Loading...
05-0750 Sewer Review No 2 120507 CITY OF YELM SEWER DEPARTMENT December 5, 2007 Re: Review #2 Tahoma Terra Fairway Multi-Family Housing In the upper Rt. Corner of sheet 18 shows a “Water Table” should this not be called a “Sewer Fitting Table”? No MJ fittings. The piping system must be constructed of PVC only, other than the gate valves. Air release Assemblies should not be placed in the roadway if possible. A Side Sewer Clean Out is required within 2’ of the bldg foundation. A hose bib is required to be shown within 50’ of the location of a STEP Tank. Show all correct details pertaining to this project. Detail # 7-22 does not apply to this project. Typical End of Line Clean Out detail # 7-20 should be shown. Show the location of all Valve boxes (Carson boxes). No 90 degree bends in the Side sewers. Sheet 19 shows a Water line profile not sewer. Please correct. In the drawings, please refer to pressure sewer lines going from the STEP Tank to the main as a “Service Line” for clarification.