Loading...
Burnett Business Park Plan Review Mini StoragePlan Review Mini Storage Accessible Path from Parking to restrooms & Office door Two hour occupancy separation wall between office and storage. Show detail. Door at one hour wall to be rated 20 minutes One hour fire wall detail should show 5/8” sheetrock both sides of wall with 5-1/2 inch mineral bat insulation. 5/8” drywall to be secured with 2-1/4” Type S screws at 7” o.c. Show detail from Armstrong. One hour wall extends to roof. If parapet not used at 1 hour fire walls, ten feet back from wall must have a one hour rating for the roof/ceiling framing and complete roof must be rated Class B. Overhang at one hour exterior fire wall limited to fascia trim on greater then 10%. Mechanical ventilation required in Studio Barns 1 & 14. Supply documentation that exterior siding meets NFPA 268