Loading...
DGWaterDetail6-4.26'X3' OPENING PER NOTE ~3 CEMENT CONC. SIDEWALK OR FINISHED GRADE ~ ADJUST TO MATCH WITH CONC. COLLARS FINISHED GRADE, SEAL INTERIOR WITH MORTAR. uooii ro'~z PRECAST CONC. VAULT ~OOER (UTILITY VAULT CO. OR APPROVED EQUAL) ~~ SLOPE \ygULTR WA LAINST VAULT TO BE PLACED LEVEL `SUMP WITH SLOPING FLOOR 1. IN AREAS OF HIGH GROUNDWATER A 1/4 HP SUMP PUMP SHALL BE INSTALLED IN THE SUMP PIT OF THE VAULT. IT SHALL BE WIRED PER WASHINGTON STATE ELECTRICAL CODE AND INSPECTED BY A7 STATE ELECTRICAL INSPECTOR. THE DISCHARGE PIPE SHALL BE CONNECTED 70 THE NEAREST APPROVED ON-SITE S70RM DRAINAGE STRUCTURE OR DRAIN TO DAYLIGHT. WHERE NO GROUNDWATER IS PRESENT USE A 2"6 DRAIN HOLE WITH 1/4 CUBIC YARD OF WASHED DRAIN ROCK. 2 THE VAULT SHALL BE A PRECAST CONCRETE VAULT SIZED TO MEET THE CLEARANCE REQUIREMENTS SHOWN ON DETAIL ~{6-5. 3. REMOVABLE DOORS SHALL BE A MINIMUM OF 6'-0" X 3'-0" DIAMOND PLATE HINGED LOCKING DOORS, WITH HINGES LOCATED AT EACH END OF OPENING. DOORS SHALL HAVE AN H-20 LOAD RATING IN AREAS THAT ARE SUBJECT TO VEHICLE TRAFFIC. DOORS SHALL BE SPRING LOADED WITH OPEN POSITION LOCK. 4. A GALVANIZED LADDER SHALL BE SET INSIDE THE VAULT FOR ACCESS INTO THE VAULT. I7 SHALL BE SECURED TO THE VAULT WITH t/2" DIA. BOLTS EPOXIED TO THE VAULT LID AND FLOOR. 5. A BILCO LADDER UP SAFETY POST MODEL N0. 2 SHALL BE ATTACHED TO THE LADDER STEPS. CITY OF YELM DEPT. OE PUBLIC WORKS WATER VAULT DETAILS APPROVE DGWG. N0. PUBLIC W0~ IRECTOR DATE V - ~~ ES~JEG~TP~4/2007/2007