05-0750 Water Review no 2 120307 From: Edward Smith
Sent: Monday, December 03, 2007 10:57 AM
To: Tim Peterson
Cc: Deonne Hardy; Kevin Ray; Jim Gibson; Steve Harrington
Subject: T T Fairway Multi-Family Housing Plan Review Public Works.doc
Plan review for TT Fairway Multi-Familt Housing from water department.
??? City of Yelm Public Works Department
901 Rhoton Road
P.O. Box 479
Yelm, WA 98597
(360) 458-8406 Fax: (360) 458-8417
Public Works Inspection Report
Date: 3-Dec-2007 Page 1
Location: TT Fairway Multi-Family Housing Department: Water
Contractor: Rep:
1. The developer is responsible for the cost of the fire hydrant locks and the City of Yelm Water Department will order and install them. The project will not be final
until the City of Yelm has received the payment in full for the fire hydrant locks.
2. Eliminate the existing ten main to the blow off at the end, and at station 0 + 70.28 install a gate valve and 22 1/2 bend.
3. Deflect the main from station 0 + 70.28 to station 2 + 44.19 too eliminating the bends.
4. At station 4 + 06.50, the Tee must be an ten by ten by eight inch Tee, with eight inch gate valve and pipe to the fire hydrant.
5. The Tee at fire hydrant at station 4 + 06.54 must be eight by eight by six inch Tee.
6. All of the fire hydrant runs must be eight inch pipe with eight by eight by six inch Tees at the fire hydrants.
7. The irrigation meter will need a Double Check Valve Assembly behind the water meter setter.
8. At stations 6 + 54.09 and 5 + 29 .37 need to have two inch gate valves on the Tees.
9. The thrust block at station 18 + 50.44 need to be a ecology block, so the water may be turned back on after the connection is done.
10. The connection to the existing main on sheet 14 - drawing C6.3 is a ten inch main.
Reviewed by: Edward Smith, John I
Signed by: Edward Smith