Community Center Krazan IIiV G.ZM&Associates,Inc. Geotechnical Engineering • Environmental Engineering Construction Testing and Inspection DATE: 4/15/2015 PROJECT #: 06615047 PROJECT: Yelm Community Center LOCATION: 310 SE 2nd Street KA P.M.: Bill Throne FIELD REPORT NO.: 15047DFRO41515-MM CONTRACTOR: Stetz PERMIT #: 20140170 INSPECTOR: Martin Mundy JURISDICTION: Yelm WEATHER: Sunny TEMP: 55 On site for reinforced concrete inspection. Contractor placed #5 and #7 epoxy -grouted dowels along 1 Line. The holes were drilled to the required depth of six inches and brushed and blown clean. Simpson SET -XP epoxy (expiration date 9/21/16) was used. The epoxy procedure provided adequate coverage of the dowels. Contractor placed the concrete for the slab -on -grade from A -B/1-2. The reinforcing steel (size, grade, lap, spacing, clearance) was in place in conformance with the plans. The concrete was placed by chute and mechanically consolidated. A total of 5.5 cubic yards of concrete was placed. See report 15047CRO41515-MM for field and compressive strength test results Reviewed By: UV" ASTM Test #: Equipment/Asset Number(s) To the best of my knowledge, the above WAS performed in accordance with the approved plans, specifications and regulatory requirements. S uperintendent/Representative: Technician: fit- wt Offices Serving the Western United States Lynnwood (425) 485-5519 - Poulsbo (360) 598-2126 a Puyallup (253) 939-2500 Deis, Field Report Revision 8 Hfleame 0211712017 the mkrmalino lnwiam.m dle reem uprgwed Gx Uwe tb,vius usenfine ekP�l. TbU reltM mr: nuv bee�evvdpeye in yktrmn wilk., mevnt(w Peaoiasi<w of 0erlimv,md!(eamed sanbue. This vu "kdkffl webuyer nbx.aau W Wi.2re.'"A beset,+. a'WdAimsnda Wa M-6 hies. Thu ie! liiq usuhjt,l lnmv..r .mxe b.bAsebmiesL By virn�%mu,gvl.aw msM lrc cues ah r¢nraxQKw'tlolrt,'Gr'�WUYM,uolls. T1e r.we mWmialitm lav baa ianuid 1M'oIDaz em vic. Date: 4/15/2015 Project #: 066-15047 Project: Yelm Community Center Location: 301 2nd Street SE Krazan PM Bill Throne Field Data Concrete: Supplier. Miles Concrete Report gr�wr5 in the ;t v,icra l :ti ,;•:,,,• , ,c: ,;;•�•�:: r y Number, 15047CRO41515MM Contractor: Stetz Construction Permit #: 20140170 Inspector: Marty Mundy Jurisdiction: City of Yelm Weather: Sunny Temp: 55 Plant No. I 2068 I Site Mix: Slump Mix Air Unit Time Truck # Ticket # % Air Inch Temp F Temp F Weight 12:55 1 M077 1 213369 1 - 1 5 1 64 1 55 - Placement Area Location SLAB ON GRADE AT GRIDLINES 1-2/A-13 Remarks Please Refer To Field Repot Number: 150470 FR041515MM Inspector:1 M.MUNDY Reported Batch DATA Cement Type Ill/ Design El Actual ED MnxNo. 1250OF 1250OF Co.. Lbs. 489 494 F. Ash lbs. 122 121 C. Agg. Lbs 1530 1509 C. Agg. Lbs 350 362 C. Agg. lbs - - sand lbs 1370 1378 Water 213 213 Admixture - - Admbtture - - Adm6dure - - Air Ent (Ozf cvL) - - Water Added On Job Site 5/13/15 - (Gals.) 10 Field Test ASTM Method C143MX C138 C1064 C173 C31 OTHER Laboratory Data Design Strength 3000 At 28 Days Date Specimens Recd F411612015 Cyl. Code Test FieldWt. Date Cure Age Dim. Area # Max Comp. Load Strength Set Tested Brk # By Typ Test Method ASTM C39 X 1422-1 4122115 - 7 4.00 12.57 - 48280 3840 1 JS 3 ASTM C109 1422-2 5113/15 - 28 - 1 ASTM C617 1422-3 5113/15 - 28 - 1 ASTM C1231 X 1422-4 5/13/15 - 28 - 1 ASTM C1019 1422-5 - H - 1 AASHTO-T22 Test Results Remarks: conforming Results Reviewed By: Date: Non -conforming Code For Break Types: 1 Cone X 2. Cone Split 3. Cone Shear / 4 Shear / 5. Columnar Split Offices Serving The Western United States Come/. Report Re, 4 Err. 1421-08 The informetien pmVided on this report is pm paled for th..x k hng uea of the okw, and moy not be repleduced In erryfarmetwitteut the written parml�bn of un digin end Kraren & Associate. iuAlI<LCaGLLl&Associ aces, Inc. Geotechnical Engineering . Environmental Engineering Construction Testing and Inspection DATE: 4/28/2015 PROJECT* 06615047 PROJECT: Yelm Community Center LOCATION: 301 2nd St. SE KA P.M.: Bill Throne FIELD REPORT NO.; 15047DFRO42815-BR CONTRACTOR: Stetz Construction PERMIT* 20140170 INSPECTOR: Bruce Ridgley JURISDICTION: City of Yelm WEATHER: Overcast TEMP: 56 Krazan and Associates on site for inspection as requested by client. Reinforcing steel bar inspection for slab on grade and thicken footings between grids 2 through 7 / A through B 3.5 through 4.5 / B through C. Upon arrival on site met with contractor and reviewed requirements and locations. Reinforcing was observed and Appeared to be in place and in conformance with project plans and specifications for (Size, Grade, Lap splice, spacing) DWG 52.01 notes and per RFI #8 and # 28. Note: Clearances will need to be confirmed before placement of concrete. Revlewed By: ASTM Test #: Equipment/Asset Number(s): To the best of my knowledge, the above WAS performed in accordance with the approved plans, specifications and regulatory requirements. Superintendent/Representative: Technician: Offices Serving the Western United States Lynnwood (425) 485-5519 • Poulsbo (360) 598-2126 • Puyallup (253) 939-2500 Daily Fidd Report ReA8ioa S Eflbcd-021132013 Tae mfemwkm marNad m are [qmn b meWrad Ml tLe eacivtha ve dUx: etml. lb's repmi auYaaI benpod—d m., .&A -6i - b oo tde amdbevtsaod wottaGo[ d4ir+k& Tbb mf a is mbiw to teviex 4alx M Ynel MbUA-1 BY mea Ole T .r iz eWx does M M10 mWoab➢ily fm Y0 by orwA& Ilea kuk—W 08 a hem movidm Moaros m ��r�.-� y� FIELD mKraz�$LAssociate s, Inc. REPORT NO.: Geotechnical Engineering . Environmental Engineering Construction Testing and Inspection 15047DFRO42915-BR DATE: 4/29/2015 CONTRACTOR: Stetz Construction PROJECT #: 06615047 PERMIT #: 20140170 PROJECT: Yelm Community Center INSPECTOR: Bruce Ridgley LOCATION: 301 2nd St. SE JURISDICTION: City of Yelm KA P.M.: Bill Throne WEATHER: Mostly Cloudy T : 54 Krazan and Associates representive on site for inspection as requested by client. Concrete sampling and testing for slab on grade and thicken footings within slab. Upon arrival met with contractor and reviewed placement location and requirements. The concrete was observed Being placed via pump and adequately consolidated. Mix placed this date was #1250OF from Miles. (1) set of 4x8 Cylinders were cast for compressive strength tests. For additional information refer to Krazan concrete report # 15047CRO42915-BR. A total of 57cy placed this date. Note: Clearances were maintained during concrete placement. Note: Kitchen area to be placed at another date after reinforcing steel is installed and inspected. Reviewed By; To the best of my ASTM Test #: Equipment/Asset Number(s): the above WAS performed in accordance with the approved plans, specifications and regulatory requirements. Suped ntendent/ Representative: Technician: Offices Serving the Western United States Lynnwood (425) 485-5519 • Poulsbo (360) 598-2126 • Puyallup (253) 939-2500 Deily Fidd Repon Revision B Eli'edive 02/172013 TSe mlim.dm protided na 0tu tgmruWCDa.[d 0.r tIIar 9ntiw uuafNe cGmi.76uiWoti Qey vaMtRe.�d'�ruln®Yfuemalrn4ut me WlilMr M�n'ovmNNe diem ead Kn:mA '. xr. hui pm iodi�aln amms➢r+'bre nTeavatioa andlu�G ��laboselmste mam7iova sv4 ammW aetiviue.. 'fLie ivfm®tlw a at�iod w re•.irapd,K N @ael sdrmLeL &Y ��C R4 Uu �epM. om aeyx�or does at auepl rc'aM'naD01Y kr �+liJnY ofwotrs 1De s+me nlbra.tiov bw baa WovideA b- d4va m QA4Krazm&Associates, Inc. Geotechnical Engineering • Environmental Engineering Construction Testing and Inspection DATE: 5/4/2015 PROJECT #: 66615047 PROJECT: Yelm Community Center LOCATION: 301 2nd Street SE KA P.M.: Bill Throne FIELD REPORT NO.: 15047DFRO50415-JB CONTRACTOR: Stetz Construction PERMIT #: 20140170 INSPECTOR: J. Blstryski JURISDICTION: City of Yelm WEATHER: Overcast TEMP: 61 ° & Associates, Inc. on site as requested for reinforcing steel bar inspection and concrete placement observation, g and testing at the following locations: - Kitchen Area — Slab On Grade arrival on site met with contractor and reviewed plan details and inspection locations. The elements of the rcement in the locations noted above were visually inspected and found to be in place with the correct size of bars, .g and clearances as detailed in project plans. to concrete was Class 3000 from Cal Portland and was observed being placed via truck chute. Consolidation was rformed using mechanical vibration. Samples were obtained and tested from the point of placement. (1) Set of (5) 4x8 linders were cast for laboratory compressive strength testing. For additional testing information and sampling details, Krazan Report #15047CR050415-JB. Reviewed By: ASTM Test M Equipment(Asset Number(s): To the best of my knowledge, the above WAS performed in accordance with the approved plans, specifications and regulatory requirements. S uperintendent/Representative: Technician: '-). �:s4flsk� Offices Serving the Western United States Lynnwood (425) 485-5519 • Poulsbo (360) 598-2126 • Puyallup (253) 939-2500 Dell,• Fidd Rcpmt Revisi°n 9 Effeuive071132013 Tbetr atimpm""WL MMS 4mCPoe7fh16e eah�muuaee of�M ctiml.lL'urcDOM mer nolcertp�u0ux0mavyR��wehnmtAe writt�a Pe�d>e d'me tlimteMw•+n A -da.. TbUmmmeimlremem.peuo b— tionmd,gM,y=as b0wem5kmodkk,1.earmeaax -i,,tw. rail .iioouoet°kre,;e,.p ro wl ey,'ueksu:1.w�,.op.ow�o.amema�nw�e�tir�a�.+naarori_ �ae�k�,�aoemero�tr�:manyomwew�. s ...:. soft ami Date: 4129/2015 Project #: 066-15047 Project: Yelm Community Center Location: 301 2nd Street SE Krazan PM Bill Throne Field Data Concrete: F Slab Supplier: I Mlles r•;irh„ \ :f :n,rre si�,h-rrlr ti Concrete Report r' Number: 15047CR0429156R Contractor: Stetz Construction Permit #: 20140170 Inspector: Bruce Ridgley Jurisdiction: City of Yelm Weather: Mostly Cloudy Temp: 50 Other I - Plant No. 1 2068 1 Site Mix.- Slump ix:Slump Mix Air Unit Time Truck # Ticket # % Air Inch Temp F Temp F Weight 10:25 1 68 1 213719 1 - 1 53/4 1 62 52 1 - Placement Area Location SLAB ON GRADE AND THICKENED FOOTINGS FOR BUILDING. Remarks CAST (1) SET OF (5) 4X8 CYLINDERS FROM LOAD #1 (10CY) 76.40LBS OF COLOR ADDED TO MIX PER PLAN. COLOR IS LISTED UNDER FIRST ADMIXTURE. Please Refer To Field Repot Number: 15047DFRO42915BR Inspector: B.RIDGLEY Reported Batch DATA Cement Type 1/fl Design El Actual El Mix No. 1250OF 1250OF Cam. Lbs. 489 490 F. Ash lbs. 122 121 C. Agg. Lba 1530 1526 C. Agg. Lbs 350 256 C. Agg. Lbs - - Sand lbs 1370 1365 Water 246 The 231 lbs Admixture 7.64 lbs 7.64 lbs Admixture - - Admixture - Air Ent. (Ozl Cwt.) Water Added On Job Site (Gals.) Field Test ASTM Method C143 Area C138 Set Tested Brk # By Typ C1064 TX C173 7 4.00 12.57 C31 OTHER 5020 Laboratory Data Design Strength 3000 At 28 Days Date Specimens Rec'd 4/30/2015 Cyl. Code Test Field Date Cure A e Dim. Area Wt. Max Comp. # Load Strength Set Tested Brk # By Typ Test Method ASTM C39 X 1476-1 5/6/15 - 7 4.00 12.57 - 63125 5020 1 MT 3 ASTM C109 1476-2 5/27/15 - 28 - 1 ASTM C617 1476-3 5/27/15 - 28 - 1 ASTM C1231 - X 1476-4 5/27/15 - 128 - 1 ASTM C1019 147&5 - I H - 1 AASHTO-T22 Test Results Remarks: I conforming Results Reviewed By: Date: S I Non -Conforming Code For Break Types: 1V Cone /\ 2. Cone Split 3. Cone Shear 4 Shear / 5. Columnar Split Offices Serving The Western United States CorxreteReport R.,4 Ee.10-21-0a The information provided on tHa mpon is prepaired for the exclusive um of the dient, and may not be reproduced in anyformalwithoul tho written pa.-nission of the clan and Kmzan & Aasociatea anew- i v,� Date: 5/4/2015 Project* 066-15047 Project: Yelm Community Center Location: 301 2nd Street SE Krazan PM Bill Throne t11t O)J.f vs 1n 4hf cs« -n r.s Concrete Report F; ; . ,f.,.":_. , ,r,;..v_-,— Number: 15047CR050415JB Contractor: Stetz Construction Permit#: 20140170 Inspector: Joe Sistryskl Jurisdiction: City of Yelm Weather: Overcast Temp: 61 Field Data Concrete: F X Other - Supplier: CalPortland Plant No. 272 Site Mix: C� Slump Mix Air Unit Time Truck# Ticket# %Air Inch TempF TempF weight 11:45 1 7638 1 1140731 - 1 41/4 69 1 61 1 - Placement Area Location I KITCHEN AREA - SLAB ON GRADE. Remarks CAST (1) SET OF (5) 4X8 CYLINDERS FROM LOAD #1 (7.25CY) ADMIXTURE AT RIGHT IS WRDA 64. Please Refer To Field Repot Number: 15047DFR060415JB Inspector: J.BISTRYSK[ Reported Batch DATA Cement Type 1 1/II Design EKI Actual �X Mix No. _ 63013 63013 Cem. Lbs. 550 551 F. Ash lbs. - - C. Agg. Lbs 1960 1953 C. Agg. Lbs - - C. Agg. Lbs - Sand lbs 1330 1315 Water 250 lbs 238 lbs Admixture 15 oz 15 oz Admixture - - Admlxture - Air Ent. (Oz/Cwt.) Water Added On Job Site (Gels.) Field Test ASTM Method C143 X C138 C1064 X C173 C31 X I OTHER Laboratory Data Design Strength 3000 At 28 Days Date Specimens Recd 5/5!2015 Co. Code Test Field Date Cure Age Dim. Area Wt. Max Comp. # Load Strength Set Tested Brk # By Typ Test Method ASTM C39 X 1502-1 5/11/15 - 7 4.00 12.57 - 61175 4870 1 MT 3 ASTM C109 1502-2 611115 - 28 - 1 ASTM C617 1502-3 611/15 - 28 - 1 ASTM C1231 X 1502-4 6/1/15 - 28 - 1 ASTM C1019 1502-5 - H - 1 AASHTO-T22 Test Results Remarks; M Conforming Results Reviewed By: a e: on -Conforming Code For Break Types: 1 Cone 2. Cone Split 3. Cone/ Shear 4 Shear 5. columnar Split Offices Serving The Western United States concrete Report Re, 4 Ex. 10-214e The Wormason provided an Na report is prepalred for the exdu" vee o! rhe diens, and may rpt be reproduced in any formal uidput Uw written p-1wion of the alien and Kmun::..aeodabas Date: 4/15/2015 Project #: 066-15047 Project: Yelm Community Center Location: 301 2nd Street SE Krazan PM Bill Throne Field Data Concrete: - Supplier: Miles Concrete Report Number: 15047CRO41515MM Contractor: Stetz Construction Permit #: 20140170 Inspector: Marty Mundy Jurisdiction: City of Yelm Weather: Sunny Temp: 55 Other Plant No. I 206B I Site Mix: Slump Mix Air Unit Time Truck# Ticket# %Air Inch Temp Temp Weight 12:55 1 M077 1 213369 1 - 1 5 1 64 1 55 1 - Placement Area Location SLAB ON GRADE AT GRIDLINES 1 -2/A -B Remarks Please Refer To Field Repot Number: 15047DFR041515MM Inspector : M.MUNDY Reported Batch DATA Cement Type I/lI Design Ell Actual Mix No. 12500E 1250OF Com. Lbs. 489 494 F. Ash lbs. 122 121 C. Agg. Lbs 1530 1509 C.Agg.Lbs 350 1 362 C. A99. Lbs - - Sand lbs 1370 1378 Water 213 213 Admixture - - AdmixNre - Admixture - Alr Ent (OzirwL} - Water Added On Job Site (Gals.) 10 Field Test ASTM Method Age Dim. C143 X C138 Tested By C1064 LXJ C173 4/22115 - C31 I X I OTHER - 482BO 3840 Laboratory Data Design Strength 3000 At 28 Days Date Specimens Recd 4!16/2015 Cyl. Code Test FieldWt. Date Cure Age Dim. Area Max Comp. # Load Strength Set # Tested By Brk Typ Test Method ASTM C39 X 1422-1 4/22115 - 7 4.00 12.57 - 482BO 3840 1 JS 3 ASTM C109 1422-2 5/13/15 - 28 4.00 12.57 - 71130 5660 1 MT 3 ASTM C617 1422-3 5113/15 - 28 4.00 12.57 - 71180 5660 1 MT 3 ASTM C1231 X 14224 5/13/15 - 128 4.00 12.57 - 70025 5570 1 MT 3 ASTM C1019 1422-5 - H - 1 AASHTO-T22 Test Results Remarks: X Conforming Results Reviewed By: Date: 1 - J Non -Conforming Code For Break Types: 12. Cone / \ Cone Split 3. Cone Shear / 4 Shear / 5. Columner Split Offices Serving The Western United States Comrefe Report Re, 4 Eft. 10-21-0e The information provided on this report la prepaied for dw a-kAw use of the clard, on) mey rnl be reproduced in airy formetwhhoul the wrdlen permission of the digin and Kreran A Aseod to Date: 4/29/2015 Project #: 066-15047 Project: Yelm Community Center Location: 301 2nd Street SE Krazan PM Bill Throne r Concrete Report With OJ!", s in thr We- r.5 Number: 15047CRO42915BR Contractor: Stetz Construction Permit #: 20140170 Inspector: Bruce Ridgley Jurisdiction: City of Yelm Weather: Mostly Cloudy Temp: 50 Field Data Concrete: Slab Other - Supplier: Miles Plant No. 2068 Site Mix: Slump Mix Air Unit Time Truck # Ticket # % Air Inch Temp F Temp F Weight 10:25 1 68 1 213719 - 1 5 314 1 62 1 52 1 - Placement Area Location ISLAB ON GRADE AND THICKENED FOOTINGS FOR BUIL Remarks CAST (1) SET OF (5) 4X8 CYLINDERS FROM LOAD #1 (10CY) 76.40LBS OF COLOR ADDED TO MIX PER PLAN, COLOR IS LISTED UNDER FIRST ADMIXTURE. Please Refer To Field Repot Number: 15047DFRO42916BR Inspector: I B.RIDGLEY Reported Batch DATA Cement Type I/I Design EK] Actual EKI MIXNo. 1260OF 1250OF cam. Lbs. 489 490 F. Ash Ibs. 122 121 C. Agg. Lbs 1530 1526 C. Agg, Lbs 350 256 C. Agg. Lbs - - E1365 sand lbs 1370 Water 245 lbs 231 lbs Admixture 7.64 lbs 7.64 lbs Admixture - - Admlxture - ^ Air Ent. 3 (Ozl owt) - - Water Added On Job Site 28 4.00 12.57 (Gals-) o Field Test ASTM Method C143 X C138 C1064 I X 1 0173 C31 X OTHER Laboratory Data Design Strength 1 3000 At 28 Days Date Specimens Recd 4!3012015 Cyl. Code Test Field Date Cure Age Dim. Area Wt. Max Comp. # Load Strength Set Tested # By Brk Typ Test Method ASTM C39 X 1476-1 5/6/15 - 7 4.00 12.57 - 63125 5020 1 MT 3 ASTM C109 1476-2 5127/15 - 28 4.00 12.57 - 80855 6430 1 JS 3 ASTM C617 1476-3 5/27/15 - 28 4.00 1 12.57 - 77220 6140 1 JS 3 ASTM C1231 X 1476-4 5/27/15 - 28 4.00 12.57 - 79400 6320 1 JS 3 ASTM C1019 1476-5 - H - 1 AASHTO-T22 Test Results Remarks: Ad X Conforming Results Reviewed By: a4: i►— r Non -Conforming Code For Break Types: 1 Cone / 2. Cone Split 3. Cone Shear / 4 Shear / s. caiumner Split Offices Serving The Western Unttea btates Garorete Rad dRev.4 Eff. 10-21-06 The Informarian provided on this rapon is prepetad for tha exclusivm uaa of the talent and may not be reproduced In any former without the wrxlen pennbelon of the than and Kremn & Asa Wtaa