DGWaterDetail6-7Top view operating nuf
^-Limits of payment
Paint Hydrant Weather shield
Sun Yellow High and Hydrant Lock
Grade Enamel Bonnet
# 13312
21/z"Hose connection
with threads
~--4 ~/z" Steamer connection
- __ with NST threads
,~. & 5" Storz adapter
F.o Style 5-37 w/SC cap
r4 ~~~e 18"-24" I
I I
To suit Standpipe
trench
depth 3' Minimum -
Each Pippe Joint 6
1106 EBAA Iron,
8„ Inc. Megalug
i ; ;:
6" Class 52 ductile iron
pipe cut to length
6" gate valve, FL X MJ
See note below
Varies -
~- 4"x8"x16" concrete block
Hydrant shoe
Backfill to top of drain ring housing
bolts with 2~~ washed rock as shown
6' x 6~ sheet of 11 mil. plastic or con-
struction fabric, covering 2" washed rock
Notes
1. Hydrants shall be located in
accordance with Section 6.060.
In addition, a minimum three foot
radius unobstructed working ^rea shall
be provided around all hydrants.
2. Hydrants shall be Dresser M & H
Reliant style 929, Clow Medallion or
American AVK Series 2780 or Mueller
Centurion
3. Gate valves shall be resilient wedge
NRS with 0-ring seals. Valve ends shall
be Mechanical joint by ANSI flanges.
Valves shall conform to AWWA 509-80.
Valves shall be Mueller M&H, Kennedy,
Clow R/W or Waterous Series 500.
4. Fire Hydrant lock payment is required
city will order and install.
Plastic barrier between
thrust block and tee
Concrete thrust block
cast-in-place against
fitting only
CITY OF YELM, WASHINGTON
DEPT. OF PUBLIC WORKS
FIRE HYDRANT
APFRQy,~Q~ DWG. N0.
l:w r
PUBLIC WORKS DIRECTOR DATE 6-~
DES. DWN. CKD. DATE
ES JEG TP Q~2007
HYDRANT OFFSET
See valve box and
valve stem detail-
6-11
Ground
6" Flanged fire
hydrant tee