05-0770 Water Review No. 2 121407 From: Deonne Hardy Sent: Friday, December 14, 2007 2:56 PM To: Tim Peterson Cc: deonneh@ci.yelm.wa.us; Kevin Ray; Steve Harrington; Jim Gibson Subject: Samantha Ridge, Review #2 Attachments: image003.wmz; oledata.mso Water review for Samantha Ridge ????r City of Yelm Public Works Department 901 Rhoton Road P.O. Box 479 Yelm , WA 98597 (360) 458-8406  Fax: (360) 458-8417 Public Works Inspection Report Date: 14 December 20007                                                                Page 1 of Location: Samantha Ridge                                                                Department:  Water Contractor                                                                                          Rep: This property has a Reclaimed Water main running through it. All of the water meter will need a Reduced Pressure Backflow Assembly behind them. At station 2 + 17.39- the sewer is too close to the water main. From station 0 + 54.45, need to run the new water main straight to the existing main under Crystal Spring Road and hot tap the old water main. Will need to cut and cap or plug the old main at the gate valve under Crystal Springs Road. The valves shown on the one inch service lines should be Corp Stops not gate valves. The irrigation shows the backflow assembly before the water meter, this needs to be behind the meter. This property has Reclaimed Water going through the project; can this be used for the irrigation system?         Reviewed by:  John I, Tim R and Edward Smith          Signed by Edward Smith