05-0770 Water #3 022708
City of Yelm
Public Works Department
901 Rhoton Road
P.O. Box 479
Yelm, WA 98597
(360) 458-8406 Fax: (360) 458-8417
Public Works Inspection Report
Date: 2/27/08 Page of
Location: Samantha Ridge Department: Water
Contractor: Rep:
The Master Meter and Reduced Pressure Backflow Assembly can not be installed directly on the 10” water main, as this is a main water transmission line from one side of the City of Yelm
to another. A separate water tap and service line will need to be installed for Master Meter and Reduced Pressure Backflow Assembly for all water services to residences.
Hot Tap at station 2+18.40, 57.68 LT will need to be at a right angle to existing 10” water main and a bend will need to be installed after new valve.
If using a master meter, what size will the Master Meter and Reduced Pressure Backflow Assembly be?
What size is the irrigation meter and reduced pressure backflow assembly for irrigation be?
How will old 10” A.C. water main be capped and abandoned?
Reviewed by: John Ivey
Signed by: Edward Smith