Loading...
105 Van Trump sewer inspection punchlist City of Yelm Community Development Department 105 Yelm Avenue West Yelm, WA 98597   December 14, 2016 Michael & Karen Conley 109 Van Trump St NE Yelm, WA 98597 Dear Mr. & Ms. Conley, After inspection of your step system the following is a punch list for sewer at 105 Van Trump. These items will need correction as well as the items from your house inspection before a final inspection is performed and a Certificate of Occupancy is issued. Per our verbal discussion at the pre-final inspection, 30 days is granted for these corrections.               1)- Need to install disconnect switch for Pump Control Panel. 2)- House breaker panel has two 50 amp. breakers for sewer. It needs to have one 20 amp. dedicated breaker. 3)- High Level Alarm float needs to be new style mechanical “ P “ float. We do not use this style of float “B” in our systems. 4)- Need to replace all butt splice connections in tank pump chamber “J” box. They need to be heat shrink waterproof connectors. The system currently has 2 wire nuts and the heat shrink splices that are on there now are punctured and rusting inside. 5)- Need new L&I electrical final for sewer when work is completed.    Randy Hatch at Yelm Public Works (360) 458-8426 would be willing to meet with electrical contractor before starting work and go over what needs to be done. Ron Kemp, CBO Building and Fire Safety Official City of Yelm 105 Yelm Ave. W Yelm, WA 98597 (360) 458-8407 ronk@ci.yelm.wa.us