Sewer Samantha Ridge 2nd ReviewIPM.Note
Sewer Samantha Ridge 2nd Review
Roberta Allen
Jon Yanasak
Roberta Allen
EX
/O=CITYOFYELM/OU=FIRST ADMINISTRATIVE GROUP/CN=RECIPIENTS/CN=JONY
Samantha Ridge 2nd Review
EX
/O=CITYOFYELM/OU=FIRST ADMINISTRATIVE GROUP/CN=RECIPIENTS/CN=R_ALLEN
EX
/O=CITYOFYELM/OU=FIRST ADMINISTRATIVE GROUP/CN=RECIPIENTS/CN=R_ALLEN
Jon Yanasak
EX
/O=CITYOFYELM/OU=FIRST ADMINISTRATIVE GROUP/CN=RECIPIENTS/CN=JONY
Tim Peterson
Roberta Allen
Sewer Samantha Ridge 2nd Review
Here you go ----
Jon Yanasak
City of Yelm Sewer Dept. Mgr
Po Box 479
Yelm Wa 98597
Phone 360-458-8411
Fax 360-458-8166
jony@ci.yelm.wa.us
<DC90029353CCCD468AA2A2858FFCD8F5397E2A@server1.ci.yelm.wa.us>
Sewer Samantha Ridge 2nd Review.EML
Jon Yanasak
Roberta Allen
11.0
Samantha Ridge 2nd Review December 18, 2007
Samantha Ridge 2nd Review December 18, 2007
Roberta Allen
EX
/O=CITYOFYELM/OU=FIRST ADMINISTRATIVE GROUP/CN=RECIPIENTS/CN=R_allen
r_allen@ci.yelm.wa.us
r_allen
458-3835
Community Development
Roberta Allen
Roberta Allen
Tim Peterson
EX
/O=CITYOFYELM/OU=FIRST ADMINISTRATIVE GROUP/CN=RECIPIENTS/CN=Tim
tim@ci.yelm.wa.us
tim
458-8499
Public Works
Tim Peterson
Tim Peterson
Samantha Ridge 2nd Review December 18, 2007.doc
CITY OF YELM SEWER DEPARTMENT
December 18, 2007
Re: Samantha Ridge 2nd Review
The number of tanks planned for this project (29) must be reduced. Please use larger tanks. This same comment was made on the 1st review when only 15 tanks were planned.
The tank sizes need to be “called out” on the drawings.
It appears that the existing Sewer Main is being replaced. Why?
A 12” Sewer Main is planned for future capacity (not shown on the drawings). This new main was to be installed next to the existing main. Please address this.
Please show all updated details pertaining to this plan.
Sta. # 4+92.50 needs an “end of line clean-out”.
For clarity, all pressure lines going from the tanks to the main are called “service lines”, not force mains.
Please show all side sewers.
All Pump Control Panels will need to be mounted on remote posts.
Please show the location of all service line valve boxes (Carson boxes).
The existing Reclaimed water Main is shown below a swale and under a proposed building. This is not acceptable.
Please show the location of hose bibs to enable servicing of the STEP Tanks.