05-0750 Sewer Email 030508 From: Jon Yanasak Sent: Wednesday, March 05, 2008 1:45 PM To: Jim Gibson Subject: Tahoma Terra Muti family housing. CJim, I understand that some confusion existed with regard to whether or not we would be requiring a baffle wall in the 3000 gallon holding tanks for the Multi-Family project. Unfortunately, I had given Randy some bad information before he went to the pre-con this morning as the prints that we have are incomplete and show such things as round tanks etc. I was in the middle of another project when Randy came to me for clarification on what you and I had agreed on before you left for vacation. Sorry about the confusion. Here is what we want: The 3000 gallon tanks should NOT have a baffle wall. The 1500 gallon pump tanks SHOULD have a baffle wall. I have actually given this some more thought and I’m OK with this one, but in the future I would rather see the pump tank also be a 3000 gallon tank due to the issue of reserve capacity. With the 1500 gallon pump tank we had better respond to an alarm rapidly! With 8 units being served by this 1500 gallon tank, it won’t take long to back-up into the buildings. Jon Yanasak City of Yelm Sewer Dept. Mgr Po Box 479 Yelm Wa 98597 Phone 360-458-8411 Fax 360-458-8166 jony@ci.yelm.wa.us