07-0135 Civil #3 100208 From: Steve Harrington
Sent: Thursday, October 02, 2008 11:05 AM
To: Karen Bennett
Subject: SPR-07-0135-YL Today's Dental Review # 3 Comments
?Karen: The following are comments for SPR-07-0135-YL Today’s Dental:
The step tank will have to be traffic rated, with no parking over tank per sewer dept. previous request.
Submittals are usually submitted with step tank calcs at time of civil plan submittal for review and approval.
Note 6 on Sheet Notes for sheet C 14.01 sheet 7 of 22 calls out the wrong detail callout (C 04.12 Detail “A”).
I did not see any indication of what storm water management manual was used for this project. I assume that the 2005 D.O.E. Storm Water Management Manual was used for this project,
since the storm water treatment devices used are considered UIC’s in which would trigger the 2005 D.O.E. manual to be used for storm water design. Please clarify.
Thank you,
Steve Harrington
Engineering / Civil Inspector
City of Yelm
Office (360) 458-8423 / Field (360) 561-4264