08-0004 Hydralic Calcs.December 31, 2007
Mr. Gary Carlson
Building Official
City of Yelm
P.O. Box 479
Yelm, WA 98597
TOWNZEN & ASSOCIATES
FIRE & BUILDING CODE SOLUTIONS
RE: Fire Sprinkler
Creek Street Plaza Building A
Dear Gary:
qqµ.,
JA44
The project listed above is approved for release of the permit; with no red line
comments noted on the plans.
If you have any questions, please give me a call.
Sincerely,
Townzen & Associates
es ownzen, FPS
President
410 11th AVE SE, SUITE 202 * OLYMPIA, WA 98501 * TEL: 360- 754 -2335 * FAX: 360- 754 -7722
www.townzen-consulting.com
5F5
SMITH FIRE SYSTEMS, INC.
1106 54th Avenue East Tacoma, Washington 98424
(253) 926 -1880 FAX (253) 926 -2350
CONTR. REG. NO. SMITHFS1360T
HYDRAULIC CALCULATION INFORMATION SHEET
PROJECT NAME CREEK STREET PLAZA BUILDING A JOB NO. TC7040
DATE 11/27/07
ADDRESS 1304 YELM AVE. E. BY JAMES NULL
YELM, WA. 98597
SYSTEM DESIGNATION: WET SYSTEM
HAZARD DESCRIPTION: FUTURE SHOPS
HAZARD CLASS PER NFPA 13: ORDINARY GROUP 2
SPECIFIC RULING:
RULING MADE BY: OF
DENSITY: .20 GPM OVER THE MOST HYDRAULICALLY REMOTE 1036 SQ. FT. (16' -0.5" ROOF)
ALLOWANCES INCLUDED IN CALCULATIONS: ADDED AT:
INSIDE HOSE GPM
OUTSIDE HOSE 250 GPM CITY CONNECTION
IN -RACK SPRINKLER DEMAND GPM
SYSTEM TYPE: WET TOTAL NUMBER OF SPRINKLERS THIS SYSTEM 180
"C" FACTOR OVERHEAD : 120 "C" FACTOR UNDERGROUND: 140
MAXIMUM ACTUAL AREA OF COVERAGE PER SPRINKLER: 121.50 SQUARE FEET
SPRINKLER MANUFACTURER: RELIABLE MODEL: F1 FR TEMPERATURE: 200 ° F
K- FACTOR: 8.0 ORIFICE SIZE: 17/32"
WATER SUPPLY:
STATIC 50 PSI
RESIDUAL 40 PSI
FLOW 1100 GPM
ELEVATION OF TEST:
DATE OF TEST: 2004
DATA PROVIDED BY: CITY OF YELM
LOCATION OF TEST: 106T" STREET AND NE CREEK STREET
BASE OF RISER DEMAND
266.59 GPM REQUIRED AT 32.35PS1
(INCLUDING 0 GPM FOR HOSE STREAMS)
SUMMARY
516.59 GPM REQUIRED AT 38.71 PSI
AT CONNECTION TO TEST HYDRANT
(INCLUDING 250 GPM FOR TOTAL HOSE STREAMS)
�,,,•C � s
o �w �L
nre a 3604
r - ell
SWIM
CERTIFICATE OF COMPETENCY STAMP
U)
a_
Z
W
W
U)
W
rr
a_
VOLUME IN GPM X 110
WATER SUPPLY DATA
JOB NAME
CREEK STREET PLAZA
S
STATIC
50 PSI
ADDRESS
1304 YELM AVE. E.
YELM, WA. 98597
RESIDUAL
40 PSI
JOB NO.
TC7040
90
SMITH FIRE SYSTEMS, INC.
FLOWING
1100 GPM
SYSTEM /AREA
TREE
'
1
S YSTEM DEMAND @ BASE OF RISER
t
266.59GP M A S 32.3 PS I
( INCLUDES 0 GPM FORHOSE STREAMS )
;
I
1
T
-- -
SYSTEM DEMAND @ CITY CONNECTION
—
-
i-
2
E
516.59 GPM AT 38.71 PSI
70+
.
(IN CLUDES 250 GPM TOTAL HOSE STREAMS)
t
,
4-.
T
T
t
gn
i
Tr
-
—
r
i
f
'
j
0 1
2 3
4 5
6
7
8
9
10
VOLUME IN GPM X 110
SUBMITTAL SERIAL NO:2244HY1
CREEK STREET PLAZA TREE .20/1036
TC7040
ORDINARY GROUP 2 (MERCANTILE)
CRKPLAI
FLOW TEST RESULTS
Water Supply
STATIC
50.00 PSI
RESIDUAL
40.00 PSI
@ 1100.00
GPM
CITY
PRESSURE
AVAILABLE
AT 516.6
GPM
SUMMARY
OF SPRINKLER OUTFLOWS
ACTUAL
MINIMUM
SPR
FLOW
FLOW
K- FACTOR PRESSURE
- --
301
- - --
25.75
- - --
24.30
-- - - - - -- --
8.00
- - - - --
10.36
302
25.05
24.30
8.00
9.81
303
24.59
24.30
8.00
9.44
304
24.36
24.30
8.00
9.27
305
24.30
24.30
8.00
9.23
306
28.74
24.30
8.00
12.90
307
28.50
24.30
8.00"
12.69
308
28.42
24.30
8.007
12.62
309
28.42
24.30
8.00
12.62
310
28.47
24.30
8.00
12.67
TOTAL WATER REQUIRED FOR SYSTEM
OUTFLOWS AT 3
TOTAL WATER REQUIREMENT
PRESSURE REQUIRED AT 0
MAXIMUM PRESSURE UNBALANCE IN LOOPS
MAXIMUM VELOCITY FROM 10 TO 21
47.53 PSI
266.59 GPM
250.00 GPM
516.59 GPM
38.71 PSI
0.00 PSI
14.84 FPS
11 -26 -2007 PAGE 1
SUBMITTAL
SERIAL NO:2244HY1
11
-26 -2007 PAGE 2
CREEK STREET
PLAZA
TREE .20/1036
TC7040
ORDINARY
GROUP 2 (MERCANTILE)
CRKPLAI
Location
Flow
Pipe
Fittings
Equiv
Friction Pressure
in
Size
&
Length
Loss
Summary
From To
GPM
IN
Devices
Ft
PSI /Ft
PSI
304 305
2.185
L
9.00
C =120
PT
9.23
(305)
Q
24.30
F =O
F
0.00
PE
0.00
BN
T
9.00
0.0052
PF
0.05
303 304DQ
24.36
2.185
L
9.00
C =120
PT
9.28
(304)
Q
48.66
F =0
F
0.00
PE
0.00
BN
T
9.00
0.0189
PF
0.17
302 303DQ
24.59
2.185
L
9.00
C =120
PT
9.45
(303)
Q
73.25
F =0
F
0.00
PE
0.00
BN
T
9.00
0.0403
PF
0.36
301 302DQ
25.05
2.185
L
8.00
C =120
PT
9.81
(302)
Q
98.30
F =0
F
0.00
PE
0.00
BN
T
8.00
0.0695
PF
0.56
34 301DQ
25.75
2.185
L
39.75
C =120
PT
10.37
(301)
Q
124.05
F =0
F
0.00
PE
0.00
BN
T
39.75
0.1068
PF
4.25
PT
14.62
( 34)
---------------
308 309
- --
2.185
L
9.00
C =120
PT
12.62
(309)
Q
1.89
F =O
F
0.00
PE
0.00
BL
T
9.00
0.0000
PF
0.00
307 308DQ
28.42
2.185
L
9.00
C =120
PT
12.62
(308)
Q
30.31
F =0
F
0.00
PE
0.00
BL
T
9.00
0.0079
PF
0.07
306 307DQ
28.50
2.185
L
8.00
C =120
PT
12.69
(307)
Q
58.80
F =0
F
0.00
PE
0.00
BL
T
8.00
0.0268
PF
0.21
35 306DQ
28.74
2.185
L
39.75
C =120
PT
12.90
(306)
Q
87.54
F =0
F
0.00
PE
0.00
BL
T
39.75
0.0561
PF
2.23
207 35DQ
-61.49
2.185
L
132.25
C =120
PT
15.13
( 35)
Q
26.05
F =T
F
14.00
PE
0.00
BL1
T
146.25
0.0060
PF
0.88
208 207
2.185
L
9.00
C =120
PT
16.01
(207)
Q
26.05
F =0
F
0.00
PE
0.00
BL1
T
i
9.00
0.0060
PF
0.05
SUBMITTAL
SERIAL
NO:2244HY1
11 -26 -2007 PAGE 3
CREEK STREET
PLAZA TREE .20/1036
TC7040
ORDINARY
GROUP 2
(MERCANTILE)
CRKPLAI
Location
Flow
Pipe
Fittings
Equiv
Friction
Pressure
in
Size
&
Length
Loss
Summary
From To
GPM
IN
Devices
Ft
PSI /Ft
PSI
209 208
2.185
L
9.00
C =120
PT
16.06
(208)
Q
26.05
F =0
F
0.00
PE
0.00
BL1
T
9.00
0.0060
PF
0.05
210 209
2.185
L
6.00
C =120
PT
16.11
(209)
Q
26.05
F =0
F
0.00
PE
0.00
BL1
T
6.00
0.0060
PF
0.04
211 210
2.185
L
7.50
C =120
PT
16.15
(210)
Q
26.05
F =0
F
0.00
PE
0.00
BL1
T
7.50
0.0060
PF
0.05
212 211
2.185
L
7.50
C =120
PT
16.20
(211)
Q
26.05
F =0
F
0.00
PE
0.00
BL1
T
7.50
0.0060
PF
0.05
45 212
2.185
L
2.08
C =120
PT
16.25
(212)
Q
26.05
F =0
F
0.00
PE
0.00
BL1
T
2.08
0.0060
PF
0.01
PT
16.26
( 45)
---------------
201 34
- --
2.185
L
132.25
C =120
PT
14.61
( 34)
Q
33.69
F =T
F
14.00
PE
0.00
BL1
T
146.25
0.0096
PF
1.40
202 201
2.185
L
9.00
C =120
PT
16.01
(201)
Q
33.69
F =0
F
0.00
PE
0.00
BL1
9.00
0.0096
PF
0.09
203 202
2.185
L
9.00
C =120
PT
16.10
(202)
Q
33.69
F =0
F
0.00
PE
0.00
BL1
T
9.00
0.0096
PF
0.09
204 203
2.185
L
6.00
C =120
PT
16.19
(203)
Q
33.69
F =0
F
0.00
PE
0.00
BL1
T
6.00
0.0096
PF
0.06
205 204
2.185
L
7.50
C =120
PT
16.25
(204)
Q
33.69
F =0
F
0.00
PE
0.00
BL1
T
7.50
0.0096
PF
0.07
206 205
2.185
L
7.50
C =120
PT
16.32
(205)
Q
33.69
F =0
F
0.00
PE
0.00
BL1
T
7.50
0.0096
PF
0.07
SUBMITTAL SERIAL NO:2244HY1 11 -26 -2007 PAGE 4
CREEK STREET PLAZA TREE .20/1036
TC7040
ORDINARY GROUP 2 (MERCANTILE)
CRKPLAI
Location
Flow
Pipe
Fittings
Equiv
Friction
Pressure
in
Size
&
Length
Loss
Summary
From
To
GPM
IN
Devices
Ft
PSI /Ft
PSI
44
206
2.185
L
2.08
C =120
PT
16.39
(206)
Q
33.69
F =0
F
0.00
PE
0.00
BL1
T
2.08
0.0096
PF
0.02
PT
16.41
( 44)
---------------
310
309
- --
2.185
L
7.96
C =120
PT
12.62
(309)
Q
26.53
F =0
F
0.00
PE
0.00
BL
T
7.96
0.0062
PF
0.05
60
310DQ
28.47
2.185
L
1.10
C =120
PT
12.67
(310)
Q
55.00
F =E
F
7.00
PE
0.00
BL
T
8.10
0.0237
PF
0.19
61
60
2.185
L
4.50
C =120
PT
12.86
( 60)
Q
55.00
F =T
F
14.00
PE
1.95
BL
T
18.50
0.0237
PF
0.44
59
61
2.185
L
3.83
C =120
PT
15.25
( 61)
Q
55.00
F =E
F
7.00
PE
0.00
BL
T
10.83
0.0237
PF
0.26
58
59
2.185
L
2.92
C =120
PT
15.51
( 59)
Q
55.00
F =E
F
7.00
PE
0.00
BL
T
9.92
0.0237
PF
0.24
57
58
2.185
L
8.10
C =120
PT
15.75
( 58)
Q
55.00
F =0
F
0.00
PE
0.00
BL
T
8.10
0.0237
PF
0.19
56
57
2.185
L
9.50
C =120
PT
15.94
( 57)
Q
55.00
F =0
F
0.00
PE
0.00
BL
T
9.50
0.0237
PF
0.23
55
56
2.185
L
9.50
C =120
PT
16.17
( 56)
Q
55.00
F =0
F
0.00
PE
0.00
BL
T
9.50
0.0237
PF
0.23
36
55
2.185
L
48.58
C =120
PT
16.40
( 55)
Q
55.00
F =2E
F
14.00
PE
-0.43
BL
T
62.58
0.0237
PF
1.48
26
36DQ
-11.47
2.185
L
3.00
C =120
PT
17.45
( 36)
Q
43.53
F =2T
F
28.00
PE
-1.30
BL
T
31.00
0.0154
PF
0.48
SUBMITTAL SERIAL NO:2244HY1
CREEK STREET PLAZA TREE .20/1036
TC7040
ORDINARY GROUP 2 (MERCANTILE)
CRKPLAI
Location Flow Pipe Fittings
in Size &
From To GPM IN Devices
25 26 2.709
Q 43.53 F =0
CM
------------------
45
36
Friction
2.185
Q
11.47
F =9E
Ft
BL1
44
45DQ
26.05
2.185
C =120
PT
Q
37.52
F
F =0
PE
0.00
CM2
T
43
44DQ
33.69
2.185
Q
71.21
PT
F =0
25)
L
189.41
CM2
PT
42
43DQ
-17.45
2.185
PE
Q
53.75
T
F =0
0.0013
PF
0.33
CM2
L
52
42
PT
2.185
45)
F
Q
53.75
PE
F =2EE
T
13.50
BL1
PF
41
52DQ
-20.24
2.185
C =120
PT
Q
33.52
F
F =T /T
PE
0.00
BL1
T
31
41
PF
2.185
L
Q
33.52
PT
F =E,T
43)
F
0.00
BL1
PE
21
31
T
2.185
0.0227
PF
Q
33.52
L
F =2T
C =120
PT
17.24 (
RN1
F
------------------
33
43
PE
2.185
T
Q
17.45
PF
F =T
L
6.50
BL1
PT
23
33
F
2.185
PE
Q
17.45
T
F =2T'
0.0095
PF
0.33
RN1
L
11 -26 -2007 PAGE 5
Equiv
Friction
Pressure
Length
Loss
Summary
Ft
PSI /Ft
PSI
5.58
C =120
PT
16.63 (
26)
F
0.00
PE
0.00
T
5.58
0.0054
PF
0.03
PT
16.66 (
25)
L
189.41
C =120
PT
17.43 (
36)
F
63.00
PE
-1.52
T
252.41
0.0013
PF
0.33
L
13.50
C =120
PT
16.24 (
45)
F
0.00
PE
0.00
T
13.50
0.0117
PF
0.16
L
13.50
C =120
PT
16.40 (
44)
F
0.00
PE
0.00
T
13.50
0.0383
PF
0.52
L
14.21
C =120
PT
16.92 (
43)
F
0.00
PE
0.00
T
14.21
0.0227
PF
0.32
L
41.00
C =120
PT
17.24 (
42)
F
6.00
PE
0.00
T
47.00
0.0227
PF
1.07
L
6.50
C =120
PT
18.31 (
52)
F
28.00
PE
0.00
T
34.50
0.0095
PF
0.33
L
136.67
C =120
PT
18.64 (
41)
F
21.00
PE
0.00
T
157.67
0.0095
PF
1.50
L
1.50
C =120
PT
20.14 (
31)
F
28.00
PE
0.65
T
29.50
0.0095
PF
0.28
PT
21.07 (
21)
L
173.33
C =120
PT
16.92 (
43)
F
14.00
PE
0.00
T
187.33
0.0028
PF
0.52
L
1.50
C =120
PT
17.44 (
33)
F
28.00
PE
0.65
T
29.50
0.0028
PF
0.08
PT
18.17 (
23)
SUBMITTAL SERIAL NO:2244HY1 11 -26 -2007 PAGE 6
CREEK STREET PLAZA TREE .20/1036
TC7040
ORDINARY GROUP 2 (MERCANTILE)
CRKPLAI
Location
Flow
Pipe
Fittings
Equiv
Friction
Pressure
in
Size
&
Length
Loss
Summary
From
To
GPM
IN
Devices
Ft
PSI /Ft
PSI
------------------
32
52
2.185
L
130.67
C =120
PT
18.31 (
52)
Q
20.24
F =0
F
0.00
PE
0.00
BL1
T
130.67
0.0037
PF
0.48
22
32
2.185
L
1.50
C =120
PT
18.79 (
32)
Q
20.24
F =2T
F
28.00
PE
0.65
RN1
T
29.50
0.0037
PF
0.11
PT
19.55 (
22)
------------------
25
35
2.185
L
1.50
C =120
PT
15.13 (
35)
Q
61.49
F =2T
F
28.00
PE
0.65
RN1
T
29.50
0.0292
PF
0.86
24
25DQ
43.53
2.709
L
13.50
C =120
PT
16.64 (
25)
Q
105.02
F =0
F
0.00
PE
0.00
CM1
T
13.50
0.0276
PF
0.37
PT
17.01 (
24)
------------------
24
34
2.185
L
1.50
C =120
PT
14.61 (
34)
Q
90.37
F =2T
F
28.00
PE
0.65
RN1
T
29.50
0.0594
PF
1.75
23
24DQ
105.02
2.709
L
13.50
C =120
PT
17.01 (
24)
Q
195.38
F =0
F
0.00
PE
0.00
CM1
T
13.50
0.0869
PF
1.17
22
23DQ
17.45
2.709
L
13.50
C =120
PT
18.18 (
23)
Q
212.84
F =0
F
0.00
PE
0.00
CM1
-
13.50
0.1018
PF
1.37
21
22DQ
20.24
2.709
L
12.50
C =120
PT
19.55 (
22)
Q
233.07
F =0
F
0.00
PE
0.00
CM1
T
12.50
0.1204
PF
1.50
PT
21.05 (
21)
------------------
4
3
8.265
L
473.00
C =140
PT
38.58 (
3)
Q
168.99
F= 2EE,2GV,2T
F
142.00
PE
0.00
LU
T
615.00
0.0002
PF
0.12
1
4
10.275
L
15.00
C =140
PT
38.70 (
4)
Q
168.99
F =0
F
0.00
PE
0.00
LU
T
15.00
0.0001
PF
0.00
PT
38.70 (
1)
SUBMITTAL
SERIAL
NO:2244HY1
11 -26 -2007
PAGE 7
CREEK STREET PLAZA TREE .20/1036
TC7040
ORDINARY
GROUP 2
(MERCANTILE)
CRKPLAI
Location
Flow
Pipe
Fittings
Equiv
Friction Pressure
in
Size
&
Length
Loss
Summary
From To
GPM
IN
Devices
Ft
PSI /Ft
PSI
------------------
2 3
8.265
L
43.00
C =140
PT
38.58 (
3)
Q
347.60
F =T,GV
F
58.00
PE
0.00
LU
T
101.00
0.0008
PF
0.08
1 2
10.275
L
180.00
C =140
PT
38.66 (
2)
Q
347.60
F =0
F
0.00
PE
0.00
LU
T
180.00
0.0003
PF
0.05
PT
38.71 (
1)
------------------
10 21
2.709
L
13.71
C =120
PT
21.07 (
21)
Q
266.59
F =2E
F
20.00
PE
0.00
FM1
T
33.71
0.1544
PF
5.20
8 10
3.320
L
12.10
C =120
PT
26.27 (
10)
Q
266.59
F =0
F
0.00
PE
5.24
FR
T
12.10
0.0573
PF
0.69
7 8
3.320
L
0.29
C =120
PT
32.20 (
8)
Q
266.59
F =0
F
0.00
PE
0.13
FR
T
0.29
0.0573
PF
0.02
6 7
6.155
L
202.00
C =140
PT
32.35 (
7)
Q
266.59
F =4EE,E
F
53.00
PE
2.60
UN
T
255.00
0.0021
PF
0.54
5 6
6.000
L
4.00
C =140
PT
35.49 (
6)
Q
266.59
F =DD1
F
0.00
PE
0.00
UN
T
4.00
0.0024
PF
0.01
6" WILKINS MODEL
350DA DOUBLE DETECTOR ASSEMBLY
2.93
3 5
6.155
L
18.00
C =140
PT
38.43 (
5)
Q
266.59
F =GV,T
F
47.00
PE
0.00
UN
T
65.00
0.0021
PF
0.14
PT
35.64 (
3)
------------------
0 1
10.275
L
0.01
C =140
PT
38.71 (
1)
Q
516.59
F =Q
0.00
PE
0.00
UN
T
0.01
0.0006
PF
0.00
PT
38.71 (
0)
SMITH FIRE SYSTEMS, INC.
JOB NO. TC7040
CREEK STREET PLAZA
AUXILIARY CALCULATED AREA # 1
AUXILIARY HYDRAULIC CALCULATION
DESIGN DENSITY: .20 GPM / 1036 SQ. FT.
SYSTEM DEMAND AT BASE OF RISER
246.58 GPM AT 27.17PS1
U)
d
Z
W
Cc
U)
U)
W
VOLUME IN GPM X 110
WATER SUPPLY DATA
JOB NAME
CREEK STREET PLAZA
S
STATIC
50
PSI
ADDRESS
1304 YELM AVE. E.
YELM, WA. 98597
RESIDUAL
40
PSI
JOB NO.
TC7040
SMITH FIRE SYSTEMS, INC.
FLOWING
1 100
GPM
SYSTEM /AREA
GRID
90
1
SYSTEM DEMAND @ BASE OF RISER
246 58 GPM AT 27.17 PSI
�
f
I
( INCLUDES 0 GPM FOR HOSE STREAMS )
...
2.
SYSTEM DEMAND @ CITY CONNECTION
496.58 GPM AT 33.53 PSI
' I
'
(INCLUDES 250 GPM TOTAL HOSE STREAMS)
Rn
I
r --
tc
4
I
HI
I
I
L
I-
i
I
I
,
T
I
I
-
1.
I
...
I I
r
•
I
0 1
2 3 4
5
6
7
8
9 10
VOLUME IN GPM X 110
AUXILIARY SUBMITTAL SERIAL NO:2244HY1
CREEK STREET PLAZA GRID .20/1036
TC7040
ORDINARY GROUP 2 (MERCANTILE)
CRKPLA2
FLOW TEST RESULTS
Water Supply
STATIC 50.00 PSI
RESIDUAL 40.00 PSI @ 1100.00 GPM
CITY PRESSURE AVAILABLE AT 496.6 GPM
TOTAL WATER REQUIRED FOR SYSTEM
OUTFLOWS AT 2
TOTAL WATER REQUIREMENT
PRESSURE REQUIRED AT 0
MAXIMUM PRESSURE UNBALANCE IN LOOPS
MAXIMUM VELOCITY FROM 10 TO 21
47.70 PSI
246.58 GPM
250.00 GPM
496.58 GPM
33.53 PSI
0.00 PSI
13.73 FPS
11 -26 -2007 PAGE 1
SUMMARY
OF SPRINKLER OUTFLOWS
ACTUAL
MINIMUM
SPR
FLOW
FLOW
K- FACTOR
PRESSURE
- --
201
- - --
25.02
- - --
24.30
-- - - - - --
8.00
-- - - - - --
9.78
202
24.96
24.30
8.00
9.73
203
24.96
24.30
8.00
9.73
204
25.00
21.17
8.00
9.77
207
24.38
24.30
8.00
9.29
208
24.30
24.30
8.00
9.23
209
24.30
24.30
8.00
9.23
210
24.33
21.17
8.00
9.25
211
24.49
21.17
8.00
9.37
212
24.84
21.17
8.00
9.64
TOTAL WATER REQUIRED FOR SYSTEM
OUTFLOWS AT 2
TOTAL WATER REQUIREMENT
PRESSURE REQUIRED AT 0
MAXIMUM PRESSURE UNBALANCE IN LOOPS
MAXIMUM VELOCITY FROM 10 TO 21
47.70 PSI
246.58 GPM
250.00 GPM
496.58 GPM
33.53 PSI
0.00 PSI
13.73 FPS
11 -26 -2007 PAGE 1
AUXILIARY SUBMITTAL SERIAL NO:2244HY1 11 -26 -2007 PAGE 2
CREEK STREET PLAZA GRID .20/1036
TC7040
ORDINARY GROUP 2 (MERCANTILE)
CRKPLA2
FROM TO
FLOW
LENGTH
FITTING
DIAM
TYPE
PSI /Ft
S -LOSS
PRESSURES
---------------
210
209
-
20.48
- - --
6.00
0.0
2.185
BL1
0.004
0.00
9.25
9.23
211
210
44.81
7.50
0.0
2.185
BL1
0.016
0.00
9.37
9.25
212
211
69.29
7.50
0.0
2.185
BL1
0.036
0.00
9.64
9.37
45
212
94.14
2.08
0.0
2.185
BL1
0.064
0.00
9.77
9.64
---------------
208
209
-
3.82
- - --
9.00
0.0
2.185
BL1
0.000
0.00
9.23
9.23
207
208
28.13
9.00
0.0
2.185
BL1
0.007
0.00
9.29
9.23
35
207
52.51
132.25
14.0
2.185
BL1
0.022
0.00
12.48
9.29
---------------
203
202
-
0.66
- - --
9.00
0.0
2.185
BL1
0.000
0.00
9.73
9.73
204
203
25.62
6.00
0.0
2.185
BL1
0.006
0.00
9.76
9.73
205
204
50.62
7.50
0.0
2.185
BL1
0.020
0.00
9.91
9.76
206
205
50.62
7.50
0.0
2.185
BL1
0.020
0.00
10.06
9.91
44
206
50.62
2.08
0.0
2.185
BL1
0.020
0.00
10.10
10.06
---------------
201
202
-
24.30
- - --
9.00
0.0
2.185
BL1
0.005
0.00
9.78
9.73
34
201
49.31
132.25
14.0
2.185
BL1
0.019
0.00
12.62
9.78
24
34
49.31
1.50
28.0
2.185
RN1
0.019
0.65
13.84
12.62
---------------
306
35
-
10.15
- - --
39.75
0.0
2.185
BL
0.001
0.00
12.51
12.47
307
306
10.15
8.00
14.0
2.185
BL
0.001
0.00
12.53
12.51
308
307
10.15
9.00
14.0
2.185
BL
0.001
0.00
12.55
12.53
309
308
10.15
9.00
14.0
2.185
BL
0.001
0.00
12.57
12.55
310
309
10.15
7.96
0.0
2.185
BL
0.001
0.00
12.58
12.57
60
310
10.15
1.10
7.0
2.185
BL
0.001
0.00
12.59
12.58
61
60
10.15
4.50
14.0
2.15
BL
0.001
1.95
14.56
12.59
59
61
10.15
3.83
7.0
2.185
BL
0.001
0.00
14.57
14.56
58
59
10.15
2.92
7.0
2.185
BL
0.001
0.00
14.58
14.57
57
58
10.15
8.10
0.0
2.185
BL
0.001
0.00
14.59
14.58
56
57
10.15
9.50
0.0
2.185
BL
0.001
0.00
14.60
14.59
55
56
10.15
9.50
0.0
2.185
BL
0.001
0.00
14.61
14.60
36
55
10.15
48.58
14.0
2.185
BL
0.001
-0.43
14.24
14.61
--------------------
36
45
37.58
189.41
63.0
2.185
BL
0.012
1.52
14.25
9.78
26
36
47.74
3.00
28.0
2.185
RN
0.018
-1.30
13.52
14.25
25
26
47.74
5.58
0.0
2.709
CM
0.006
0.00
13.56
13.52
--------------------
44
45
56.56
13.50
0.0
2.185
CM2
0.025
0.00
10.12
9.78
43
44
107.17
13.50
0.0
2.185
CM2
0.082
0.00
11.22
10.12
42
43
69.14
14.21
0.0
2.185
CM2
0.036
0.00
11.73
11.22
52
42
69.14
41.00
6.0
2.185
BL1
0.036
0.00
13.43
11.73
41
52
37.54
6.50
28.0
2.185
BL1
0.012
0.00
13.83
13.43
31
41
37.54
136.67
21.0
2.185
BL1
0.012
0.00
15.67
13.83
21
31
37.54
1.50
28.0
2.185
RN1
0.012
0.65
16.67
15.67
--------------------
33
43
38.03
173.33
14.0
2.185
BL1
0.012
0.00
13.46
11.21
23
33
38.03
1.50
28.0
2.185
RN1
0.012
0.65
14.46
13.46
AUXILIARY SUBMITTAL SERIAL NO:2244HY1
CREEK STREET PLAZA GRID .20/1036
TC7040
ORDINARY GROUP 2 (MERCANTILE)
CRKPLA2
11 -26 -2007 PAGE 3
FROM
TO
FLOW
LENGTH
FITTING
DIAM
TYPE
PSI /Ft
S -LOSS
--------------------
32
52
31.60
130.67
0.0
2.185
BL1
0.009
0.00
22
32
31.60
1.50
28.0
2.185
RN1
0.009
0.65
--------------------
25
35
42.35
1.50
28.0
2.185
RN1
0.015
0.65
24
25
90.09
13.50
0.0
2.709
CM1
0.021
0.00
23
24
139.40
13.50
0.0
2.709
CMl
0.047
0.00
22
23
177.43
13.50
0.0
2.709
CM1
0.073
0.00
21
22
209.04
12.50
0.0
2.709
CM1
0.098
0.00
--------------------
4
3
110.44
473.00
107.0
8.265
LU
0.000
0.00
1
4
110.44
15.00
0.0
10.275
LU
0.000
0.00
--------------------
2
3
136.14
43.00
58.0
8.265
LU
0.000
0.00
1
2
386.14
180.00
0.0
10.275
LU
0.000
0.00
--------------------
10
21
246.58
13.71
20.0
2.709
FM1
0.134
0.00
8
10
246.58
12.10
0.0
3.320
FR
0.050
5.24
7
8
246.58
0.29
0.0
3.320
FR
0.050
0.13
6
7
246.58
202.00
40.0
6.155
UN
0.002
2.60
5
6
246.58
4.00
0.0
6.000
UN
0.003
0.00
6" WILKINS
MODEL 350DA
DOUBLE DETECTOR
ASSEMBLY
3
5
246.58
18.00
35.0
6.155
UN
0.002
0.00
--------------------
0
1
496.58
0.01
0.0
10.275
UN
0.001
0.00
PRESSURES
14.54 13.43
15.44 14.54
13.55
12.47
13.83
13.55
14.46
13.83
15.44
14.46
16.67
15.44
33.51 33.45
33.51 33.51
33.46 33.45
33.51 33.46
21.19
16.68
27.03
21.19
27.17
27.03
30.37
27.17
30.38
30.37
2.95
33.46
33.33
33.53 33.53
SMITH FIRE SYSTEMS, INC.
JOB NO. TC7040
CREEK STREET PLAZA
AUXILIARY CALCULATED AREA # 2
AUXILIARY HYDRAULIC CALCULATION
DESIGN DENSITY: .20 GPM / 7 SPRINKLERS IN CANOPY
SYSTEM DEMAND AT BASE OF RISER
106.85 GPM AT 17.44 PSI
U)
a_
z
W
U)
w
cr-
CL
VOLUME IN GPM X 110
WATER SUPPLY DATA
JOB NAME
CREEK STREET PLAZA
SSTATIC
50 PSI
ADDRESS
1304 YELM AVE.
E.
YELM, WA. 98597
RESIDUAL
40 PSI
JOB NO.
TC7040
90
SMITH FIRE SYSTEMS, INC.
FLOWING
1100 GPM
SYSTEM /AREA
CANOPY
.:1
:::
is
�
• I
I
1 SYSTEM DEMAND @ BASE OF RISER
}
——
—
106.85 GPM AT 17.44 PSI
- I
_•
( INCLUDES 0 GPM FOR HOSE STREAMS )
-
2 SYSTEM DEMAND (p CITY CONNECTION
-
-
-
356.85 GPM AT 24.77 PSI
( INCLUDES 250 GPM TOTAL HOSE STREAMS)
I
-
-
I
{_.•
-
- -
- --
-�•- -•
: -.I
.l
:.. -.
1
!
-
-�..
T. I'I :...
-_ 1
- -_
-
i I 1. I
`.hViJll..:.
_
I
...
_.
:
...
..._
4
I.
oo
. ...
i
i
.
.
.
.....
1
,
-.
in
t
0 1
2 3
4 5 6
7
8 9 10
VOLUME IN GPM X 110
AUXILIARY SUBMITTAL SERIAL NO:2244HY1 11 -26 -2007 PAGE 1
CREEK STREET PLAZA CANOPY .20/7 HEADS
TC7040
ORDINARY GROUP 2 (MERCANTILE)
CRKPLA2
FLOW TEST RESULTS
Water Supply
STATIC 50.00 PSI
RESIDUAL 40.00 PSI @ 1100.00 GPM
CITY PRESSURE AVAILABLE AT 356.9 GPM 48.75 PSI
SUMMARY OF SPRINKLER OUTFLOWS
ACTUAL MINIMUM
SPR FLOW FLOW K- FACTOR PRESSURE
- -- - - -- - - -- -- - - - - -- -- - - - - --
401 15.55 15.20 5.60 7.71
402 15.35 15.20 5.60 7.51
403 15.24 15.20 5.60 7.40
404 15.20 15.20 5.60 7.37
405 15.19 14.82 5.60 7.36
406 15.17 14.82 5.60 7.34
407 15.16 14.82 5.60 7.33
TOTAL WATER REQUIRED FOR SYSTEM 106.85 GPM
OUTFLOWS AT 3 250.00 GPM
TOTAL WATER REQUIREMENT 356.85 GPM
PRESSURE REQUIRED AT 0 24.77 PSI
MAXIMUM PRESSURE UNBALANCE IN LOOPS 0.00 PSI
MAXIMUM VELOCITY FROM 26 TO 36 6.14 FPS
AUXILIARY SUBMITTAL SERIAL NO:2244HY1
CREEK STREET PLAZA CANOPY .20/7 HEADS
TC7040
ORDINARY GROUP 2 (MERCANTILE)
CRKPLA2
FROM TO
58 404
63 407
62 63
62 406
61 62
59 405
57 403
56 402
55 401
61 59
60 61
310 60
309 310
308 309
307 308
306 307
35 306
207 35
208 207
209 208
210 209
211 210
212 211
45 212
44 45
206 44
205 206
204 205
203 204
202 203
201 202
34 201
24 34
58 59
57 58
56 57
55 56
36 55
43 44
FLOW LENGTH FITTING
15.20 1.92 5.0
15.16 1.92 5.0
15.16 7.50 0.0
15.17 1.92 5.0
30.33 3.67 0.0
15.19 1.92 5.0
15.24 1.92 5.0
15.35 1.92 5.0
15.55 1.92 5.0
7.71 3.38 7.0
38.04 4.50 14.0
38.04 1.12 0.0
38.04 7.96 0.0
38.04 9.00 0.0
38.04 9.00 0.0
38.04 8.00 0.0
38.04 39.75 7.0
38.04 132.25 0.0
38.04 9.00 0.0
38.04 9.00 0.0
38.04 6.00 0.0
38.04 7.50 0.0
38.04 7.50 0.0
38.04 2.08 14.0
35.07 13.50 0.0
4.57 2.08 14.0
4.57 7.50 0.0
4.57 7.50 0.0
4.57 6.00 0.0
4.57 9.00 0.0
4.57 9.00 0.0
4.57 132.25 0.0
4.57 1.50 28.0
7.49 2.92 7.0
22.69 8.10 0.0
37.93 9.50 0.0
53.27 9.50 0.0
68.82 48.58 14.0
30.50 13.50 0.0
11 -26 -2007 PAGE 2
DIAM TYPE PSI /Ft S -LOSS PRESSURES
1.049 AO 0.078 0.00 7.91 7.37
1.049 AO 0.078 0.00 7.87 7.33
2.185 BN 0.002 0.00 7.89 7.87
1.049 AO 0.078 0.00 7.88 7.34
2.185 BN 0.008 0.00 7.91 7.88
1.049 AO 0.078 0.00 7.90 7.36
1.049 AO 0.079 0.00 7.94 7.40
1.049 AO 0.080 0.00 8.06 7.51
1.049 AO 0.082 0.00 8.28 7.71
2.185 CM 0.001 0.00 7.91 7.90
2.185 BL 0.012 -1.95 6.18 7.91
2.185 BL 0.012 0.00 6.19 6.18
2.185 BL 0.012 0.00 6.29 6.19
2.185 BL 0.012 0.00 6.40 6.29
2.185 BL 0.012 0.00 6.51 6.40
2.185 BL 0.012 0.00 6.61 6.51
2.185 BL 0.012 0.00 7.17 6.61
2.185 BL1 0.012 0.00 8.76 7.17
2.185 BL1 0.012 0.00 8.87 8.76
2.185 BL1 0.012 0.00 8.98 8.87
2.185 BL1 0.012 0.00 9.05 8.98
2.185 BL1 0.012 0.00 9.14 9.05
2.185 BL1 0.012 0.00 9.23 9.14
2.185 BL1 0.012 0.00 9.42 9.23
2.185 CM2 0.010 0.00 9.56 9.42
2.185 BL1 0.000 0.00 9.56 9.56
2.185 BL1 0.000 0.00 9.56 9.56
2.185 BL1 0.000 0.00 9.56 9.56
2.185 BL1 0.000 0.00 9.56 9.56
2.185 BL1 0.000 0.00 9.56 9.56
2.185 BL1 0.000 0.00 9.56 9.56
2.185 BL1 0.000 0.00 9.59 9.56
2.185 RN1 0.000 0.65 10.25 9.59
2.185 BL 0.001 0.00 7.91 7.90
2.185 BL 0.005 0.00 7.95 7.91
2.185 BL 0.012 0.00 8.06 7.95
2.185 BL 0.022 0.00 8.27 8.06
2.185 BL 0.036 -0.43 10.09 8.27
2.185 CM2 0.008 0.00 9.66 9.55
AUXILIARY SUBMITTAL SERIAL NO:2244HY1 11 -26 -2007 PAGE 3
CREEK STREET PLAZA CANOPY .20/7 HEADS
TC7040
ORDINARY GROUP 2 (MERCANTILE)
CRKPLA2
FROM
TO
FLOW
LENGTH
FITTING
DIAM
TYPE
PSI /Ft
S -LOSS
PRESSURES
42
43
22.35
14.21
0.0
2.185
CM2
0.004
0.00
9.72
9.66
52
42
22.35
41.00
6.0
2.185
BL1
0.004
0.00
9.93
9.72
41
52
13.68
6.50
28.0
2.185
BL1
0.002
0.00
9.99
9.93
31
41
13.68
136.67
21.0
2.185
BL1
0.002
0.00
10.27
9.99
21
31
13.68
1.50
28.0
2.185
RN1
0.002
0.65
10.97
10.27
--------------------
36
45
2.97
189.41
63.0
2.185
BL
0.000
0.65
10.09
9.41
26
36
71.79
3.00
28.0
2.185
RN
0.039
-1.30
9.99
10.09
25
26
71.79
5.58
0.0
2.709
CM
0.014
0.00
10.07
9.99
24
25
71.79
13.50
0.0
2.709
CM1
0.014
0.00
10.25
10.07
23
24
76.36
13.50
0.0
2.709
CM1
0.015
0.00
10.46
10.25
--------------------
33
43
8.14
173.33
14.0
2.185
BL1
0.001
0.00
9.79
9.66
23
33
8.14
1.50
28.0
2.185
RN1
0.001
0.65
10.46
9.79
22
23
84.50
13.50
0.0
2.709
CM1
0.018
0.00
10.71
10.46
--------------------
32
52
8.67
130.67
0.0
2.185
BL1
0.001
0.00
10.03
9.93
22
32
8.67
1.50
28.0
2.185
RN1
0.001
0.65
10.70
10.03
21
22
93.17
12.50
0.0
2.709
CM1
0.022
0.00
10.98
10.70
4
3
116.85
473.00
142.0
8.265
LU
0.000
0.00
24.77
24.71
1
4
116.85
15.00
0.0
10.275
LU
0.000
0.00
24.77
24.77
--------------------
2
3
240.00
43.00
58.0
8.265
LU
0.000
0.00
24.75
24.71
1
2
240.00
180.00
0.0
10.275
LU
0.000
0.00
24.77
24.75
--------------------
10
21
106.85
13.71
20.0
2.709
FM1
0.029
0.00
11.94
10.98
8
10
106.85
12.10
0.0
3.320
FR
0.011
5.24
17.31
11.94
7
8
106.85
0.29
0.0
3.320
FR
0.011
0.13
17.44
17.31
6
7
106.85
202.00
53.0
6.155
UN
0.000
2.60
20.14
17.44
5
6
106.85
4.00
0.0
6.000
UN
0.000
0.00
20.14
20.14
6" WILKINS
MODEL 350DA DOUBLE DETECTOR
ASSEMBLY
4.54
3
5
106.85
18.00
47.0
6.155
UN
0.000
0.00
24.71
24.68
--------------------
0
1
356.85
0.01
0.0
10.275
UN
0.000
0.00
24.77
24.77
_j
11mabi�
Model F1 FR Sprinkler Types
Standard Upright
Standard Pendent
Conventional
Vertical Sidewall
Horizontal Sidewall
- HSW 1 Deflector
Model F1 FR Recessed Sprinkler Types
Recessed Pendent
Recessed Horizontal Sidewall
- HSW 1 Deflector
Listings & Approvals
1. Listed by Underwriters Laboratories: Inc. (UL)
2. Listed by Underwriters' Laboratories of Canada (U LC)
3. Certified by FM Approvals
4. Loss Prevention Council (LPC, UK)
5. NYC BS &A No. 587 -75 -SA
6. Meets MIL- S -901C and MIL -STD 167 -1
7. Verband der Schadenversicherer (VdS, Germany)
8. NYC MEA 258 -93 -E
UL Listing Category
Sprinklers, Automatic & Open
Quick Response Sprinkler
UL Guide Number
VNIV
Patents: US Patent No. 6,374,920 Applies to
Model F1 FR Vertical Sidewall Sprinklers.
Product Description
Reliable Models F1 FR and F1 FR Recessed Sprinklers are
quick response sprinklers which combine the durability of a
standard sprinkler with the attractive low profile of a decorative
sprinkler.
The Models F1 FR and F1 FR Recessed automatic sprinklers
utilize a 3.0 mm frangible glass bulb. These sprinklers have
demonstrated response times in laboratory tests which are
five to ten times faster than standard response sprinklers. This
quick response enables the Model F1 FR and F1 FR Recessed
sprinklers to apply water to a fire much faster than standard
sprinklers of the same temperature rating.
The glass bulb consists of an accurately controlled amount
of special fluid hermetically sealed inside a precisely manu-
factured glass capsule. This glass bulb is specially con-
structed to provide fast thermal response. The balance of
parts are made of brass, copper and beryllium nickel.
At normal temperatures, the glass bulb contains the fluid
in both the liquid and vapor phases. The vapor phase can
be seen as a small bubble. As heat is applied, the liquid ex-
Bulletin 136 Kiev 0
Model F1FR
Model F1 FR Recessed
Quick Response
Sarinklers
Upright
Pendent
Vertical Sidewall Conventional
Horizontal Sidewall Recessed Pendent
HSW 1 Deflector (Model FP Shown)
pands, forcing the bubble smaller and smaller as the liquid
pressure increases. Continued heating forces the liquid to
push out against the bulb; causing the glass to shatter,
opening the waterway and allowing the deflector to distrib-
ute the discharging water.
Application
Quick response sprinklers are used in fixed fire protec-
tion systems: Wet, Dry, Deluge or Preaction. Care must be
exercised that the orifice size, temperature rating, deflector
style and sprinkler type are in accordance with the latest
published standards of the National Fire Protection Asso-
ciation or the approving Authority Having Jurisdiction.
Quick response sprinklers are intended for installation as
specified in NFPA 13, FM Global Loss Prevention Data
Sheet 2 -8N or other applicable standards. Quick response
sprinklers and standard response sprinklers should not be
intermixed.
The Reliable Automatic Sprinkler Co., Inc. 103 Fairview Park Drive, Elmsford, New York 10523
DD
N
I
,s
Upright
Pendent
Vertical Sidewall Conventional
Horizontal Sidewall Recessed Pendent
HSW 1 Deflector (Model FP Shown)
pands, forcing the bubble smaller and smaller as the liquid
pressure increases. Continued heating forces the liquid to
push out against the bulb; causing the glass to shatter,
opening the waterway and allowing the deflector to distrib-
ute the discharging water.
Application
Quick response sprinklers are used in fixed fire protec-
tion systems: Wet, Dry, Deluge or Preaction. Care must be
exercised that the orifice size, temperature rating, deflector
style and sprinkler type are in accordance with the latest
published standards of the National Fire Protection Asso-
ciation or the approving Authority Having Jurisdiction.
Quick response sprinklers are intended for installation as
specified in NFPA 13, FM Global Loss Prevention Data
Sheet 2 -8N or other applicable standards. Quick response
sprinklers and standard response sprinklers should not be
intermixed.
The Reliable Automatic Sprinkler Co., Inc. 103 Fairview Park Drive, Elmsford, New York 10523
DD
N
I
Model F1 FR Quick Response Upright, Pendent & Conventional Sprinklers
Installation Wrench: Model D Sprinkler Wrench
-
Upright Pendent Conventional
Model F1 FR Quick Response Recessed Pendent Sprinkler
Installation Wrench: Model GFR1 Sprinkler Wrench
Installation Data:
Nominal
Factor
Sprinkler Identification
Sprinkler Type
—
Sprinkler Identification
Sprinkler
Approval
I Number SIN
Metric
US
Metric
Height
9
Or anization
g
-
- 5,6
80
2 2„ (56mm)
1,2,3,45,7,8
R3615
(20mrr)
SSU
SSP
Standard - Upright
(SSU) and Pendent
(SSP) Deflectors
Marked to Indicate
Position
;' NPT (R'',,'
4,2
" (15mm) Standard Orifice with y' NPT (R);) Thread
S 6
80
22" (56mm)
1,2,3 4 5,6,7
R3625t
83615
- - -- —
" (20mm ) Large Orifice with,';" NPT (R' /.,)Thread
8.0
115
2.3" (58mm)
1,2,3,4,7,8
- -
R3622t't
R3612
"(17mm ) Small Orifice with,,-," NPT (R:,) Thread
' Z
60
1 22" (56mm)
1.2,8
R3623 "�
R3613
(10mm) Small Orifice %dth NPT (R _) Thread
2.8
40
22" (56mm)
1,2,8
R3621
10mm Orifice XLH with R'"" Thread
4.2
60
56mrn
4,6,7
R3624
R3614
Conventional- Install
in Upright or Pendent Position
10mm Orifice XLH with R „ Thread
4.2
60
56mm
R367,1
15mrr Standard Orifice v.ith r," NPT (R') Thread
5,6
80
56mm
4,6,7
R3675
20mm Large Orifice with ,' NPT (R;,)Thread
8 0
115
58mm
1 7
R3672
Polyester coated upright UL and ULC listed corrosion
resistant.
-
Upright Pendent Conventional
Model F1 FR Quick Response Recessed Pendent Sprinkler
Installation Wrench: Model GFR1 Sprinkler Wrench
Installation Data:
Nominal
Thread
K Factor
Sprinkler
A royal
Sprinkler Identification
Orifice
Size
US
Metric
Height
Organizations
Number (SIN)
(15mm)
° NPT (R;: >l
- 5,6
80
2 2„ (56mm)
1,2,3,45,7,8
R3615
(20mrr)
: NPT (R/)
8 0
115
2 3" (58mm)
1,2,3,8
j R3612
:," (11 mm)
;' NPT (R'',,'
4,2
- I 60
2 2" (56mm)
128 8 -
P3613
(10mm)
��" NPT (RY�)
2.8
-
40
-
2 2" (56mm),
- -
1,2,6
R3611
10mm
R':
4,2
60
56mm
4,7
i 83614
o '
`'1 Refer to escutcheon data table for approvals and dimensions.
Model F1 FR Quick Response Vertical Sidewall Sprinkler
Installation Wrench: Model D Sprinkler Wrench
Installation Position: Upright or Pendent
Approval Type: Light Hazard Occupancy
Installation Data:
Nominal
Thread
K Factor
Sprinkler Approval
Sprinkler
Identification
Orifice
Size
-
US Metric Height Organizations
--
Number (SIN) _
NPT (R'G)
5 -6 80 22" (56mm) 1.2, 3, 6, 8
- —r - - -- —_
R3685
15mrn
NPT (R' /_)
5.6 80 2.2" (56mm) 4
r) LPC Approval is for Pendent position only.
Vertical Sidewall
US Patent No. 6,374,920
Orientation
Upright
Pendent
Deflector to Ceiling
Dimension (Min. - Max.)
- —
4 ( 12" 102mm - 305r m)
6' 12'(152rmn- :30r,rn)
Model F1 FR Quick Response Horizontal Sidewall Sprinkler
Deflector: HSW 1
Installation Wrench: Model D Sprinkler Wrench
Installation Data:
Approval Organizations
K Factor and Type of Approval Sprinkler
-- -- Identification
Nominal Thread Sprinkler Light T Ordinary Number (SIN)
Orifice Size US Metric Length
Hazard Hazard
f (15mm) NPT(R %2) 5.6 80 2 63" (67n,m) 1.2,3,5,8 1,2,5,8 R3635
NOTE: UL, ULC and MEA Listing permits use vvith F1 or F2 recessed escutcheon.
7
Horizontal Sidewall
41
"x
h M,
.;
7-
0,
?i? k(
,�' ALS A ✓ u'fAE�1f nPi�-
41
Installation
Quick response sprinklers are intended for installation as
specified in NFPA 13, FM Global Loss Prevention Data Sheet
2 -81N or other applicable standards. Quick response sprin-
klers and standard response sprinklers should not be inter-
mixed.
The Model F1 FR Recessed Quick Response Sprinklers are to
be installed as shown. The Model F1 or F2 Escutcheons illus-
trated are the only recessed escutcheons to be used with the
Model F1 FR Sprinklers. The use of any other recessed escutch-
eon will void all approvals and negate all warranties.
When installing Model F1 FR Sprinklers, use the Model D Sprin-
kler Wrench. When installing Model F1 FR Recessed Pendent or
Sidewall Sprinklers, use the Model GFR 1 Sprinkler Wrench. Any
other type of wrench may damage these sprinklers.
Glass bulb sprinklers have orange bulb protectors to minimize
bulb damage during shipping, handling and installation. RE-
MOVE THIS PROTECTION AT THE TIME THE SPRINKLER
SYSTEM IS PLACED IN SERVICE FOR FIRE PROTECTION. Re-
moval of the protectors before this time may leave the bulb vul-
nerable to damage. RASCO wrenches are designed to install
sprinklers when covers are in place. REMOVE PROTECTORS
BY UNDOING THE CLASP BY HAND. DO NOT USE TOOLS
TO REMOVE THE PROTECTORS.
Temperature Ratings
Sprinkler Max. Ambient Bulb
Classification Temperature Temp. Color
I °C °F
Ordinary
57
35
100 -,F(38`C)
Orange
Ordinary
to Ceiling or I
68
155
I00`F(38'C)
Red
Inten7iediate
79
175
150`F(66 1C)
yellow
Intermediate
(38.1rnm) '� C'
93
200
150'F (66'C)
Green
igh ('i
141
286
225T(i0 "c')
Rue
t'1 Not available for recessed sprinklers
Escutcheon Data
No Dimensional Figure for FP
Maintenance
The Models F1 FR and F1 FR Recessed Sprinklers
should be inspected quarterly and the sprinkler system
maintained in accordance with NFPA 25. Do not clean
sprinklers with soap and water, ammonia or any other
cleaning fluids. Remove dust by using a soft brush or gen-
tle vacuuming. Remove any sprinkler which has been
painted (other than factory applied) or damaged in any
way. A stock of spare sprinklers should be maintained to
allow quick replacement of damaged or operated sprin-
klers. Prior to installation sprinklers should be maintained
in the original cartons and packaging until used to mini-
mize the potential for damage to sprinklers that would
cause improper operation or non - operation.
Sprinkler Types
Standard Upright
Standard Pendent
Conventional
Sidewall (Vertical. Horizontal HSW1)
Recessed Pendent
Recessed Horizontal Sidewall HSW1
Finishes "' "'
Standard Finishes
Sprinkler -- Escutcheon
Bronze Brass
Chrome Plated Chrome Plated
White Polyester Coatedinl 'White Painted rst
Special Application Finishes
Sprinkler Escutcheon
Bright Brass ,Bright Brass
Black Plated Black Plated
Black Paint Black Paint
Off White Off White
Satin Chrome Satin Chrome
Othef finishes and colors are available or special o,dei
Consult the factory for details -
? FM Approvals is limited to bronze and brass, chrome or black
plated finishes only.
isi FP Push -on ?Th read -off escutcheon.
a) UL and ULC listed corrosion resisiance.
SIN nun bers R3621, R3622, R3623, R3625.
Note: For /1/2" orifice pendent FM approved white
polyester coated and UL approved white polyester
corrosion resistant sprinklers refer to Bulletin 014.
Ordering Information
Specify:
1. Sprinkler Model
2. Sprinkler Type
3. Orifice Size
4. Deflector Type
5. Temperature Rating
6, Sprinkler Finish
7. Escutcheon Type
8. Escutcheon Finish (where applicable)
Note: When Model F1 FR Recessed sprinklers are
ordered, the sprinklers and escutcheons are packaged
separately.
The equipment presented in this bulletin is ;o 0c it alled in accordance ✓ ith tae latest oeriincnt ;turd <ar1; of the National Fire Protection Association, Factory 1r + -_ al R(.sca-
Corporation, or other similar organization- a,,)d also , rl? the provisions of governmental codes _:r ordina u, whe -ever applicable.
Products manufactured and di,.trihuted by Reliable have been protec?ing life and property for over 80 ye- - r. _;nd ere - rstalled and ,e viced h7 ,ernost higi ly qunhhed e d rep,ta-
ble sprinkler contractors located thmugho, it the United States. Canada and foreign countries
Manufactured by
Reliable
The Reliable Automatic Sprinkler Co., Inc.
(800)431 -1588 Sales Offices
(800)848 -6051 Sales Fax
(914)829 -2042 Corporate Offices
wwva-
reliablesprinklercorn Internet Address
�i
Revision lines In lc aae .jpdaied o., nem data
FG. P 'ec ir. U.S.' llr;7 P /NY 99997' D:) P7
Face of Fitting
Escutcheon on
Approvals
Adjustment
to Ceiling or I
Dimension
Wall Dimension
1y'
F7
1,2,4,8
Max Recess
(38.1rnm) '� C'
Min Recess
%„ (Srnni 24rnm)
_
19.1m,,rn) -_ -- ___ - --
F2
1 L3,4,5,7'8
Max Recess
f (38 Imm)
Min Recess
(5mm 17mn-i)
Fp
1,2
Max Recessed
1 ✓, "(a3 1mm)
i
(11mm
Push on!
Threadcrf
P
Min Re c scd
1"(2b_4mm)
�-
-
L- —
(24rrIrn - - --
No Dimensional Figure for FP
Maintenance
The Models F1 FR and F1 FR Recessed Sprinklers
should be inspected quarterly and the sprinkler system
maintained in accordance with NFPA 25. Do not clean
sprinklers with soap and water, ammonia or any other
cleaning fluids. Remove dust by using a soft brush or gen-
tle vacuuming. Remove any sprinkler which has been
painted (other than factory applied) or damaged in any
way. A stock of spare sprinklers should be maintained to
allow quick replacement of damaged or operated sprin-
klers. Prior to installation sprinklers should be maintained
in the original cartons and packaging until used to mini-
mize the potential for damage to sprinklers that would
cause improper operation or non - operation.
Sprinkler Types
Standard Upright
Standard Pendent
Conventional
Sidewall (Vertical. Horizontal HSW1)
Recessed Pendent
Recessed Horizontal Sidewall HSW1
Finishes "' "'
Standard Finishes
Sprinkler -- Escutcheon
Bronze Brass
Chrome Plated Chrome Plated
White Polyester Coatedinl 'White Painted rst
Special Application Finishes
Sprinkler Escutcheon
Bright Brass ,Bright Brass
Black Plated Black Plated
Black Paint Black Paint
Off White Off White
Satin Chrome Satin Chrome
Othef finishes and colors are available or special o,dei
Consult the factory for details -
? FM Approvals is limited to bronze and brass, chrome or black
plated finishes only.
isi FP Push -on ?Th read -off escutcheon.
a) UL and ULC listed corrosion resisiance.
SIN nun bers R3621, R3622, R3623, R3625.
Note: For /1/2" orifice pendent FM approved white
polyester coated and UL approved white polyester
corrosion resistant sprinklers refer to Bulletin 014.
Ordering Information
Specify:
1. Sprinkler Model
2. Sprinkler Type
3. Orifice Size
4. Deflector Type
5. Temperature Rating
6, Sprinkler Finish
7. Escutcheon Type
8. Escutcheon Finish (where applicable)
Note: When Model F1 FR Recessed sprinklers are
ordered, the sprinklers and escutcheons are packaged
separately.
The equipment presented in this bulletin is ;o 0c it alled in accordance ✓ ith tae latest oeriincnt ;turd <ar1; of the National Fire Protection Association, Factory 1r + -_ al R(.sca-
Corporation, or other similar organization- a,,)d also , rl? the provisions of governmental codes _:r ordina u, whe -ever applicable.
Products manufactured and di,.trihuted by Reliable have been protec?ing life and property for over 80 ye- - r. _;nd ere - rstalled and ,e viced h7 ,ernost higi ly qunhhed e d rep,ta-
ble sprinkler contractors located thmugho, it the United States. Canada and foreign countries
Manufactured by
Reliable
The Reliable Automatic Sprinkler Co., Inc.
(800)431 -1588 Sales Offices
(800)848 -6051 Sales Fax
(914)829 -2042 Corporate Offices
wwva-
reliablesprinklercorn Internet Address
�i
Revision lines In lc aae .jpdaied o., nem data
FG. P 'ec ir. U.S.' llr;7 P /NY 99997' D:) P7