota, call 763- 493 -6435.
Description
5700 performs drift compensation and
calibration checks on each of the
sensors in the system.
The basic IntelliKnight 5700 system
can be enhanced by adding modules
such as 5864 remote annunciator,
5824 seriallparallel printer interface
module (for printing system reports),
and 5496 intelligent power module.
5700 also features a powerful built -in
dual line fire communicator that allows
for reporting of all system activity to a
remote monitoring location.
Features
• Up to 50 addressable points
• Up to 125 zones and 125 output
groups
• Uses standard wire —no shielded or
twisted pair required
• Built -in digital communicator.
• Central station reporting by point or
by zone
• Supports Class B (Style 4) and Class
A (style 6 or 7) configuration for SLC
• Distributed, intelligent power
• Drift compensation
• 13 pre- programmed output cadences
(including ANSI -3.41) and 4
programmable outputs
Notification circuits configurable as 1
Class A (Style Z) or 2 Class B (Style
Y), or auxiliary power for resettable.
constant, or door holder power
• Built -in synchronization for AMSECO,
Centex"', Faraday, System Sensor
and Wheelock appliances
• Built -in annunciator with 80- character
LCD display
• RS-485 bus provides communication
to system accessories
• Upload or download programming,
event history, or detector status
onsite or from a remote location
using a PC and 5660 Silent Knight
Software Suite (SKSS)
Improvements in SKSS deliver five
times faster upload/downloads
• Built -in RS -232 interface for
programming via PC
• Built -in Farm C trouble relay rated at
2.5A at 27.4 VDC
• Two built -in Form C programmable
relays rated at 2.5A at 27.4 VDC
Programmable date setting for
Daylight Saving Time
Electrical Specifications
Primary AC: 120 VAC, 60 Hz, 1.5A
Total Accessory Load: 2.5A c7 27.4
VDC
Notification Power: 2.5A @ 27A VDC.
power - limited
Standby Current: 200 mA
Alarm Current: 325 mA
NofificafionlAux Power Circuits:
2.5A @ 27.4 VDC per circuit,
power - limited
Battery Charging Capacity: 7.0 -35.0 AH
Battery Size: 7 AH max, allowed in
FACP cabinet. Larger capacity
batteries can be housed in an RBB
accessory cabinet.
Mechanical Specifications
Dimensions:
12.75" W x 15.2" H x 3.4" D
(32.39Wx38.42Hx8.57Dcm)
Weight: 11.5 lbs. (5.2 kg)
Color. Red
Model 5700
Telephone Requirements:
FCC Part 15 and Part 68 approved
Type of Jack: RJ31X (two required)
Approvals
NFPA 13, NFPA 15, NFPA 16, NFPA
70. & NFPA 72: Central Station:
Remote Signalling; Local Protective
Signalling Systems; Auxiliary Protected
Premises Unit: & Water Deluge
Releasing Service. Suitable for
automatic, manual, waterflow, sprinkler
supervisory (DACT non - coded)
signalling services.
Other Approvals: UL Listed;
CSFM 7170 - 0559: 144:
MEA 429 -92 -E Vol. XVI.
SILENT
KNIGT
by
13, H
Honeywell
SLC Detectors
SD505 -APS
Addressable photoelectric smoke detector.
S0505 -AIS
Addressable ionization smoke detector.
SD505 -AHS
Absolute temperature heat detector that
goes into alarm immediately if the
temperature exceeds the programmable hp
point. Trip point range from 135 °F -150 °F
(0 °C- 37 1C).
SD505 -6AB
Six inch base for use with detector heads
SD505-APS, SD505 -AIS and 50505 -AHS.
SD505.4AB
Four inch base for use with detector heads
50505 -APS, SD505 -AIS, and SD505 -AHS.
SD505 -6SB
Six -inch sounder base for use with existing
sensor and base. Operates in single and
multi - station modes and/or as a system
sounder. Requires 2 additional wires for
power
SD505 -61B
Short circuit isolator base for SD505 -AHS.
SD505 -APS, and SD505 -AIS detectors
SD505 -6RB
Six -inch relay base for use with existing
sensor and base. Provides one Form C
contact.
SD505 -ADH
Duct housing that detects smoke in HVAC
ducts.
SD505 -ADHR
Duct detector base with relay. Provides
Form C alarm contact. For use with
SD505 -APS and 507505 -AIS sensors.
Compatible with SD505 -DTS remote test
switch
SD500- PSISD500 -PSDA
SD500 -PS is a single action pull station and
SD500 -PSDA is a dual action pull station.
I
ron..r reiwn rewrr
144 0 0 l
SLC Modules
Model SD500 -AIM
Dry contact input module for use with
normally open dry contacts. It features an
indicator LED to show alarm status.
SD500 -MIM
Mini dry contact input module is a small
version of the SD500 -AIM. For use with pull
stations and other normally open dry contact
inputs.
SD500 -AIM
Addressable notification module providing a
single Class A or Class B notification circuit
on the SLC
SD500 -ARM
Addressable relay module that features two
Form C output relays. Provides indicator
LED to show output status.
SD500 -SDM
Two -wire detector Input module. Allows for
the connection of conventional 2 -wire
detectors on the SLC loop. Requires two
additional wires for power.
SD500 -LIM
A short circuit isolator module for SLC
devices. When a short occurs on the SLC
loop, it is detected as a trouble, but all SLC
devices protected by the isolator module
continue to operate.
SD500 -LED
An LED driver capable of driving_ 80 LEDs
through the SLC loop. Up to 40
SD500 -LEDs can be used per system.
S -BUS Accessories
58601R Remote Fire Annunciator
Features the same 80 character backlit LCD
display keypad and firefighter's key switch
as the 5700 The system can be fully
programmed and operated from any 5860.
5860 is gray and 5860R is red.
5496 Intelligent Power Module
A 6 amp notification power expander that
provides four additional power - limited
notification appliance circuit outputs.
57010
_k
5880 LED /10 Module
Features 40 LED
outputs, 8 normally
open dry contact inputs Za
and one piezo output.
5+865 -3 and 5865 -4
Remote LED
Annunciator
Features 30
Programmable LED (15
red and 15 yellowy outputs and a piezo
sounder. The 5865 -4 adds a silence and
reset switch to the package.
5883 Relay Board
Features 10 general purpose Form C relays.
Used with 5880 module.
5824 Serial /Parallel Printer
Interface Module
Provides one parallel and one RS -232 serial
port for connecting a printer to 5808. Use to
print a real -time log of system events,
detector status reports, and event history.
interfaces with building control system
Miscellaneous Accessories
5660 Silent Knight Software Suite
User - friendly Windows software for remote
programming of 5700s using a PC. Upload
and view panel account information, event
history, and detector status.
5670 Silent Knight Software Suite
End -user facility management software
allows viewing of detector status and event
history via modem or direct connection.
RBB
Remote Battery Box Accessory Cabinet. Use
if backup batteries are too large to fit into
FACP cabinet Dimensions.
16" W x 10" H x 6" D
(406 mmWx254mmHx152mmD)
SD505 -DTS
Remote test switch that provides remote key
operated test function and annunciation of
detector alarm with SD505 -ADHR.
SILENT This document is not intended to be used for installation purposes. We try to
keep our product information up -to -date and accurate- We cannot cover all
KNIGHT U. I specific applications or anticipate all requirements. All specifications are
subject to change without notice. For more informalion, contact Silent Knight
Will by Honaywell 7550 Meridian Circle Suite 100, Maple Grove, Mn 55369 -4927.
Phone-. (800) 328-1103, Fax: (763) 493 -6475.
Intelliltnight & JumpStart are Registered Trademarks of Silent Knight
Flexput is a Trademark of Silent Knight
5495
MADE IN AMERICA
FORMA 350392 Rev, D. 04/06
Copyright r 2006 Silent Knight
L_J
EO
Addressable
Photoelectric Type
Smoke Detector im
Detect smoldering fires quickly and get
help fast with lntelliKnightO photoelectric
smoke detectors.
IntelliKnight addressable photoelectric smoke detectors are the clear choice for commercial settings where
smoldering fires are a threat. In addition to accurately detecting a smoldering fire, each SD505 -APS
photoelectric detector has a unique address, which is recognized by the IntelliKnight panel. No precious seconds
are wasted in determining location of an alarm.
The SD505 -APS compensates automatically for contamination in the environment. And detector testing is
simple —even from a remote site. Like other IntelliKnight detector models, the SD505 -APS offers a low profile for
pleasing aesthetics. The IntelliKnight family of detectors has been designed to use a common rase, Model
SD505 -6AB, allowing complete application and placement flexibility. Combine all this with the features you've
come to expect from Silent Knight smoke detectors —easy installation, stable operation, RFltransient protection„
and vandal- resistant locking —and it adds up to a flexible solution for all your fire protection needs.
Model SD505 -APS
Analog I Addressable
Photoelectric Type
Smoke Detector
The SD505 -APS is particularly
suited to detecting dense smoke
typical of fires involving materials
such as soft furnishings, plastic,
foam or other similar materials
which tend to smolder and produce
large visible particles.
The detector features automatic
compensation for contamination
and a simple detector calibration
test procedure that can be run from
the panel or remotely (using the
WindowsT^ based downloading
software).
Operation
The SD505 -APS units made up of
an LED light source and a silicon
photo diode receiving element. In a
normal standby condition, the
receiving element receives no light
from the pulsing light source. In the
event or fire, smoke enters the
detector and light is reflected from
the smoke particles to the receiving
element.
The light received is converted into
an electronic signal. Under normal
conditions, the status LED blinks
approximately every 15 seconds,
indicating that the head is
communicating with the loop. The
LED lights continuously during the
alarm period.
Features
• Low profile, 2 inches, including
base
• Simple and reliable addressing
without mechanical switches
• Automatic compensation for
sensor contamination
• Built -in fire test feature
• Simple detector calibration
testing through the control panel
or remotely through a
WindowsTm based computer
software.
• Vandakresistance locking
features
• Field cleanable
• UL listed, meets NFPA 72 Ch 7
requirements
• CSFM approved
• MEA approved
• FM Approved
L
SD505 -APS Smoke Detector
Specifications
Operating Voltage: 17-41 VDC
Current Consumption:
Standby:
55 rnA
Alarm:
.55 mA
Ambient Temperature:
32 °F to 120 °F
(0 °C to 49 °C)
Mounting:
4" Square, 4"
OCT. Single
gang mud ring
Relative Humidity:
85%
noncondensing
Air Velocity:
0 - 300 FPM
Compatible Bases:
SD505 -6AB
(Sold Separately)
(6" Base)
SD505-AAB
(4" Base)
SILENT
KNIGHT
by Honeywell
E
Model SD505 -APS
Addressable Photoelectric Type
Smoke Detector
Engineering Specifications
The contractor shall furnish and install where indicated on the plans, addressable photoelectric smoke detector
Silent Knight SD505 -APS. The combination detector head, and twist -lock base, shall be UL"'' listed compatible
with Silent Knight's IntelliKnight fire control panels.
The base shall permit direct interchange with Silent Knight SD505 -AIS Ionization Smoke Detector, or SD505-
AHS Heat Detector. Base shall be the appropriate twist -lock base SD505 -6AB.
The smoke detector shall have a flashing status LED for visual supervision. When the detector is actuated, the
flashing LED will latch on steady. The detector may be reset by actuating the control panel reset switch.
The calibration of the detector shall be capable of being selected and measured by the control panel without the
need for external test apparatus.
The vandal - resistant, security locking feature shall be used in those areas as indicated on the drawing. The
locking feature shall be field selectable as required.
The SD505 -APS shall automatically perform a functional test of the detector. The test method shall simulate
effects of products of combustion in the chamber to ensure testing of detector circuits.
N
Model SD505 -6AB Detector Base
(front view)
Diameter v 3- 15115"
v
i u
0
Height - 2 inches,
including base
Model SD505 -APS Detector Head
(front view)
SILENT This document is not intended to be used for installation purposes. We try to MADE IN AMERICA
KNIGHT" keep our product information up-to -date and accurate. We cannot cover all
specific applications or anticipate all requirements All specifications are FORM# 354225 Rev C,. 05105
subject to change without notice. For more information. contact Silent Knight
by Honeywell 7550 Meridian Circle Suite 100, Maple Grove, Mn 55369 -4927 Copyrght,v- 2005 Silent Knight
Phone: (800) 328 -0103, Fax: (763) 493 -6475.
SD500 -PS and SD50�0 -PSDA
Addressable Pull - Station
Intellil(night's addressable pull stations
combine fast response with pin -point
location ID.
The SD500 -PS and SD500 -PSDA are a single action or dual action addressable manual fire alarm pull station
for use with Silent Knight's IntelliKnight fire control panel. Extremely easy to operate, the SD500- PSIPSDA
provides a fast and practical means of manually initiating a fire alarm signal. The IntelliKnight panel recognizes
each manual pull station by its specific address saving precious seconds in determining the location of an alarm.
The SD500- PSIPSDA mounts to a single gang box and features a rugged metal construction that lasts and
lasts..
Combine all this with the features you've come to expect from Silent Knight - easy installation and stable
operation - and it adds up to a flexible solution for all your fire protection needs.
Model SD500 -PS &
SD500 -PSDA
Addressable Pull
Station
The SD500 -PS is a single action
addressable fire pull station, and
the SD500 - -PSDA is a dual action
addressable fire pull station. The
SD500- PSIPSDA feature rugged
metal construction A terminal strip
on back of the pull station allows
interconnection of the pull station to
the SLC of an IntelliKnight control
panel. The SD500- PSIPSDA is
designed for indoor use in non-
explosive environments. The
normally open initiating point
contacts are gold-plated to avoid
risk of corrosion. The SD500-
PSIPSDA has been tested by UL
for compliance to the requirements
of the Americans with Disabilities
ACT (ADA).
Features
• UL Listed
• CSFM listed
• ADA compliant
• Key reset (Same key as Silent
Knight enclosures)
• Surface mount back box
available
• Terminals - accept up to 14
gauge wire
• Extremely easy to operate
• Corrosion- resistant gold- plated
contacts.
• Reflective label makes it easier
to locate in low light
Operation
The SD500- PSIPSDA single action
pull stations are operated by a pull
on the front pull cover of the
station. A plunger switch, wired to
a self contained addressable
module, is released as the pull
station opens to initiate the alarm.
Once operated, the cover hangs
down and can be seen up to 100
feet away. The pull station is reset
by returning the front cover to the
normal upright position and
relockng the station with a reset
key. The reset keys are the same
keys used on Silent Knight
enclosures.
The SD500- PSIPSDA includes a
status LED which blinks, indicating
that the addressable module is
communicating with the loop. The
status LED lights continuously
during an alarm. A dip switch on
the addressable module is used to
set the unique address.
Specifications
Operating Voltage. 24VDC
Standby Current- 55mA
Alarm Current: .55mA
SD500 -PS
Ambient Temperature: 32` F to 120 °F
(0'C to 49 °C)
Mounting: Single gang
box -
Optional Red Surface Mount Box PS -SMBB
SILENT
KNIGHT
SD500 -PS and SD500 -PSDA
Addressable Pull-Station 92
Engineering Specifications
Manual pull station shall be addressable Module SD500- PSISD500 -PSDA. Equipment shall be made of 14
gauge C.R.S.(Cold Rolled Steel), painted with a red enamel . The label shall contain the words Fire Alarm and
be made of a reflective material embossed text 31$ Inches tall. Operating instruction shall be clearly visible on
the same label. Manual station Shall contain a key operated test and reset lock using a lock plate actuator, the
key shall match the control panel.
Manual station shall contain four terminal blocks with two connected to the addressable module and two connect
to the SLC loop. Manual station shall provide data to the control panel with an ID address programmed by dip
switch settings .
Manual stations shall be Underwriters Laboratories Inc. listed and - installed within the limits defined in the
American Disabilities Act.
PACP
N. i
r �
r ♦ _
It
♦ ♦
♦ I ♦
i ♦'� ' \i f�V �I �4�ar sF'�i59.0 •��.[9 StC•
i
'S
Wiring
r 2•irr
Mounting to Single Mounting to Optional
Gang Electrical Box Surface Mount Box
S PIG"
I
S'D500 -iPSDA
i—�
Installing SD500 -t_K cal Uaa min he
., � �
Dimensions at Woo caw
SILENT
KNIGHT
• A fd�uY EYipw +r
7550 Meridian Circle, Maple Grove, MN 55369 -492.7 MADE IN AMERICA
800 -446 -6444 or in Minnesota 763- 493 -6435 FORM# 350342, Re,,. 09/03
FAX: 763- 493 -6475
World Wide Web: http:.I/vvww.silentknight.com Copyright C 2003 Silent Knight
SYSTEM
SENSOR'
Selectable Output
Horns, Strobes, and
Horn /Strobes
SpectrAlert" Advance selectable- output horns, strobes,
and horn /strobes are rich with features guaranteed to
cut installation times and maximize profits.
The 5pectrAlert Advance series o` notification appliances is
designed to simplify installations, with features such as plug in
designs, instant feedback messages to ensure correct installation of
is individual devices, and 1 1 field-selectable candela settings for wall
and ceiling strobes and horn /strobes.
When installing Advance products, first attach a universal mounting
plate to a four -inch square, four -inch octagon or double -gang
junction box. Tie two -wire mounting plate attaches to a single -gang
junction box.
Next, connect the notification appliance circuit wiring ,o the SEMS
terminals on the mounting plate.
Finally, attach the horn, strobe or horn /strobe to the mounting plate
by inserting the product's tabs in the mounting plate's grooves. The
device will rotate into position, locking the product's pins Into the
mounting plate's terminals.The device will temporarily hold in place
with a catch until it is secured with a captured mounting screw.
The 5pectrAlert Advance series includes outdoor notification
appliances - Outdoor strobes and horn/strobes (two wire and four
wire) are available for wall or ceiling. Outdoor horns are available for
wall only. All System Sensor outdoor products are rated between
minus 40 degrees Fahrenheit and 151 degrees Fahrenheit in wet or
dry applications.
Features
• Electrically compatible with existing SpectrAlert products
Automatic selection of 12- or 24 -volt operation at 15 and 15/75
candela
Plug -in design
• Field selectable candela settings on wall and ceiling units: 15, 15175,
30, 75, 95.110, 115, 135, 150, 177,185
Same mounting plate for wall- and ceiling -mount units
• Shorting spring on mounting plate for continuity check before
installation
• Tamper resistant construction
• Outdoor wall and ceiling products rated from -40 °F to 1517
• Design allows minimal intrusion into the back box
• Horn rated at 88+ dbA at 16 volts
• Rotary switch for horn tone and three volume selections
• Outdoor products UL listed to UL 1638 (strobe) and UL 464 (horn)
outdoor requirements
• Outdoor products rainproof per UL 50 (NEMA 3R)
Compatible with MIDL sync module
Agency Listings
sr"AJUNC
UL
F IIA
MEA
1 _ -i 6:E u i S9,�rtlOCa melha�t
rF7ds3iiA,an�ncxxrnkwd
'I_'�- iE31F8 (horn Fpt -+ @s.
LIVED
APPROVED
approved
e5x13U Iham.Fmcil
SpectrAlert Advance Specifications
+.r
'General
SpectrAlert Advance homs, strobes and horn /strobes shall mount to a standard 4 x 4 x Iii - lncl -r back box, 4 -inch octagon back box or double -gang back
box. Two -wire products shall also mount to a single -gang 2 x 4 x 1 r: a -inch back box. .A universal mounting plate shalt be used for mounting ceiling and wall
praduch. I he r1001`1 b(jrI appliance Circuil whine shall lerrvlitrate at the universal It7uuntiritg plate. Also, SpectiAle,l Adv3rrie pruducts, when used with lire
Sync - Circuit- Module 44- es6011 y, shall be puweled hom a rion- [coded 11001 catioll appliance circuit Output and shatj operate err a riurntr al 11 Ur 24 volts. When
used with the Sync -Circuit Module, 12 -volt toted notification appliance circuit outputs shall operate between nine and 175 volts; 24-volt fated notification
appliance circuit outputs shall operate between 17 and 33 volts Indoor SpectrAlert Advance products shall operate between 32 and 126 degrees Fahrenheit
from a regulated DC, or full -wave rectified, unfiltered power supply Sirclocs and ham /strobes shall r ove field - selectable candela settings including 15, 15/75, 30,
75, 95, 110, 115,135, 150, 177, 185.
strobe
The strobe shall he a System `Genie[ Spa,.1rAlert Advance Model listed to l II 1 971 and shall to approved for fire pinterT :ve service. The it rnbp shall be
wired m a primary - signaling rimifiratlon appliance and comply with the Americans with Disabilities Art rarluirements for visible signaling appliances. N%hing hr
I Flz over the strobe's entire operating voltage range. The strobe Iight shall consist of a xenon flash tube and associated tens/reflector system.
Horn/Strobe Combination
The horri /strobe shall be a System Senso, SpectrAlert Advance Model listed to UL 1971 and LIL 464 and shall be approved far fire protective service,
The horir /strobe shall be wired as a primary - signaling notification appliance and comply with the Americans with Dlsalbittles Act requirements rot visible
signaling appliances, flashing at I Hz over v--e strobe's entire operating voltage range. The strobe light shall consist of a xenon flasti tube and associated
leirs/reflector systerrr. Ilrr hum sralI have direr audibility UPI icins arid air uptlun w switch lie. [Weer d lerrrpural three - pattern ar,d a nurr- tempura! (CW)tirruuus)
pattem.These options are set by a multiple position switch, on four -wire products, the strobe shall be powered independently of the sounder. The horn on
hone /strobe models shad operate on a coded or non -coded power supply.
Outdoor Products
SpectrAlert Advance outdoor horns, strobes and hom /strobes shall be listed for outdoor use by UL and shall operate between minus 46 degrees and 151
degrees Fahrenheit.The products shall be listed for use with a System Sensor outdoor /weatherproof back box with half inch and three - fourths inch conduit
entries.
Synchronization Module
The module shall be 3 System Sensor Sync- Circuit model flipL listed to UL 461 and shall be approved for fire protective service. The module shall tynchrorilze
SpectrAlen strobes at I Hz and horns at temporal three. Also, white operating the strobes, the module shall silence the horns on hoWstrabe models over a
single pair of wires. The module shall mount to a 4 11he x 411A6 x 21/e -inch back box, the module shall also control two Style Y (class 8) circuits or one Style Z
(class A) clrcurc the module shall synchronize multiple zones. Daisy chaining two or more synchronization modules together will synchronize all the zones they
control. The module shall not operate on a coded power supply.
PhysicaliElectrical Specifications
Standard Operating Temperature
321 to 12W VIC to 491C)
K Series Operating Temperature
-4(rF to 151 °F ( -40 °C to 66C)
Humidity Range
16 to 93% non-condensing (indoor products)
Strobe Flash Rate
1 flash per second
Nominal voltage
Regulated 12DC/FWR or regulated 24DC/FWR'
Operating Voltage Range2
8 to 17,5 V f I2V nominal) or 16 to 33 V (24 norninal)
Input terminal wire gauge
12 to 18 AWG
Ceiling mount dimensions (including lens)
6_8-d arneleF x 25 "high (1 ;3 mm ammeter x Fa min high)
Wall mount dimensions (including lens)
5bl x 4.7W x 2.5"D (1.42 rnm 1. x 114) min W x 64 mm D)
Horn dimensions
Shl x 4,7W x 1.3D (141 mm L x 119 mm W x 35 rrirri 0)
Wall -mount back box skirt dimensions (BBS -2, BBSW -2)
5.91 x 5.0V x 21T) (151 mm L x 128 mm W x 56 rnm D)
Ceiling -mount back box skirt dimensions (88SC -2, BBSCW -2)
11 'diameter x 225 -high (180 min diameter x 57 mm h gh)
Walt -mount weatherproof back box dimensions (SA -WBB)
�).r"1_ x 5.1'W x l.t] J (145 ruin L x 130 mere W x S 1 risen D)
Ceding -mount weatherproof back box dimensions (SA -W880
7 1 `diameter x 2.0- high 1 60 mm diameter x 51 mm high)
Notes:
1. full Wave I+c4_ 1WO I I WI11 voltage is a non -n guloic d, i liner varying power source that is used on some powet supply and panel outputs
2. P S, PC, and SC products will operate at 12 V nominal only for 15 and 15/75 cd.
�J
UL Current Draw Data
Sound Pattern
Listed Candela
Candela rating at -40 °F
15
Do not use below 321
15175
30
75
44
95
70
110
11.0
U L Max, Strobe Current Draw
(m A R MS)
135
135
150
150
177
177
UL Max. Horn Current
Draw
(mA
RMS)
80
86
86
96
8 -17.5 Volts
3
16 -33 Volts
LOW
71
73
76
8 -173 Volts
83
16 -33
Volts
Candela
DC
FWR
DC
82
FWR
88
Sound Pattern
d6
92
DC FWR
DC
FWR
Standard 1-
123
128
78
66
85
71
90
Temporal
High
6
57 55
Law
69
75
Candela Range 15/75"
142
148
84
77
92
81
Coded
Ternporal
Medium
82
44 49
88
58
69
30'
NA
NA
Coded
94
78
96
85
temporal
Low
90
38 44
98
44
48
75"
NA
NA
81
158
88
153
96
Non- temporal
High
57 56
69
75
95'
IN
NA.
181
176
Non- temporal
Medium
42 50
60
69
110
NA
NA
202
195
Non - temporal
Low
41 44
50
50
115
NA
NA
210
205
Coded
High
57 55
69
75
High 135
NA
NA
228
207
Coded
Medium
44 51
56
69
Candela Range 150
NA
NA
246
220
Cooled
Low
40 46
52
50
177
NA.
NA
281
251
185
NA.
NA
286
258
UL Max. Current Draw
8 -17.5 Volts
16-33
Volts
DC Input
15
15175
15
15/75 30
75
95
110
115
I. - „ poral High
137
147
79
90
107
176
19L
212
218
Temporal Medium
132
144
69
80
97
157
182
201
210
Temporal Low
132
143
66
77
93
154
179
198
207
Non - temporal High
141
152
91
100
116
176
201
221
229
Non - temporal Medium
133
145
75
85
102
163
187
207
216
Non - temporal Low
431
144
68
79
96
156
182
201
210
FWR Input
Temporal High
136
155
88
97
112
168
190
210
218
Temporal Mediurn
129
152
78
88
103
160
184
202
206
` Temporal Low
129
151
76
86
101
160
184
144
201
1Vr' Nan - temporal High
142
161
103
112
126
181
203
221
229
Nan - temporal Medium
134
155
85
95
110
166
189
2208
216
Nan - temporal Low
1
14
80
?(?
105
161
184
202
211
UL Max. Current Draw (mA
RMS1, 2-wire
16-33 Volts
Horn/Strobe,
High
Candela
Range
(135-185 cd)
16-33 Volts
DC input
135
150
177
185
FWR Input
135
150
177
185
Temporal High
245
259
290
297
lerriporal High
215
231
258
265
Temporal Medium
235
253
288
297
Temporal Medium
209
224
250
258
Temporal Law
232
251
282
292
lemporaI Low
207
221
248
256
Non-temporal High
255
270
303
309
Non- temporal High
233
248
275
281
Non- temporal Medium
242
259
293
299
Non - temporal Medium
219
232
262
267
Non - temporal Low
238
254
291
295
Non - temporal Low
214
229
256
7.62
Candela Derating
Horn Tones
and Sound Output
Data
Far K series products used at low temperatures,
listed
canrirfla
,-- Output
ratings must be reduced in accordance with
this
table
8-17 5
16 33
24 Volt Nominal
Strobe Output lcd)
Sound Pattern
Listed Candela
Candela rating at -40 °F
15
Do not use below 321
15175
30
75
44
95
70
110
11.0
175
115
135
135
150
150
177
177
185
165
Switch
Position
Sound Pattern
dB
Volts
DC
FWR
Volts
DC
FWR
Reverberant
DC FWR
Anechoic
DC FWR
I
Iermparal
high
78
78
8=1
84
88
88
6t7
98
2
Temporal
Medium
7A
74
80
80
86
86
96
96
3
Temporal
LOW
71
73
76
76
83
80
94
89
4
Non- temporal
High
82
82
88
88
93
92
100
100
Non- temporal
Medium
78
78
85
85
90
90
98
98
6
Non - temporal
Law
75
75
81
81
88
84
96
92
7'
Coded
High
82
82
88
88
93
92
101
101
8'
Coded
Medium
78
78
85
85
90
90
97
98
9'
Coded
Low
75
75
81
81
88
85
96
92
'Settings 7, 8, and 9 are not available on 2 -wire horn /strobe
SpectrAlert Advance Dimensions
_
2.s
Wall -mount horn /strobes Ceiling -mount horn /strobes
7.1"
71" {+- ?.25+1 W2� pia.
5.05 =+� j�2.23+f 6ia. 1 I f� D
6 .. � [f u/
5A,
Wall back box skirt Ceiling back box skirt Wall weatherproof back box Ceiling weatherproof back box
SpectrAlert Advance Ordering Information
Model Description Model Description
Wall Horn /Strobes Ceiling HomiStrobes (contd.)
P2R " 2 -wire l torn /Strobe,' Standard cd', Red PC2W *' 2 -wire Horn /Strobe, Standard cd, White
P2RH' 2 -wire! Porn /Strobe. Hiqh cd, Red PC2WH *' 2 -wire Horri /Strobe. High cd, White
P2RK* 2 -wire Born /Strobe, Standard cd. Red, Outdoor PC4R 4 -wire Horn /Strobe, Standard cd, Red
P2RHK' 2 -wire HornlStrobe, High cd, Red. Outdoor PCARH 4-wIre Horn/Strobc, High cd, Red
P2W* 2-wire Horn/Strobe, Standard cd, Whrte PC4RK 4-wlre Horn/Strobe, Standard cd, Red, Outdoor
P2W1 i* 2 -wire Horn/Strobe, High cd, White PC4RHK 4-wlre Horr'i/Strobe, High cd, Red, Outdoor
P4R* 4 -wire Horn /Strobe, Standard cd. Red PC4W 4 -wire Horr-kStrobe, Standard cd, White
P4RH' 4 -wire Horn /Strobe, High cd, Red PC4WH 4 -wire Florrt/Strobe. Highs cd, Wltiite
P4RK 4-wire Horn/Strobe, Standard cd, Red, Outdoor Ceiling Strobes
P4RHK 4 -wire Horn/Strobe, High cd, Red. Outdoor SCR* Strobe, Standard cd, Red
p4W* 4 -wire Horn/Strobe. Standard cd, White SCRI1* Strobe, High cd, Red
P4W A* 4 -wire Horn /Strobe, High cd. White SCRK Strobe, Standard cd, Red, Outdoor
Wall Strobes SCRHK Strobe, High cd, Red, Outdoor
51 ?* Strobe, Standard cd, Red SCW *' Strobe. Standard cd, Whxte
SRH *' Strobe, High cd, Red CCWI ^" Strobe, High cd, White
SRK Strobe, Standard cd, Red, Outdoor Homs
SRIiK Strobe, Fligh cd, Red, Outdoor HR Horn, Red
SW* Strobe, Standard cd, White HRK Horn, Red, Outdoor
SWi I* Strobe, I sigh cd. White HW Horn, White
Ceiling Horn /Strobes Accessories
PC2R* 2-wire Horn/Strobe. Standard cd, Red BBS -2 Hack Box Skirt. Wail, Red
PC2RH' 2 -wire Horn /Strobe„ High cd, Red BBSW -2 Back Box Skirt, Wall, White
PC2RK 2 -wire Horn /Strobe, Standard cd, Red, Outdoof BBSC -2 Back Box Skirt, Ceiling, Red
PC2RHK 2 -wire Hom/Strobe, High cd, Red, Outdoor BBSCW2 Back Box Skirt, Ceiling, White
Notes:
' Add " -P "to model number for plain housing (no'FIRE "marking on cover), e.g., P2R -P
t Add' -SP" to model number for "f UEGO'rnarking on cover, e.g., P2R-SP
t "Standard cd," refers to strobes that include 15,15/75,30,75,95, 114, and 115 candela settings.'HPgh cd; refers to strobes that Include 135, 150, 177, and 185
candela settings.
AlI outdoor unn�i t 1s en 'dingr/n "K"include a weatherproof back box.
SENSOR
SENSOR Phone -80 - SENSOR2 "Fax: 630 -3777- 6495 min* nliwrnmxvs .rct�rgrn:wwu+..irdmnrmc *wrr
YYY /A]S+IIl9`rp4� 7 71[*f -1 � u7c
BATTERY CALCULATIONS
STANDBY
SK -5700
SK -M IM
5K- PULL STATION
SK- SMOKE
P211 15/30CD
15CD STROBE ONLY
P2R 75CD
P2R 110CD
DEV'IC'ES CURRENT CURRENT TOTAL (STANDBY
SUM COLUMN FOR: 0.805
TOTAL ALARM
0.325
0.1.65
0.385
0.055
0.316
0.462
0.704
1.696
TOTAL
STANDBY
ALARM
TOTAL
1
0.2
0.325
0.2
3
0.055
0.055
0.165
7
0.055
0.055
0.385
1
0.055
0.055
0.055
4
0
0.079
0
7
0
0.066
0
4
0
0.176
0
8
0
0.212
0
SUM COLUMN FOR: 0.805
TOTAL ALARM
0.325
0.1.65
0.385
0.055
0.316
0.462
0.704
1.696
TOTAL
LOAD
REQUIREMENTS
TOTAL
STANDBY LOAD (AMPS)
0.805
24
19.32
ALARM LOAD (AMPS)
4.108
0.0833
0.342196
BATTERY AMP HOUR: 19.6622
TOTAL AMP HOURS REQUIRED: 23.59464
* Batteries will be 2 18amp /hr batteries
x