05-0091 Sewer #3 081208CITY OF YELM SEWER DEPARTMENT
Aug 12, 2008
Re: WalMart Step tank Review Aug. 12, 2008 SPR-05-0091
The new 6000 gal. tank must have hold downs similar to the existing STEP Tank
The New 6000 gal tank must have a baffle wall separating the solids end from the pump chamber configured to 2/3 â 1/3 volume.
The new 6000 gal tank shall have 3 risers, 1 over the inlet âTâ, the 2nd over the opposite end of the solids portion of the tank, and the 3rd over the pumps.