08-0045 Fire Alarm System 013108MyffY
E L E C T K/ C Inc_
COMMERCIAL•I N DUSTRIAL
Kirby Electric Inc.
PROPOSAL
4826 "B" St. NW Ste. 101 Telephone 12531 B59 -2000
Auburn, WA 98001 Fm (2531859-2363
SUBMITTALS FOR
CREEK ST. PLAZA BLDG. A
1304 YELM AVE. SE
YELM, WA
FIRE ALARM SYSTEM
SILENT KNIGHT 5700 ADRESSABLE PANEL
SILENT KNIGHT ADRESSABLE SMOKE DETECOR
SILENT KNIGHT ADRESSABLE PULL STATION
SYSTEM SENSOR HORN /STORBES
SYSTEM SENSOR STROBE ONLY
SYSTEM SENSOR MODULE
PLANS
BATTERY CALCULATIONS
VOLTAGE DROP CALCULATIONS
January 30, 2007
DEREK MCCOY
KIRBY ELECTIC
4826 B ST. NW, STE. 101
AUBURN, WA 98001
253.859.2000
RECEIVED
JAN 312008
N
C
IntelliKnight® Model 5700
Single Loop Addressable
Fire Alarm Control System
The affordable addressable fire alarm
control panel solution.
IntelliKnight Model 5700 is a 50 point class leading single loop
addressable fire alarm control /communicator system. 5700 provides you
with the revolutionary value and performance of addressable sensing
technology combined with exclusive, built -in digital communication,
distributed intelligent power, that includes an easy to use interface. Powerful features such as drift compensation
and maintenance alert are delivered in this powerful FACP from Silent Knight.
For more information about the IntelliKnight system, or to locate your nearest source, please call
1- 600 -446 -6444, or in Minnesota, call 763 -493 -6435.
Description
5700 performs drift compensation and
calibration checks on each of the
sensors in the system.
The basic IntelliKnight 5700 system
can be enhanced by adding modules
such as 5860 remote annunciator,
5824 serial /parallel printer interface
module (for printing system reports),
and 5496 intelligent power module.
5700 also features a powerful built -in
dual line fire communicator that allows
for reporting of all system activity to a
remote monitoring location.
Features
• Up to 50 addressable points
• Up to 125 zones and 125 output
groups
• Uses standard wire --no shielded or
twisted pair required
• Buift4n digital communicator.
• Central station reporting by point or
by zone
• Supports Class B (Style 4) and Class
A (Style 6 or 7) configuration for SLC
• Distributed, intelligent power
• Drift compensation
• 13 pre - programmed output cadences
(including ANSI -3.41) and 4
programmable outputs
• Notifcation circuits configurable as 1
Class A (Style Z) or 2 Class B (Style
Y), or auxiliary power for resettable,
constant, or door holder power
• Built -in synchronization for AMSECO,
Gentex®, Faraday, System Sensors
and Wheelock@ appliances
• Built-in annunciator with 80- character
LCD display
RS-485 bus provides communication
to system accessories
• Upload or download programming,
event history, or detector status
onsite or from a remote location
using a PC and 5660 Silent Knight
Software Suite (SKSS)
• Improvements in SKSS deliver five
times faster upload /downloads
• Built-in RS -232 interface for
programming via PC
Built -in Form C trouble relay rated at
2.5A at 27.4 VDC
• Two built -in Form C programmable
relays rated at 2.5A at 27.4 VDC
• Programmable date setting for
Daylight Saving Time
Electrical Specifications
Primary AC: 120 VAC, 60 Hz, 1.5A
Total Accessory Load: 2.5A @ 27.4
VDC
Notification Power: 2.5A @ 27.4 VDC,
power - limited
Standby Current: 200 mA
Alarm Current: 325 mA
Notification /Aux Power Circuits:
2.5A @ 27.4 VDC per circuit,
power - limited
Battery Charging Capacity: 7.0 -35.0 AH
Battery Size: 7 AH max. allowed in
FACP cabinet. Larger capacity
batteries can be housed in an RBB
accessory cabinet.
Mechanical Specifications
Dimensions:
12.75'W x 15.2 "Hx3.4'D
(32.39 W x 38.42 H x 8.57 D cm)
Weight: 11.5 Ibs.(5.2 kg)
Color: Red
MOdel 57DO
Telephone Requirements
FCC Part 15 and Part 68 approved
Type of Jack: RJ31X (two required)
Approvals
NFPA 13, NFPA 15, NFPA 16, NFPA
70, 8 NFPA 72: Central Station;
Remote Signalling; Local Protective
Signalling Systems; Auxiliary Protected
Premises Unit; & Water Deluge
Releasing Service. Suitable for
automatic, manual, waterfow, sprinkler
supervisory (DACT non - coded)
signalling services.
Other Approvals: UL Listed;
CSFM 7170- 0559:144;
MEA 429 -92 -E Vol. XVL
SILENT
KNIGHT
by Honeywell
SLC Detectors
S0505 -APS
Addressable photoelectric smoke detector.
SD505 -AIS
Addressable ionization smoke detector.
SD505 -AHS
Absolute temperature heat detector Nat
goes into alarm immediately if the
temperature exceeds the programmable trip
point. Trip point range Rom 135T -15TF
(0- C -3PC).
SD505 -6AB
Six inch base for use with detector heads
SD505 -APS, SD505 -AIS and SD505 -AHS.
SD505-4AB
Four inch base for use with detector heads
SD505 -APS, SD505 -AIS, and SD505 -AHS.
SDSO5 -BSB
Six -inch sounder base hr use with existing
sensor and base. Operates in single and
multi - station modes and/or as a system
sounder Requires 2 additional wires for
power.
SD505-61B
Short circuit isolator base for SD505 -AHS,
SD505 -APS, and SD505 -AIS rated...
SDSO"RB
Six -inch relay base for use with existing
sensor and base. Provides one Form C
co md.
SD505-ADH
Dud housing that date= smoke in HVAC
ducts,
SD505 -ADHR
Dud detector base with relay. Provides
Form C alarm contact. For use with
SD505 -APS and 50505 -AIS sensors.
Compatible with SD508 -DTS remote test
switch.
SD50g- PS /SD500 -PSDA
SD5W-PS is a single action pull station and
SD500 -PSDA is a dual action pull station.
SLC Modules
Model SD500 -AIM
Dry contact input module for use with
normally open dry contacts. It features an
indicator LED W show alarm status.
SDS00 -MIM
Mini dry contact input module is a small
version of the SD500 -AIM. For use with pull
stations and other normally open dry contact
inputs.
SD500 -ANM
Addressable notification module providing a
single Class A or Class B notification circuit
on the SLC.
50500 -ARM
Addressable relay module that features two
Form C output relays. Provides indicator
LED to show output status.
SDS00 -SDM
Two -wire detector input module. Allows for
the connection of conventional 2 -wire
detectors on the SLC loop. Requires two
additional wires for power.
SD500 -LIM
A short circuit isolator module for SLC
devices. When a short occurs on the SLC
loop, it is detected as a trouble, but all SLC
devices protectetl by the isolator module
continue to operate.
50500 -LED
An LED driver capable of driving 80 LEDs
through the SLC Icop. Up to 40
SD500 -LEDs can be used per system.
S -BUS Accessories
5860 /R Remote Fire Annunciator
Features the same 80 character backlit LCD
display keypad and firefighters key switch
as the 5700. The system can be fully
programmed and operated from any 5860.
5860 is gray and 5860R is red.
5496 Intelligent Power Module
A 6 amp notification power expender that
provides four additional power - limited
notification appliance circuit outputs.
5880 LED00 Module
Features 40 LED
outputs, 8 normally
open dry coread inputs
and one piezo output.
58653 and 5865-4
Remote LED
Annunciator
Features 30 zi
Programmable LED (15
red and 15 yellow) outputs and a piezo
sounder. The 5865,1 adds a silence and
reset switch to the package.
5883 Relay Board
Features 10 general purpose Form C relays.
Used with 5880 module.
5824 Serial /Parallel Printer
Interface Module
Provides one parallel and one RS -232 serial
port for connecting a printer to 5808. Use to
print a real -time log of system events,
detector status reports, and event history.
Interfaces with building control system.
Miscellaneous Accessories
5660 Silent Knight Software Suite
User - friendly Windows software for remote
programming of 5700s using a PC. Upload
and vies panel account information, event
history, and detector status.
5670 Silent Knight Software Suite
End -user facility management software
allows viewing of detector status and event
history As modem or direct connection.
RIBS
Remote Battery Box Accessory Cabinet. Use
if backup batteries are too large to fit into
FACP cabinet. Dimensions:
16- Wx10 -H x6-D
(406 mm W x 254 mm H x 152 mm D)
SD505 -DTS
Remote test switch that provides remote key
operated test function and annunciation of
detector alarm with SD505 -ADHR.
SILENT This document is not intended to be used for installation purposes. We by to
®.KNIGHT keep our product information up-to -date and accurate. We cannot cover all
specific applications or anticipate all requirements. All specifications are
subject to change without notice. For more information, contact Silent Knight
4.+ b/ Honeywell 7550 Meridian Circle Suite t W, Maple Grove, Mn 553694927.
Phone. (800)328 -0103. Fax: (763)493 -6475.
IntelliKnight 8 JumpStart are Registered Trademarks of Silent Knight
Flexput is a Trademark of Silent Knight
MADE IN AMERICA
FORMA 350392 Rev. D, 04106
Copyright 0 2006 Silent Knight
Addressable ,
Photoelectric Type
Smoke Detector
Detect smoldering fires quickly and get
help fast with IntelliKnight® photoelectric
smoke detectors.
IntelliKnight addressable photoelectric smoke detectors are the clear choice for commercial settings where
smoldering fires are a threat. In addition to accurately detecting a smoldering fire, each SD505 -APS
photoelectric detector has a unique address, which is recognized by the IntelliKnight panel. No precious seconds
are wasted in determining location of an alarm.
The SD505 -APS compensates automatically for contamination in the environment. And detector testing is
simple even from a remote site. Like other IntelliKnight detector models, the SD505 -APS offers a low profile for
pleasing aesthetics. The IntelliKnight family of detectors has been designed to use a common base, Model
SD505 -6AB, allowing complete application and placement flexibility. Combine all this with the features you've
come to expect from Silent Knight smoke detectors —easy installation, stable operation, RF /transient protection,
and vandal - resistant locking —and it adds up to a flexible solution for all your fire protection needs.
Model SD505 -APS
Analog / Addressable
Photoelectric Type
Smoke Detector
The SD505 -APS is particularly
suited to detecting dense smoke
typical of fires involving materials
such as soft furnishings, plastic,
foam or other similar materials
which tend to smolder and produce
large visible particles.
The detector features automatic
compensation for contamination
and a simple detector calibration
test procedure that can be run from
the panel or remotely (using the
WindowsT based downloading
software).
Operation
The SD505 -APS units made up of
an LED light source and a silicon
photo diode receiving element. In a
normal standby condition, the
receiving element receives no light
from the pulsing light source. In the
event or fire, smoke enters the
detector and light is reflected from
the smoke particles to the receiving
element.
The light received is converted into
an electronic signal. Under normal
conditions, the status LED blinks
approximately every 15 seconds,
indicating that the head is
communicating with the loop. The
LED lights continuously during the
alarm period.
Features
• Low profile, 2 inches, including
base
• Simple and reliable addressing
without mechanical switches
• Automatic compensation for
sensor contamination
• Built -in fire test feature
• Simple detector calibration
testing through the control panel
or remotely through a
WindowsTm based computer
software.
• Vandal- resistance locking
features
• Field cleanable
• UL listed, meets NFPA 72 Ch 7
requirements
• CSFM approved
• MEA approved
• FM Approved
LY
SD505 -APS Smoke Detector
Specifications
Operating Voltage: 17-41 VDC
Current Consumption:
Standby:
.55 mA
Alarm:
.55 mA
Ambient Temperature: 32°F to 120 °F
(0^C to 49^C)
Mounting:
4" Square, 4"
OCT. Single
gang mud ring
Relative Humidity:
85%
noncondensing
Air Velocity: 0 - 300 FPM
Compatible Bases: SD505 -6AB
(Sold Separately) (6" Base)
SD505.4AB
(4" Base)
SILENT
KNIGHT
by Honeywell
Model SD505 -APS
Addressable Photoelectric Type
Smoke Detector
Engineering Specifications
The contractor shall furnish and install where indicated on the plans, addressable photoelectric smoke detector
Silent Knight SD505 -APS. The combination detector head, and twist -lock base, shall be UL® listed compatible
with Silent Knight's IntelliKnight fire control panels.
The base shall permit direct interchange with Silent Knight SD505 -AIS Ionization Smoke Detector, or SD505-
AHS Heat Detector. Base shall be the appropriate twist -lock base SD505 -6AB.
The smoke detector shall have a flashing status LED for visual supervision. When the detector is actuated, the
flashing LED will latch on steady. The detector may be reset by actuating the control panel reset switch.
The calibration of the detector shall be capable of being selected and measured by the control panel without the
need for external test apparatus.
The vandal- resistant, security locking feature shall be used in those areas as indicated on the drawing. The
locking feature shall be field selectable as required.
The SD505 -APS shall automatically perform a functional test of the detector. The test method shall simulate
effects of products of combustion in the chamber to ensure testing of detector circuits.
L01
Model SD505 -6AB Detector Base
(front view)
Diameter= 3- 15116'
o_
• ' 1'
Height • 2 inches,
including base
Model SD505 -APS Detector Head
(front view)
SILENT
This document is not intended to be used for installation purposes. We try to
KNIGHT
keep our product information up-to -date and accurate. We cannot cover all
specific applications or anticipate all requirements. All specifications are
° -°
subject to change without notice. For more information, contact Silent Knight
by Honeywell
7650 Mandan Circe Suite 100, Maple Grove, Mn 553694927.
Phone: (800)328 -0103, Fax: 17631493 -6475.
MADE IN AMERICA
FORM# 350225 Rev C,, 05/05
Copyright ® 2005 Silent Knight
SD500 -PS and SD500 -PSDA
Addressable Pull- Station
IntelliKnight's addressable pull stations
combine fast response with pin -point
location ID.
The SD500 -PS and SD500 -PSDA are a single action or dual action addressable manual fire alarm pull station
for use with Silent Knight's IntelliKnight fire control panel. Extremely easy to operate, the SD500- PS/PSDA
provides a fast and practical means of manually initiating a fire alarm signal. The IntelliKnight panel recognizes
each manual pull station by its specific address saving precious seconds in determining the location of an alarm.
The SD500 -PS /PSDA mounts to a single gang box and features a rugged metal construction that lasts and
lasts.
Combine all this with the features you've come to expect from Silent Knight - easy installation and stable
operation - and it adds up to a flexible solution for all your fire protection needs.
Model SD500 -PS &
SD500 -PSDA
Addressable Pull
Station
The SD500 -PS is a single action
addressable fire pull station, and
the SD500 - -PSDA is a dual action
addressable fire pull station. The
SD500- PS/PSDA feature rugged
metal construction A terminal strip
on back of the pull station allows
interconnection of the pull station to
the SLC of an IntelliKnight control
panel. The SD500- PS/PSDA is
designed for indoor use in non-
explosive environments. The
normally open initiating point
contacts are gold- plated to avoid
risk of corrosion. The SD500-
PS /PSDA has been tested by UL
for compliance to the requirements
of the Americans with Disabilities
ACT (ADA).
Features
• UL Listed
• CSFM listed
• ADA compliant
• Key reset (Same key as Silent
Knight enclosures)
• Surface mount back box
available
Terminals - accept up to 14
gauge wire
• Extremely easy to operate
• Corrosion - resistant gold - plated
contacts.
• Reflective label makes it easier
to locate in low light
Operation
The SD500 -PS /PSDA single action
pull stations are operated by a pull
on the front pull cover of the
station. A plunger switch, wired to
a self contained addressable
module, is released as the pull
station opens to initiate the alarm.
Once operated, the cover hangs
down and can be seen up to 100
feet away. The pull station is reset
by returning the front cover to the
normal upright position and
relocking the station with a reset
key. The reset keys are the same
keys used on Silent Knight
enclosures.
The SD500 -PS /PSDA includes a
status LED which blinks, indicating
that the addressable module is
communicating with the loop. The
status LED lights continuously
during an alarm. A dip switch on
the addressable module is used to
set the unique address.
Specifications
Operating Voltage: 24VDC
Standby Current 55mA
Alarm Current: .55mA
SD500 -PS
Ambient Temperature: 32 -F to 120 -F
(WC to 49 °C)
Mounting: Single gang
box -
Optional Red Sudace Mount Box P&SMBB
SILENT
KNIGHT
SD500 -PS and SD500 -PSDA
Addressable Pull- Station
Engineering Specifications
Manual pull station shall be addressable Module SD500- PS/SD500 -PSDA. Equipment shall be made of 14
gauge C.R.S.(Cold Rolled Steel), painted with a red enamel. The label shall contain the words Fire Alan and
be made of a reflective material embossed text 3/8 inches tall. Operating instruction shall be clearly visible on
the same label. Manual station Shall contain a key operated test and reset lock using a lock plate actuator, the
key shall match the control panel.
Manual station shall contain four terminal blocks with two connected to the addressable module and two connect
to the SLC loop. Manual station shall provide data to the control panel with an ID address programmed by dip
switch settings .
Manual stations shall be Underwriters Laboratories Inc. listed and installed within the limits defined in the
American Disabilities Act.
R
r
III I
�C-0
Mounting to Single Mounting to Optional
Gang Electrical Box Surface Mount Box
tVlf
SD500 -PSDA
I
Installing SD500 -LK
SILENT
KNIGHT
7550 Meridian Circle, Maple Grove, MN 55369 -4927
800 - 446 -6444 or in Minnesota 763- 493 -6435
FAX 763- 493 -6475
World Wide Web: httpWrivin .silentknighLCOm
e Wiwi �a..Ynr
N'P-r
Dimensions °
MADE IN AMERICA
FORM# 3503x2, Re, 09103
Copyright 0 2003 Silent Knight
Wiring
xnrr
e Wiwi �a..Ynr
N'P-r
Dimensions °
MADE IN AMERICA
FORM# 3503x2, Re, 09103
Copyright 0 2003 Silent Knight
f� SYSTEM
Z4 SENSOR
Selectable Output
Horns, Strobes, and
Horn /Strobes
SpectrAlert'Advance selectable- output horns, strobes,
and horrvstrobes are rich with features guaranteed to
cut installation times and maximize profits.
The SpectrAll Adlrana swMs of notification appliances is
designed to simplify installations, with features such as plug in
0 designs, instant feedback messages to ensure correct installation of
individual devices, and 11 field - selectable candela settings for wall
and ceiling strobes and horNetrobes.
When installing Advance products, first attach a universal mounting
plate to a four -inch square, four inch octagon or double -gang
junction box. The two -wire mounting plate attaches to a single -gang
junction box.
Next, connect the notification appliance circuit wiring to the SEMS
terminals on the mounting plate.
Finally, attach the horn, strobe or horn/strobe to the mounting plate
by Inserting the product's tabs in the mounting plate's grooves. The
device will rotate into position, locking the product's pins into the
mounting plate's terminals. The device will temporarily hold in place
with a catch until it is secured with a captured mounting screw.
The SpectrAlert Advance series includes outdoor notification
appliances. Outdoor strobes and horn7strobev (two wire and four
wire) are available for wall or ceiling. Outdoor horns are available for
wall only. All System Sensor outdoor products are rated between
minus 40 degrees Fahrenheit and 151 degrees Fahrenheit in wet or
dry applications.
N
Features
• Electrically compatible with existing SpectrAlert products
• Automatic selection of 12 -or 24-volt operation at 15 and 15/75
candela
• Plug -in design
• Field selectable candela settings on wall and ceiling units: 15,15/75,
30, 75, 95,110,115,135, 150,177,185
• Same mounting plate for wall- and ceiling -mount units
• Shorting spring on mounting plate for continuity check before
installation
• Tam per resistant construction
• Outdoor wall and ceiling products rated from -4TF to 151 °F
• Design allows minimal intrusion into the back box
Horn rated at 88 +dbA at 16 volts
• Rotary switch for horn tone and three volume selections
• Outdoor products UL listed to UL 1638 (strobe) and UL464 (horn)
outdoor requirements
• Outdoor products rainproof per UL 50 (NEMA 3R)
• Compatible with MDL sync module
Agency Listings
draxWMa
uL
FM
MEA
orkel
1®
LISTED
arvawev
approved
'..
SpectrAlen Advance horn schoose, and horn /avobee shall mount to a standard � x I:.; inch back box, flinch octagon back box or double e -gang back
box Two -wire products shall also mount to a Single going 2 x4 x 17 /vAreh back box. A universal mounting plate shall be Used for mounting ceiling and wall
Voters. The notification appliance d¢uh win Ing shall terminate at the universal mounting plate. Alva, Sidi Alert Advance products, when used with the
Sync{Trculf Module accessory shall be powered from a nonmded notification appliance circuit output and shall operate on a nominal 12 or 24 volts. When
used with the Syna-C'acun Module, 12 -volt rated notification appliance circuit outputs shall operate between nine and ITS vdb; 24-volt rated notification
appliance credit outputs shall operate between 17 and 33 volts. Indoor Spectoden Advance products shall operate between 32 and 120 degrees Fahrenheit
from a regulated a, or full -wave rectified, unfiltered power supply Strobes and horn /strobes shall have fieldselectable candela settings including 15,15/75.30
75.95. 110, 115,135, 150, 177, 1 U.
strobe
The strobe shall be a System Sensor SpectrNert Advance Model_ listed to Ill 1971 and shall be approved for fire protective semice.The strobe shell be
wired as a primarysignaling notification appliance and romplywith the Americans wish Disabilities Aet requirements for visible signaling appliances, flashing at
I Hzover the strobes entire operating voltage range. The strobe light shall consist of a xenon Flash tube and associated lens/reflectorsyuem
Re horn/strobe robe COrobiro a S
The horn /strobe shall be a System Sensory- sagnAlert Advance Model_ listedpl UAL 1971 and UL 464 and shall be approved for fire protective servfce.
ThehoMSUObeshall bho,aas a pryer the Craning notification apg voltaandR withthe Americans with Disabilities A¢requirementsociateible
Signaling applian<es.f1 he h ,at 1 Hz over the strobe's entire operating voltage range, to Swit a strobe light shall oral tnee- xenon ash tube and associated
lente rnThssystemhiehorn Shall have three
itions itop tionsandheprodutswi shbetweenatemporaltlnee-sand and aesoundporal(cornOnus)
pattern.Theseopnonsare se[ bye multiple position switch.Onfour -wire pmtluas, the strobe shall be powered independently ofMe sountler.The horn on
horn /strobe models shall operate on a coded or non -coded power supply
Outdoor Products
Spec[nAlen Advance outdoor horns, strobes and horNStrobes shall be listed for outdoor use by UL and shall operate between minus 40 degrees and 151
degrees Fahrenheicthe products shall Witted for use with a System Sensor outdoorAVeatherproof back box with half inch and three - fourths inch conduit
entries.
syrchronimtlon Module
The module shall be a System Sensor Synctirmit model MDL listed to UL 464 and shall be approved for fire protective seryl module shall synchronize
O 5peccouen strobes at l HZ and horns at temporal three. All while operating the st robes, the module shall silence the horns on horNS[robe models over
single pair of wires The module shall mount to a 411/16 x 4 1/m x 2' /i inch bad box.The module shall also control two Style Y(class By circuits or one Style Z
(doss A) circuit The module shall syndvouide multiple zone, Daisy chaining two or made synchronization modules together will synchronize all me mines they
Notes:
I. full Wave RCaified TWR) voltage is a non regulated, time varying power source that is used on some power supply and panel outputs.
2. P, 5, PC, and SC products will operate at 12V nominal only for 15 and 15/75 cd
N
L
C
UL Current Draw Data
Temporal High I% 155 88 97 112 168 1% 210 218
Temporal Medium 129 152 78 88 103 160 184 202 206
Temporal Low 129 151 76 % 101 160 184 194 201
Nointem;dcal High 142 161 103 112 126 181 203 221 229
Nor,temporal Medium 134 155 85 95 110 166 189 208 216
Non terni Low 132 154 % 90 105 161 IM 202 211
Candela Denting Horn Tones and Sound Output Data
For K series products used atlow temperatures, listed osdi
Faunas must be reduced In so,smance with this table ,..._...__.__,
Temporal
Listed Candela
Candela rating at -40 °F
15
Do not use below 32°F
1595
30
75
95
95
O
8- 17.SVolts
1633yota
115
115
e- 17.5Wha
t5- 33V0lU
15a
Candela
i
MR
Ix
MR
Sound Pattern
dB
K
FWR
DC
FWR
Standard 15'
123
128
66
71
Temporal
High
57
55
69
25
Candela Range 1595-
142
148
77
81
Temporal
Medum
44
49
58
69
31
NA
NA
94
96
Temporal
Low
38
44
44
48
75'
NA
NA
158
153
Non- temporal
High
57
56
69
75
95'
NA
NA
181
176
Norrtemporal
Medium
42
50
60
69
ma
NA
NA
202
195
Nomtemporal
Low
41
44
50
50
115
NA
NA
210
205
Coded
Hqh
57
55
69
75
Temporal High I% 155 88 97 112 168 1% 210 218
Temporal Medium 129 152 78 88 103 160 184 202 206
Temporal Low 129 151 76 % 101 160 184 194 201
Nointem;dcal High 142 161 103 112 126 181 203 221 229
Nor,temporal Medium 134 155 85 95 110 166 189 208 216
Non terni Low 132 154 % 90 105 161 IM 202 211
Candela Denting Horn Tones and Sound Output Data
For K series products used atlow temperatures, listed osdi
Faunas must be reduced In so,smance with this table ,..._...__.__,
8 -17.5 16-33
Switch Volts Volts
Pasition Sound Patnm dB a fail a
2
Temporal
Listed Candela
Candela rating at -40 °F
15
Do not use below 32°F
1595
30
75
95
95
O
Ila
110
115
115
135
76
15a
0
177
77
185
185
8 -17.5 16-33
Switch Volts Volts
Pasition Sound Patnm dB a fail a
2
Temporal
Medium
74
74
%
80
%
m
95
96
3
Temporal
Low
71
73
76
76
83
80
94
89
4
Norrtemporal
High
82
82
88
98
93
92
100
100
5
Norntemporal
Medium
78
78
85
85
90
90
98
98
6
Noretemporal
Low
75
75
81
81
88
84
95
92
7'
Cooled
High
82
82
88
88
93
92
101
101
81
Coded
Medium
76
78
85
85
SO
90
97
%
9'
Ceded
Low
75
75
81
81
88
85
96
92
15ectings 7,8, and 9 are not available on 2 -wire horNSttobe
C
SpectrAlert Advance Dimensions
Sfi
Wall-mi hohn/sttobes
Wall back box skirt Ceiling back box skirt
SpectrAlert Advance Ordering Information
Wall weatherproof back box calling weatherproof back box
Ceiling HorNStrobes (conVd.)
PC2W^ 2 -wire HoMStrobe, Standard cd, White
PC2WH^ 2 -wi1e Hiaw5trobe, High cd, Mine
Wall Strobes
5R^
Strobe, Standard cd, Red
SRH't
Strobe, High cd, Red
SRK
Strobe, Standard cd, Red. Outdoor
SRHK
Strobe, High cd, Red, Outdoor
SW Strobe,
Standard cd, White
SWH'
Strobe, High on, White
Ceiling HO trobes
PC2R'
2 -wire HoMStrobe, Standard cd, Red
PC2RH'
2,,m HOrNStrobe, Hach cd, Red
PORK
2wna Horn/Stnobe, Standard od, Red, Outdoor
PC2RHK
2-wire H.mrSadbe, High Per Red, Outdoor
BE Back Bid Skirt, Wa11,Red
BB5W -2 Back Box Skirt Well,White
BBSC -2 Back Box Skirt, Ceiling. Red
BBSCW -2 Back Be. Skirt, Ceiling. Whhe
HRes:
' Add ' -F'to model number for plain housing (no FIRE'marking on cover), mg., P2R -P
t Mel' SP'to model number for FUEGO'marking on co er, e.g. P2R -SP
3'Stardad cdf refers to strobes that include 15.1595130175,95, 110, arM 115 candela settlngs.Fllgh cd' refers to strobes that Include 135,150,177, and 1 BS
candela settings.
Al outdoor units ending in'rindude a weatherproof back box.
SYSTEM
3825 Mao Avenue• 5t, Charles, IL Wp4
SE/VSOR Phone80USENSOR2•EaZ6 377fi495
BATTERY CALCULATIONS
STANDBY
DEVICES
CURRENT
CURRENT
TOTAL(STANDBYI
TOTAL (ALARM)
24
19.32
STANDBY
ALARM
0.0833
0.342196
SK -5700
1
0.2
0.325
0.2
0.325
SK -MIM
3
0.055
0.055
0.165
0.165
SK -PULL STATION
7
0.055
0.055
0.385
0.385
SK -SMOKE
1
0.055
0.055
0.055
0.055
P2R 15 /30CD
4
0
0.079
0
0.316
15CD STROBE ONLY
7
0
0.066
0
0.462
P2R 75CD
4
0
0.176
0
0.704
P2R 110CD
8
0
0.212
0
1.696
SUM COLUMN FOR:
0.805
4.108
TOTAL
LOAD
REQUIREMENTS
TOTAL
STANDBY LOAD (AMPS)
0.805
24
19.32
ALARM LOAD (AMPS)
4.108
0.0833
0.342196
BATTERY AMP HOUR: 19.6622
TOTAL AMP HOURS REQUIRED: 23.59464
* Batteries will be 2 18amp /hr batteries