Loading...
05-0770 Water #3 022708 City of Yelm Public Works Department 901 Rhoton Road P.O. Box 479 Yelm, WA 98597 (360) 458-8406 Fax: (360) 458-8417  Public Works Inspection Report Date: 2/27/08 Page  of  Location: Samantha Ridge Department: Water Contractor: Rep: The Master Meter and Reduced Pressure Backflow Assembly can not be installed directly on the 10” water main, as this is a main water transmission line from one side of the City of Yelm to another. A separate water tap and service line will need to be installed for Master Meter and Reduced Pressure Backflow Assembly for all water services to residences. Hot Tap at station 2+18.40, 57.68 LT will need to be at a right angle to existing 10” water main and a bend will need to be installed after new valve. If using a master meter, what size will the Master Meter and Reduced Pressure Backflow Assembly be? What size is the irrigation meter and reduced pressure backflow assembly for irrigation be? How will old 10” A.C. water main be capped and abandoned? Reviewed by: John Ivey Signed by: Edward Smith