2020.0061.BP0006 ELECTRICAL PAGES - Grocery OutletLIGHTING CONTROLS ARE INTEGRATED INTO THE REFRIGERATIONCONTROLS SYSTEM. REFER TO REFRIGERATION SETFOR DETAILS OF LIGHTING CONTROL PROVIDED BYREFRIGERATION PACKAGE.1. ALL WIRE TO BE THHN/THWN COPPER, STRANDED EXCEPT WHERE NOTED OTHERWISE.2. ALL DEVICES AND EQUIPMENT INSTALLED OUTDOORS OR EXPOSED TO THE WEATHER SHALL BE OF WEATHERPROOF CONSTRUCTION.3. ALL DEVICES SHALL BE SPECIFICATION GRADE. ALL SINGLE AND GANGED PLATES SHALL BE THERMOPLASTIC AND SHALL MATCH THE DEVICE IN COLOR.COORDINATE DEVICE COLOR WITH THE ARCHITECT PRIOR TO INSTALLATION. GANG DEVICES AT GROUP LOCATIONS UNDER A SINGLE COVER PLATE.4. THE ELECTRICAL PLANS ARE SCHEMATIC IN NATURE AND ARE NOT INTENDED TO SHOW ALL OF THE ARCHITECTURAL DETAIL OR SPECIFICS OFELECTRICAL CONSTRUCTION. TAKE ALL DIMENSIONS FROM THE ARCHITECTURAL DRAWINGS.5. NOT USED.6. ALL CONNECTIONS TO MECHANICAL EQUIPMENT SHALL BE MADE WITH A MINIMUM OF 24" OF WEATHERPROOF FLEXIBLE CONDUIT TO PREVENT SOUNDAND VIBRATION TRANSMISSION TO THE STRUCTURE.7. COORDINATE ALL MOTOR OVERLOADS AND/OR FUSES FURNISHED BY THIS CONTRACT WITH THE ACTUAL EQUIPMENT INSTALLED. SIZE OVERLOADS BASEDON MOTOR NAMEPLATE FULL LOAD CURRENT AND SERVICE FACTOR. FUSES FOR MOTOR AND TRANSFORMER CIRCUITS SHALL BE DUAL ELEMENT. FUSESFOR OTHER "NON-INRUSH" LOADS SHALL BE FAST ACTING. ALL FUSES SHALL BE CURRENT LIMITING CLASS RK5 OR CLASS L UNLESS OTHERWISE NOTED.8. GROUNDING CONDUCTORS ARE GENERALLY NOT SHOWN. GROUND AND BOND ALL EQUIPMENT, RACEWAYS, MOTORS, PANELBOARDS ANDSWITCHBOARDS, ETC. IN ACCORDANCE WITH NEC ARTICLE 250.9. BONDING OF ALL INTERIOR METAL PIPING SHALL BE IN ACCORDANCE WITH ARTICLE 250-90 AS FOLLOWS:A. ALL INTERIOR METAL WATER PIPING SHALL BE BONDED TO ONE OR MORE GROUNDING ELECTRODES USED. THE BONDING JUMPING SHALL BESIZED IN ACCORDANCE WITH TABLE 250-66.B. INTERIOR METAL PIPING THAT MAY BECOME ENERGIZED (i.e. GAS PIPING, ETC.), SHALL BE BONDED TO ONE OR MORE GROUNDING ELECTRODESUSED. THE BONDING JUMPER SHALL BE SIZED IN ACCORDANCE WITH TABLE 250-122, USING THE RATING OF THE CIRCUIT THAT MAY ENERGIZE THEPIPING.10. INSTALL ALL WALL MOUNTED POWER, TELEPHONE AND DATA OUTLETS AT +18" A.F.F. UNLESS OTHERWISE NOTED. INSTALL ALL LIGHTING CONTROLSWITCHES, FIRE ALARM PULLSTATIONS, FIREMANS TELEPHONE JACKS, AND WALL TELEPHONE JACKS AT +48" AFF, UNLESS OTHERWISE NOTED. ALLHEIGHT MEASUREMENTS SHALL BE TO THE CENTERLINE OF THE DEVICE.11. CONDUCTOR PENETRATION OF FIRE RATED PORTIONS OF A STRUCTURE SHALL BE EFFECTIVELY SEALED AND SLEEVED WITH STEEL FLEX 3 FEET EACHSIDE OF THE PENETRATION, OR OTHER APPLIED METHODS.12. INSTALLATION INSTRUCTIONS FOR ALL LISTED EQUIPMENT SHALL BE MADE AVAILABLE TO THE BUILDING INSPECTOR AT THE TIME OF INSPECTION.13. ALL LIGHT SWITCHES NOT WITHIN SIGHT OF LUMINAIRES SHALL BE EQUIPPED WITH A PILOT LIGHT.14. WIRES FOR MECHANICAL CONTROLS AND FIRE ALARM SHALL BE IN CONDUITS WHERE REQUIRED BY CODES.15. WIRES SHALL BE IN CONDUITS WHERE THERE IS EXPOSURE TO THE ELEMENTS OR POTENTIAL DAMAGE (FOR EXAMPLE, IN WAREHOUSE UNDER 10'-0").16. A WORKING SPACE OF NOT LESS THAN 30 INCHES IN WIDTH, 36 INCHES IN DEPTH AND 78 INCHES IN HEIGHT SHALL BE PROVIDED IN FRONT OF ELECTRICALSERVICE EQUIPMENT. NO STORAGE OF ANY MATERIALS SHALL BE LOCATED WITHIN THE DESIGNATED WORKING SPACE.17. PROVIDE APPROVED HANDLE TIE FOR ALL MULTIWIRE BRANCH CIRCUITS AS REQUIRED PER NEC ART. 210.4(B).18. ELECTRICAL CONTRACTOR SHALL FULLY REVIEW REFRIGERATION DRAWINGS AND SHALL INCLUDE IN BID ALL WORK THAT IS TO BE COMPLETED BYELECTRICAL CONTRACTOR, INCLUDING ALL SWITCHES, CONDUITS, BELDEN CABLES, CONTROL WIRES, POWER WIRES ETC, AS CALLED OUT ONREFRIGERATION DRAWINGS FOR A COMPLETE AND OPERABLE REFRIGERATION SYSTEM. NO CHANGE ORDER SHALL BE ALLOWED.19. COMMISSIONING AND OVERSEEING THE INSTALLATION OF ELECTRICAL SYSTEMS SHALL BE PERFORMED BY OTHERS.20. ALL ELECTRICAL WORK SHALL BE DESIGNED PER 2014 NATIONAL ELECTRICAL CODE, AND 2015 WASHINGTON STATE ENERGY CODE.21. 110.2 APPROVAL:ALL ELECTRICAL EQUIPMENT SHALL BE LABELED, LISTED OR CERTIFIED BY A NATIONALLY RECOGNIZED TESTING LABORATORYACCREDITED BY THE UNITED STATES OCCUPATIONAL SAFETY HEALTH ADMINISTRATION.22. EACH MULTIWIRE BRANCH CIRCUIT SHALL BE PROVIDED WITH A MEANS THAT WILL SIMULTANEOUSLY DISCONNECT ALL UNDERGROUND CONDUCTORS ATTHE POINT WHERE THE BRANCH CIRCUIT ORIGINATES, ART. 210.4(B). SEE PANEL SCHEDULES HANDLE-TIE NOTE.23. THE MAXIMUM COMBINED VOLTAGE DROP ON BOTH INSTALLED FEEDER CONDUCTORS AND BRANCH CIRCUIT CONDUCTORS TO THE FARTHESTCONNECTED LOAD OR OUTLET SHALL NOT EXCEED 5%.DRAWING NUMBERE1.0E2.0E3.0E4.0E5.0E6.0E7.0DRAWING TITLEELECTRICAL OVERVIEW SHEETELECTRICAL LIGHTING PLANELECTRICAL POWER PLANREFRIGERATION POWER PLANELECTRICAL DETAILS SHEETELECTRICAL SINGLE LINE AND RISER DIAGRAMELECTRICAL SPECIFICATIONS1PHSINGLE-PHASE1PSINGLE POLE3PHTHREE-PHASE4WFOUR-WIREA/EARCHITECT/ENGINEERACALTERNATING CURRENT ORARMORED CABLEAFAMPERE FRAME OR AMP FUSEAFFABOVE FINISHED FLOORAFGABOVE FINISHED GRADEAHJAUTHORITY HAVING JURISDICTIONAICAMPERE INTERRUPTING CAPACITYALTALTERNATEAMPAMPEREASCAMPS SHORT CIRCUITATAMPERE TRIPATSAUTOMATIC TRANSFER SWITCHAUTOAUTOMATICBFFBELOW FINISH FLOORBLDGBUILDINGBRKRBREAKERCCONDUITCCTVCLOSED CIRCUIT TELEVISIONcdCANDELACDCONSTRUCTION DOCUMENTSCKTCIRCUITCLDCURRENT LIMITING DEVICECLGCEILINGCOAXCOAX CABLECOMMCOMMUNICATIONCONTRCONTRACTORCLCASE LIGHTINGCTCURRENT TRANSFORMERCUCOPPERDCDIRECT CURRENTDISCDISCONNECTDSDISCONNECT SWITCHDWGDRAWINGECELECTRICAL CONTRACTORELECELECTRIC OR ELECTRICALELEVELEVATOREMERGEMERGENCYEMTELECTRICAL METALLIC TUBINGEWCELECTRIC WATER COOLEREWHELECTRIC WATER HEATERFAFIRE ALARMFAAPFIRE ALARM ANNUNCIATOR PANELFACPFIRE ALARM CONTROL PANELFLAFULL LOAD AMPSFLEXFLEXIBLE METALLIC CONDUITFLUORFLUORESCENTFTFEET OR FOOTFU SWFUSED SWITCHG OR GNDGROUND OR GENERATORGENGENERATORGFCIGROUND FAULT CIRCUITINTERRUPTERHIDHIGH INTENSITY DISCHARGEHPHORSEPOWERHTHEIGHTHZHERTZIESNAILLUMINATION ENGINEERING SOCIETYOF NORTH AMERICAIMCINTERMEDIATE METAL CONDUITIWHINSTANTANEOUS WATER HEATERJ-BOXJUNCTION BOXABBREVIATIONS LIST SHOWN IS FOR GENERAL REFERENCE ONLY. THE PRESENCE OF ANABBREVIATION DOES NOT IMPLY ITS USE ON THIS PROJECT. REFER TO THE DRAWINGS FOR SPECIFICABBREVIATIONS USED.kVKILOVOLTkVAKILOVOLT AMPEREkWKILOWATTLEDLIGHT EMITTING DIODELFLINEAR FEET (FOOT)LTGLIGHTINGLTG PNLLIGHTING PANELLVLOW VOLTAGEMAXMAXIMUMMCMETAL-CLADMCAMINIMUM CIRCUIT AMPSMCBMAIN CIRCUIT BREAKERMDPMAIN DISTRIBUTION PANELMECHMECHANICALMINMINIMUMMOCPMAXIMUM OVERCURRENT PROTECTIONMLOMAIN LUGS ONLYMTDMOUNTEDMTGMOUNTINGNANOT APPLICABLENECNATIONAL ELECTRICAL CODENEMANATIONAL ELECTRICALMANUFACTURERS ASSOCIATIONNEUT OR NNEUTRALNFPANATIONAL FIRE PROTECTIONASSOCIATIONNICNOT IN CONTRACTOCON CENTERPPOLEPENDPENDANTPFPOWER FACTORPHPHASEPNLPANELPTPOTENTIAL TRANSFORMERPVCPOLYVINYL CHLORIDE (PLASTIC)PWRPOWERRCPREFLECTED CEILING PLANRECRECESSEDRCPTLRECEPTACLERGSRIGID GALVANIZED STEELRMROOMRMSROOT MEAN SQUAREREQDREQUIREDSDSMOKE DETECTORSFSQUARE FOOT (FEET)SPECSPECIFICATIONSURFSURFACESWSWITCHSWBDSWITCHBOARDSWGRSWITCHGEARTCTIME CLOCKTELTELEPHONETYPTYPICALUONUNLESS OTHERWISE NOTEDUPSUNINTERRUPTIBLE POWER SUPPLYUCUNDER COUNTERVVOLTVAVOLT AMPEREVFDVARIABLE FREQUENCY DRIVEVOLTVOLTAGEWWATTWHWATER HEATERWPWEATHERPROOF (NEMA 3R WHILE INUSE - UTILIZE WEATHER RATEDRECEPTACLE)XFRTRANSFERXFMRTRANSFORMERELECTRICAL ABBREVIATIONSNTSELECTRICAL SYMBOL LEGENDNTSFLOOR FLUSH RECEPTACLEDESCRIPTIONSYMBOLS3S3MOTOR - NUMBER INDICATES HORSE POWER RATING.3-WAY SWITCHSINGLE POLE SWITCHEXIT SIGN ARROW & SHADING INDICATES DIRECTION OF SIGNEMERGENCY FIXTURETJQUAD RECEPTACLE, SHADED OUTLETS ARE GFI TYPEHOME RUN TO PANEL. ARROWS INDICATE QUANTITY OF CIRCUITS. CEILING AND WALL MOUNTED JUNCTION BOXTWIST LOCK RECEPTACLE, SHADED OUTLETS ARE GFI TYPEDROP RECEPTACLETELEPHONE OUTLETZZZZFUSED DISCONNECT SWITCH.FRACTIONAL HORSE POWER MOTORSSWITCH WITH THERMAL OVERLOAD FORCOMBINATION STARTER DISCONNECTSURFACE MOUNTED ELECTRICAL PANELRECESSED ELECTRICAL PANELNONFUSED DISCONNECT SWITCH. ALL ISOLATED GROUNDRECEPTACLES ARE TO BEPROVIDED WITH AN INSULATED,ISOLATED GROUND CONDUCTORFROM RECEPTACLE TO THEISOLATED GROUND BUS IN THEPANEL.SCALE COMMUNICATION OUTLET, E.C. SHALL PROVIDE J-BOX WITH 3/4"CAND PULL WIRE TO ABOVE CEILING. E.C. SHALL PROVIDE ALL NECESSARYJUNCTIONS TO FACILITATE COMMUNICATION WIRE AS REQUIRED. E.C.SHALL COORDINATE ALL EFFORTS WITH COMMUNICATIONS CONTRACTORPRIOR TO ROUGH-IN.CHECKOUT COMMUNICATION OUTLET, E.C. SHALL PROVIDE J-BOX WITH3/4"C AND PULL WIRE TO ABOVE CEILING. E.C. SHALL PROVIDE ALLNECESSARY JUNCTIONS TO FACILITATE COMMUNICATION WIRE ASREQUIRED. E.C. SHALL COORDINATE ALL EFFORTS WITHCOMMUNICATIONS CONTRACTOR PRIOR TO ROUGH-IN.COMPUTER NETWORK OUTLET, E.C. SHALL PROVIDE J-BOX WITH 3/4"C ANDPULL WIRE TO ABOVE CEILING. E.C. SHALL PROVIDE ALL NECESSARYJUNCTIONS TO FACILITATE COMMUNICATION WIRE AS REQUIRED. E.C.SHALL COORDINATE ALL EFFORTS WITH COMMUNICATIONS CONTRACTORPRIOR TO ROUGH-IN.RECESSED TYPE DISPLAY OR CLOCK HANGER RECEPTACLES E.C. SHALLUTILIZE ON WALL MOUNTED NEON, CLOCK OR FLY GLUELIGHTRECEPTACLES. CAT# SHALL BE EITHER HUBBLE 5236 FOR RECESSEDRECEPTACLE OR HANGER TYPE 5233. NOTE: SHANTY NEON SHALL HAVEQUAD RECEPTACLE MOUNT ON REAR OF SHANTY.DROP RECEPTACLE, SHADED OUTLETS ARE GFI TYPEDSPECIAL PURPOSE RECEPTACLE - VOLTAGE AND AMPS ASREQUIRED BY EQUIPMENT AND INDICATED IN PANEL SCHEDULE.E.C. SHALL MATCH CORD AND PLUG.SYMBOL LIST SHOWN IS FOR GENERAL REFERENCE ONLY. THE PRESENCE OF A SYMBOL DOES NOTIMPLY ITS USE ON THIS PROJECT. REFER TO THE DRAWINGS FOR SPECIFIC SYMBOLS USED.TDISOLATED GROUND QUADRECEPTACLE, SHADED OUTLETSARE GFI TYPEISOLATED GROUND DUPLEXRECEPTACLE, SHADED OUTLETSARE GFI TYPETRANSFORMER mSDUPLEX CONVENIENCE RECEPTACLE 20A, 125V, HUBBELL #5362-I SHADEDOUTLETS ARE GFI TYPEDATA OUTLETELECTRICAL DRAWINGS LISTNTSELECTRICAL GENERAL NOTESNTSFLOOR BOX WITH TWO (2) L5 DUPLEX RECEPTACLESFLOOR BOX WITH ONE (1) SPECIAL VOLTAGE L15/20R RECEPTACLEFLOOR BOX WITH SINGLE DATA POINT FOR XWEB WIRING - EITHER RJ45 JACK ON END OR WIRE OR RAW END ON CAT6 CABLESINGLE WALL OUTLET WITH ONE (1) SPECIAL VOLTAGE RECEPTACLE L15/20RXA-34 FT LINEAR LED FIXTURE - GROCERY OUTLETAPPROVED LIGHTINGTYPEA-2SAME AS TYPE 'A-1',EXCEPT WITH EMERGENCYBACKUP DRIVERDESCRIPTION120V32MANUFACTURER & CATALOG No.64VOLT WATTSNOTESXETWIN HEAD EMERGENCY LIGHT FIXTURE WITHBATTERY BACKUPUNIVERSAL MOUNTED EXIT SIGN WITH BATTERYBACKUP & REMOTE HEAD CAPABILITY. PROVIDEFACES AND CHEVRONS AS SHOWN ON THEDRAWINGS.LITHONIA: LE-S-W-G-120/277-ELN OR EQUALLITHONIA:WLTUMRCODED NOTES:1.FIXTURE AND LAMPS ARE FURNISHED BY GROCERY OUTLET. INSTALLED BY ELECTRICAL CONTRACTOR.B-1A-18 FT LINEAR LED FIXTURE - GROCERY OUTLETAPPROVED LIGHTING120V64SOLAR ELECTRIC WAY:SWW8FT4LED16K120V120V120V120V120V3232>510SUSPENDED BOTTOM OF FIXTURE AT +14'-0" A.F.F. VERIFY WITHGOI FOR ALL SUSPENDED FIXTURES.SUSPENDED BOTTOM OF FIXTURE AT +14'-0" A.F.F. WITH 90 MINEMERGENCY DRIVER. VERIFY WITH GOI FOR ALL SUSPENDEDFIXTURES.SOLAR ELECTRIC WAY:SWW8FT4LED16KEMLIGHTING FIXTURE SCHEDULENTSSOLAR ELECTRIC WAY:SWW4FT2LED16K8 FT LINEAR LED FIXTURE - GROCERY OUTLETAPPROVED LIGHTINGSOLAR ELECTRIC WAY:SWW8FT2LED16KSAME AS TYPE 'B-1',EXCEPT WITH EMERGENCYBACKUP DRIVERSOLAR ELECTRIC WAY:SWW8FT2LED16KEMB-2FOR STOCK/BOH AREAS, SUSPENDED BOTTOM OF FIXTURE AT+14'-0" A.F.F. VERIFY WITH GOI FOR ALL SUSPENDED FIXTURES.FOR STOCK/BOH AREAS, SUSPENDED BOTTOM OF FIXTURE AT+14'-0" A.F.F. VERIFY WITH GOI FOR ALL SUSPENDED FIXTURES.WITH 90 MIN EMERGENCY DRIVER.C-1120V324 FT LED WRAP FIXTURE - GROCERY OUTLETAPPROVEDSOLAR ELECTRIC WAY:SWW4FTWP2LED16KSURFACE MOUNTEDSUSPENDED BOTTOM OF FIXTURE AT +14'-0" A.F.F. VERIFY WITHGOI FOR ALL SUSPENDED FIXTURES.C-2120V32SOLAR ELECTRIC WAY:SWWSL4FTW-EMSURFACE MOUNTED. WITH 90 MIN EMERGENCY DRIVER.SAME AS TYPE 'C-1',EXCEPT WITH EMERGENCYBACKUP DRIVER1111111V-28 FT LINEAR LED VAPORLOCK FIXTURE -GROCERY OUTLET APPROVED120V64SOLAR ELECTRIC WAY:SWW8FTVL4LED16K1SURFACE MOUNTED COOLER/FREEZER BOXES (WET AREA OROUTSIDE)WITH 90 MIN EMERGENCY BACKUP.WITH 90 MIN EMERGENCY BACKUP. WET LOCATION LISTED.11CODEE2.2ENERGY COMPLIANCE FORMSSCOPE OF WORKNTSTHIS PROJECT IS THE TAKEOVER OF AN EXISTING BIG SUNBIRD SPORTING GOODS STOREAND CONVERSION INTO A SUPERMARKET. THERE IS AN EXISTING SERVICE WITH A 1200AMAIN SWITCH ON EXTERIOR OF BUILDING, THIS WILL BE REUSED. THE MDP WILL RECEIVENEW BREAKERS AS REQUIRED AND THE EXISTING BRANCH PANELS WILL BE REPLACED WITHNEW AS SHOWN IN EXISTING ELECTRICAL ROOM. ALL LIGHTING WILL BE REPLACED WITHLED AND NEW MORE EFFICIENT HVAC WILL BE INSTALLED.CODES AND REGULATIONNTS2015 INTERNATIONAL BUILDING CODE2017 NATIONAL ELECTRICAL CODE2015 INTERNATIONAL MECHANICAL CODE2015 WASHINGTON STATE ENERGY CODE2015 UNIFORM PLUMBING CODE2015 INTERNATIONAL FIRE CODEALL WORK PERFORMED MUST BE IN COMPLIANCE WITH 2017 NATIONAL ELECTRICAL CODESATELLITE IMAGE OF SITENTSE4.1ELECTRICAL ROOF POWER PLANE2.1EMERGENCY ELECTRICAL LIGHTING PHOTOMETRIC PLAN4275 N Palm St, Suite 100
Fullerton, CA 92835
(714) 578-2300 office
www.coolsysenergydesign.com
BBCCDDFFGGAA112233445566EELTGCONTMDPP1MAINSWITCHP2RPLPB-1B-1 B-1B-1
V-2B-2B-1B-1B-2B-1B-2B-1B-1B-1B-2B-1B-1B-1B-2B-2B-1B-1B-2B-1B-2B-1B-1B-1B-1B-2B-1B-1B-1B-1B-2B-1B-1B-2B-1B-1B-2B-2B-1B-1B-1B-2B-1B-1B-1B-2 B-1B-2B-1B-1B-1B-2B-1 V-2
V-2V-2V-2V-2C-2C-1C-2C-1C-1 C-2 C-1 C-2C-1C-1C-2C-1A-3A-2A-1A-1A-1A-1A-2A-1A-1A-2A-1A-1A-2A-1A-1A-2A-3A-1A-1A-1A-1A-1A-1A-1A-1A-1A-1A-1A-1A-1A-1A-1A-3A-2A-1A-2A-1A-1A-2A-1A-1A-2A-1A-1A-2A-1A-1A-2A-3A-1A-1A-1A-1A-1A-1A-1A-1A-1A-1A-1A-1A-1A-1A-1A-3A-2A-1A-2A-1A-1A-2A-1A-1A-2A-1A-1A-2A-1A-1A-2A-3A-1A-1A-1A-1A-1A-1A-1A-1A-1A-1A-1A-1A-1A-1A-1A-3A-1A-3A-2A-1A-1A-1A-1A-1A-1A-1A-1A-1A-1A-1A-1A-1A-1A-1A-2A-1A-1A-2A-1A-1A-2A-1A-1A-2A-1A-1A-2A-1A-1A-1A-1A-1A-1A-1A-1A-1A-1A-1A-1A-1A-1A-1A-1A-2A-2A-1A-1A-2A-1A-1A-2A-1A-1A-2A-1A-1A-1A-2A-1A-1A-2A-1A-1A-2A-1
A-1A-2A-1A-1A-2A-1A-1A-2A-1A-1A-2 B-1A-2A-1 C-2V-2V-2V-2V-2GENERAL NOTES1. INSTALLATION OF CONDUITS AND WIRES SHALL BE CONCEALED ABOVE THE CEILING AND BEHIND WALLS. WHERE NOT POSSIBLE, CONTRACTOR SHALLOBTAIN APPROVAL FOR EXPOSED LOCATIONS PRIOR TO ROUGH IN. USE WIREMOLD IN EXPOSED AREAS.2. REFER TO T24 VOLTAGE DROP TABLE TO DETERMINE POWER CONDUIT AND WIRE SIZE FOR 20A, 120/208V CIRCUITS, BASED ON THE EXACT LOAD ANDDISTANCE FROM THE ELECTRICAL PANEL.3. ALL EXIT AND EMERGENCY LIGHTS TO BE CONNECTED AHEAD OF ALL LIGHT SWITCHES AND CONTROLS.4. REFER TO ARCHITECTURAL DRAWINGS FOR MOUNTING HEIGHT AND EXACT LOCATION OF LIGHT FIXTURES.5. E.C. SHALL REFER TO REFRIGERATION DRAWINGS FOR LIGHTING AND EMS CONTROL INFORMATION AND REQUIREMENTS.6. COORDINATE ALL LIGHTING WORK WITH MECHANICAL AND FIRE SPRINKLER WORK.7. PROVIDE APPROVED HANDLE TIE FOR ALL MULTIWIRE BRANCH CIRCUITS AS REQUIRED PER NEC ART. 210.4(B).8. THE BOTTOM OF THE RECEPTACLE OUTLET BOXES SHALL NOT BE LESS THAN FIFTEEN INCHES ABOVE FINISHED FLOOR AND THE TOP OF THE OUTLETBOXES FOR CONTROLS AND SWITCHES SHALL NOT BE MORE THAN FORTY-EIGHT INCHES ABOVE THE FINISHED FLOOR.9. E.C. SHALL PROVIDE ADDITIONAL EMERGENCY EGRESS LIGHTING AND EXIT SIGNAGE PER FIRE INSPECTOR REQUIREMENTS.9101112E.C. SHALL PROVIDE POWER FOR STORE SIGNS. E.C. SHALL COORDINATE EXACT LOCATION WITH ARCHITECT AND OWNER PRIOR TO INSTALLATION.NOT USED.PROVIDE A TOGGLE SWITCH FOR THE CONNECTION OF CEILING MOUNTED EXHAUST FAN FURNISHED AND INSTALLED BY M.C. AND CONNECTEDBY E.C. EXHAUST FAN SHALL BE 120V, 1 PHASE, CONTROLLED BY SAME OCCUPANCY SENSOR/SWITCH AS ROOM LIGHT. COORDINATE EXACTLOCATION AND REQUIREMENTS WITH M.C.1314120 MINUTE HOUSEKEEPING OVERRIDE MOTION SENSOR. PROVIDE 2LP-18 AWG. CABLE FOR POWER AND CONTROLS. COORDINATE EXACTLOCATION AND REQUIREMENTS WITH R.C.5678CODED NOTES1234PHOTOCELL FOR DAYLIGHTING CONTROL. SEE REFRIGERATION DRAWINGS FOR ADDITIONAL INFORMATION AND REQUIREMENTS.-CEILING MOUNTED OCCUPANCY SENSOR WITH POWER PACK IN FREEZER/COOLER. WET, REFRIGERATION LISTED, BY WATTSTOPPER CB-100 OREQUAL.SEE REFRIGERATION DRAWINGS AND REFRIGERATION POWER PLANS (E4.0) FOR COOLER BOX LIGHTING INFORMATION.-WALL SWITCH OCCUPANCY SENSOR (VACANCY TYPE FOR OFFICES <250 SQ FT.) WITH ON/OFF AND DIMMING, DUAL TECHNOLOGY,BY SENSOR SWITCH nWSX-PDT-LV-DX OR EQUAL. SENSOR SHALL BE CONNECTED VIA CAT-5 WITH POWER PACKS FEEDING LIGHTFIXTURES (nPP16-D OR EQUAL) AND FANS/CONTROLLED OUTLETS (nPP16-PLT24 OR EQUAL). VERIFY FINAL LOCATION PRIOR TOROUGH-IN.PROVIDE POWER PACKS TO FEED LIGHT FIXTURES BY SENSOR SWITCH nPP16-D OR EQUAL AND FANS/CONTROL OUTLETS BY SENSOR SWITCHnPP16-PLT24 OR EQUAL.PROVIDE CAT-5 CABLE AS A CONNECTION BETWEEN POWER PACKS AND COMPATIBLE LOW VOLTAGE OCCUPANCY SENSORS.-DIMMING CONTROL WIRING HOMERUN TO DIMMING MODULES.SEE DETAIL 2/E5.0 AND REFRIGERATION DRAWINGS CONTROL DETAILS FOR COMPLETE LIGHTING CONTROL DETAILS AND REQUIREMENTS.SALES FLOOR AND STOCK ROOM LOCAL AREA ON/OFF AND DIMMING LIGHTING CONTROL AS REQUIRED BY WASHINGTON STATE ENERGY CODEIS PROVIDED BY THE LIGHTING CONTROL TOUCHSCREEN PANEL. THE TOUCHSCREEN IDENTIFIES THE LIGHTS BEING SERVED ANDANNUNCIATES THEIR STATUS AS ALLOWED. SWITCH SYMBOL SHOWN ON PLAN IS SYMBOLIC, NO PHYSICAL SWITCH IS REQUIRED.120 MINUTE OVERRIDE AS REQUIRED BY WASHINGTON STATE ENERGY CODE, LOCATED IN THE EMS PANEL. COORDINATE WORK ANDREQUIREMENTS WITH REFRIGERATION CONTRACTOR AND GOI PROJECT MANAGER.10. EXIT SIGNS SHALL BE INTERNALLY OR EXTERNALLY ILLUMINATED AT ALL TIMES. EXTERNALLY ILLUMINATED EXIT SIGNS SHALL BE CONNECTED TO ANEMERGENCY POWER SYSTEM (BATTERIES, UNIT EQUIPMENT OR AN ON-SITE GENERATOR) THAT WILL ILLUMINATE THE EXIT SIGNS FOR A DURATION OFNOT LESS THAN 90 MIN IN CASE OF PRIMARY POWER LOSS (C.B.C. 1011).DIMMING MODULE 01(VESTIBULE)7LP-1LP-2LP-2LP-2LP-2LP-2LP-2LP-2LP-2LP-2LP-2LP-2LP-2LP-2LP-2LP-3LP-3LP-3LP-3LP-3LP-3LP-3LP-3LP-3LP-3LP-3LP-3LP-3LP-3LP-4EMLP-4, EMLP-4EMLP-4EMLP-4EMLP-4EMLP-4EMLP-4, EMLP-4, EMLP-4, EMLP-4, EMLP-4, EMLP-4, EMLP-4, EMLP-4, EMLP-4, EMLP-4, EMLP-4, EMLP-5, EMLP-5, EMLP-5, EMLP-5, EMLP-5, EMLP-5, EMLP-5, EMLP-5, EMLP-5, EMLP-5, EMLP-5, EMLP-5, EMLP-4EMLP-6LP-6LP-6LP-6LP-6LP-6LP-6LP-6LP-6LP-6LP-6LP-6LP-6LP-6LP-6LP-6LP-6LP-6LP-6LP-6LP-6LP-6LP-6LP-6LP-6LP-6LP-6LP-6LP-6LP-6LP-6LP-6LP-6LP-7LP-7LP-7LP-7LP-7LP-7LP-7LP-7LP-7LP-7LP-7LP-7LP-7LP-7LP-7LP-7LP-7LP-7LP-7LP-7LP-7LP-7LP-7LP-7LP-7LP-7LP-8LP-8LP-8LP-8LP-8LP-8LP-8LP-8LP-8LP-8LP-8LP-8LP-8LP-8LP-8LP-8LP-8LP-8LP-8LP-8LP-8LP-8LP-8LP-8LP-8LP-8LP-9LP-9LP-9LP-9LP-9LP-9LP-9LP-9LP-9LP-9LP-9LP-9LP-9LP-9LP-9LP-9LP-9LP-9LP-9LP-9LP-9LP-9LP-9LP-9LP-9LP-9LP-10LP-10LP-10LP-10LP-10LP-10LP-4EMLP-10LP-15LP-15LP-15LP-15LP-15LP-15LP-15LP-15LP-15OS32OS32OS32LP-11LP-11LP-11LP-11LP-11LP-11LP-11LP-13EMLP-13EMLP-13EMLP-13EMLP-13EMLP-13, EMLP-13, EMLP-13, EMLP-13, EMLP-13, EMLP-13, EMLP-13, EMLP-13, EMLP-13, EMLP-13, EMLP-14LP-14LP-14LP-14LP-14LP-14LP-14LP-14LP-14LP-14LP-14LP-14LP-14LP-14LP-14LP-14LP-14LP-14LP-14LP-14LP-14LP-14LP-14LP-14LP-14LP-14LP-14LP-14LP-14LP-14LP-14LP-14LP-14LP-14LP-18LP-18LP-18LP-18LP-17LP-17LP-17LP-17LP-17LP-17LP-17LP-17DIMMING MODULE 02(SALES FLOOR)7DIMMING MODULE 03(BACK OF HOUSE)7PC1PC1PC1PP PP 4PP PP 4PP PP PP PP 1212OS15PP D136PP PP 54(TYP.)(TYP.)(TYP.)BALESTORAGE117SALESFLOOR101STOCKROOM111VESTIBULE100TRASHENCLOSURE116EXISTINGELECTRICALROOM114DAIRYCOOLER104BACKOFFICE103FRONTOFFICE102BREAKROOM110ALCOVE113WOMENS108MEN'S109EQUIPMENTROOM115W-1W-1PROVIDE LOW-VOLTAGE WALL POD, SINGLE CHANNEL WITH ON/OFF DIMMING CONTROL, BY SENSOR SWITCH nPODM DX OR EQUAL. VERIFYFINAL LOCATION PRIOR TO ROUGH IN.PP PP 13PP PP 13LP-19XLP-19LP-19XLP-19LP-19XW-1LP-19XLP-19W-1LP-19XLP-19LP-2010LP-1610LP-2210LP-1LP-181/8"=1'-0"ELECTRICAL LIGHTING PLAN14275 N Palm St, Suite 100
Fullerton, CA 92835
(714) 578-2300 office
www.coolsysenergydesign.com
BBCCDDFFGGAA112233445566EEB-1B-1 B-1B-1
V-2B-2B-1B-1B-2B-1B-2B-1B-1B-1B-2B-1B-1B-1B-2B-2B-1B-1B-2B-1B-2B-1B-1B-1B-1B-2B-1B-1B-1B-1B-2B-1B-1B-2B-1B-1B-2B-2B-1B-1B-1B-2B-1B-1B-1B-2 B-1B-2B-1B-1B-1B-2B-1 V-2
V-2V-2V-2V-2C-2C-1C-2C-1C-1 C-2 C-1 C-2C-1C-1C-2C-1A-3A-2A-1A-1A-1A-1A-2A-1A-1A-2A-1A-1A-2A-1A-1A-2A-3A-1A-1A-1A-1A-1A-1A-1A-1A-1A-1A-1A-1A-1A-1A-1A-3A-2A-1A-2A-1A-1A-2A-1A-1A-2A-1A-1A-2A-1A-1A-2A-3A-1A-1A-1A-1A-1A-1A-1A-1A-1A-1A-1A-1A-1A-1A-1A-3A-2A-1A-2A-1A-1A-2A-1A-1A-2A-1A-1A-2A-1A-1A-2A-3A-1A-1A-1A-1A-1A-1A-1A-1A-1A-1A-1A-1A-1A-1A-1A-3A-1A-3A-2A-1A-1A-1A-1A-1A-1A-1A-1A-1A-1A-1A-1A-1A-1A-1A-2A-1A-1A-2A-1A-1A-2A-1A-1A-2A-1A-1A-2A-1A-1A-1A-1A-1A-1A-1A-1A-1A-1A-1A-1A-1A-1A-1A-1A-2A-2A-1A-1A-2A-1A-1A-2A-1A-1A-2A-1A-1A-1A-2A-1A-1A-2A-1A-1A-2A-1
A-1A-2A-1A-1A-2A-1A-1A-2A-1A-1A-2 B-1A-2A-1 C-2V-2V-2V-2V-278.6186.5186.578.678.6186.5186.578.671.2115.771.2115.771.2115.7115.771.2 71.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.2 71.2115.7115.771.271.2115.7115.771.2 71.2115.7115.771.2 71.2115.7115.771.2 71.2115.7115.771.2 71.2115.7115.771.2 71.2115.7115.771.2 71.2115.7115.771.2 71.2115.7115.771.2 71.2115.7115.771.2 71.2115.7115.771.2 71.2115.7115.771.2 71.2115.7115.771.2 71.2115.7115.771.2 71.2115.7115.771.2 71.2115.7115.771.2 71.2115.7115.771.2 71.2115.7115.771.2 71.2115.7115.771.2 71.2115.7115.771.2 71.2115.7115.771.2 71.2115.7115.771.2 71.2115.7115.771.2
71.2
115.7
115.7
71.2
71.2
115.7
115.7
71.2
71.2
115.7
115.7
71.2
71.2
115.7
115.7
71.2
71.2
115.7
115.7
71.2
71.2
115.7
115.7
71.2
71.2
115.7
115.7
71.2
71.2
115.7
115.7
71.2
71.2
115.7
115.7
71.2
71.2
115.7
115.7
71.2
71.2
115.7
115.7
71.2
71.2
115.7
115.7
71.2
71.2
115.7
115.7
71.2
71.2
115.7
115.7
71.2
71.2
115.7
115.7
71.2
71.2
115.7
115.7
71.2
71.2
115.7
115.7
71.2
71.2
115.7
115.7
71.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2
115.7
115.7
71.2
71.2
115.7
115.7
71.2
71.2
115.7
115.7
71.2
71.2
115.7
115.7
71.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.771.2115.771.2115.771.2115.771.2115.771.2115.771.2115.771.2115.771.2115.771.2115.771.2115.771.2115.771.2115.771.2115.771.2115.771.2115.7
71.2115.771.2115.771.2115.771.2115.771.2115.771.2115.771.2115.771.2115.778.6186.5186.578.678.6186.5186.578.678.6186.5186.578.678.6186.5186.578.678.6186.5186.578.678.6186.5186.578.678.6186.5186.578.678.6186.5186.578.678.6186.5186.578.6 78.6186.5186.578.671.2115.7115.771.2 71.2115.7115.771.2 71.2115.7115.771.2 71.2115.7115.771.2 71.2115.7115.771.2 71.2115.7115.771.2 71.2115.7115.771.2 71.2115.7115.771.2 71.2115.7115.771.2 71.2115.7115.771.2 71.2115.7115.771.2 71.2115.7115.771.2 71.2115.7115.771.2 71.2115.7115.771.271.2115.7115.771.2 71.2115.7115.771.2 71.2115.7115.771.2 71.2115.7115.771.2 71.2115.7115.771.2 71.2115.7115.771.2 71.2115.7115.771.2 71.2115.7115.771.2 71.2115.7115.771.2 71.2115.7115.771.2 71.2115.7115.771.2 71.2115.7115.771.2 71.2115.7115.771.2 71.2115.7115.771.2 71.2115.7115.771.2 71.2115.7115.771.2 71.2115.7115.771.2 71.2115.7115.771.2
71.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.271.2115.7115.771.278.6186.5186.578.678.6186.5186.578.671.2115.7115.771.2 71.2115.7115.771.2 71.2115.7115.771.271.2115.7115.771.271.2115.7115.771.2 71.2115.7115.771.271.2115.7115.771.2 71.2115.7115.771.278.6186.5186.578.678.6186.5186.578.678.6186.5186.578.678.6186.5186.578.678.6186.5186.578.678.6186.5186.578.61/8"=1'-0"EMERGENCY ELECTRICAL LIGHTING PHOTOMETRIC PLAN14275 N Palm St, Suite 100
Fullerton, CA 92835
(714) 578-2300 office
www.coolsysenergydesign.com
4275 N Palm St, Suite 100
Fullerton, CA 92835
(714) 578-2300 office
www.coolsysenergydesign.com
BCDFGA112233445566ELTGCONTMDPP1MAINSWITCHP2RPLP(TYP. OF (5))16P1-52651313P1-48P1-4823P1-4547P1-(80,82,84)2425P1-56MEATCOOLERSTOCKROOM214P1-3726P1-494P1-414P1-3913P1-4613P1-46VESTIBULESALES FLOORPP15(TYP. OF (5))17(TYP. OF (5))18(TYP. OF (5))PPPPPPPPP1-1P1-3P1-5P1-7P1-9P1-12P1-14P1-16P1-18P1-20P1-2P1-4P1-6P1-8P1-1014P1-53SEE DETAIL FOR CABLE TRAYAND WIRE BASKET IN THIS SHEET12" CABLE TRAY12" DATA WIRE BASKETGFI+44"P1-2820P1-3412P1-32GFIP1-30GFIP1-30WOMENSMENSBREAKROOMGFI+48"GFI+48"GFI+48"P1-36P1-38P1-40P1-35P1-35P1-35IG715P1-31P1-4328P1-478P1-478P1-4760NF10P1-50 (CONTROLS)MDP-18P1-47P1-55P1-57P1-592830P1-61 P1-5111P2-(2,4)P2-(3,5)MDP-230NFP2-1312E-3.0P2-6P2-8EXISTINGELECTRICALROOMEQUIPMENT ROOMFREEZERCORRIDORP2-7P2-9P2-10TO CU-1TO CU-2TO CU-3P2-(23,25)30NFP2-(19,21)30NFP2-(20,22)30NFP2-(24,26)30NF9FRONTOFFICEBACKOFFICEP2-(12,14)30NF30NFP2-28RCP-13838393838c36c36c363838c3627c36P1-22P1-13P1-11P1-24P1-22P1-11P1-13P1-22P1-17P1-15P1-29P1-29P1-26P1-26P1-2735P1-2342444543P1-19P1-2137P1-2540414037GENERAL NOTESCODED NOTES289141213PROVIDE A J-BOX FOR CONNECTION OF POWER HAND DRYER. SEEARCH. SHEETS FOR ADA MOUNTING INFO.CONVENIENCE WALL MOUNT OUTLET WITH METAL COVER PLATE.MOUNT J-BOX AT +84" & PROVIDE FLEX CONDUIT WITH WALL MOUNTEDCLAMPS TO RECEPTACLE IN RACK TOE-KICK. VERIFY FINALINSTALLATION LOCATION WITH GOI PROJECT MANAGER PRIOR TOROUGH-IN.RECEPTACLE IN CEILING FOR SECURITY AND PUBLIC VIEWINGMONITORS. COORDINATE LOCATIONS WITH QUALITY SOLUTIONSPRIOR TO ROUGH-IN.QUALITY SOLUTIONS CONTACT: FALLON BELTRAN, 916-683-6834,FALLON@QSTELECOM.COM.1516181719PROVIDE ADDITIONAL ISOLATED GROUND WIRE.-PROVIDE QUAD RECEPTACLE FOR CHECK STAND MERCHANDISINGEQUIPMENT.PROVIDE POWER AND DATA OUTLETS CONNECTIONS AND POWERPOLE PER GOI CHECK STAND REQUIREMENTS.42COORDINATE EXACT POWER POLE LOCATION AND REQUIREMENTSWITH GOI PROJECT MANAGER AND FIXTURE INSTALLER.NOT USED202221BATTERY-POWERED EMERGENCY DOOR ALARM FOR THE MAN DOORS.DETEX 500 OR APPROVED EQUAL.E.C. TO VERIFY FUNCTIONALITY AND CONNECTIONS.NOT USED.2324COFFEE GRINDER RECEPTACLE. COORDINATE LOCATION WITHFIXTURE PLAN AND MERCHANDISING SET CREW PRIOR TO ROUGH-IN.2545E.C. IS REQUIRED TO EXTEND TELEPHONE AND FIBER TO RACK AREAAS REQUIRED. E.C. SHALL COORDIANTE WITH GOI I.T. REP FOR EXACTREQUIREMENTS AND RESPONSIBILITIES.43441120A, 120V RECEPTACLE FOR CONNECTION OF FLOOR SCRUBBER WITHBUILT-IN DISCONNECT SWITCH. VERIFY OUTLET, VOLTAGE, AMPERAGEREQUIREMENTS AND LOCATION WITH STORE OWNER PRIOR TOROUGH-IN. EQUIPMENT BY OWNER. CONDUIT, WIRING ANDCONNECTION BY E.C.3610PROVIDE DISCONNECT SWITCH FOR CONNECTION OF BALER. VERIFYRECEPTACLE, VOLTAGE, AMPERAGE REQUIREMENTS, AND LOCATIONWITH STORE OWNER PRIOR TO ROUGH-IN. EQUIPMENT BY OWNER.DISCONNECT, CONDUIT, WIRING, AND CONNECTION BY E.C.3435RECEPTACLE FOR EMPLOYEE TIME CLOCK AT +48"-+60" A.F.F.,PROVIDE LOW VOLTAGE WIRING THROUGH THE WALL FOR THECONNECTION OF KEYPAD. VERIFY FINAL INSTALLATION LOCATIONWITH GOI CONSTRUCTION MANAGER AND QUALITY SOLUTIONS PRIORTO ROUGH-IN.PROVIDE DUPLEX CONTROLLED RECEPTACLE. IT IS TO BECONNECTED VIA WALL SWITCH OCCUPANCY SENSOR, DUALTECHNOLOGY SET UP TO "MANUAL ON" MODE, BY SENSOR SWITCHnWSX-DT-LV OR EQUAL AND POWER PACK, BY SENSOR SWITCHnPP16-PLT24 OR EQUAL. REFER TO LIGHTING PLAN. CONTROLLEDRECEPTACLES SHALL BE CLEARLY MARKED TO DIFFERENTIATE THEM FROMNON-CONTROLLED RECEPTACLES.37MOUNT PLUGSTRIPS IN OFFICES ABOVE COUNTER WITH SIMPLEXOUTLETS EVERY 6". REFER TO ARCHITECTURAL DRAWINGS FOR MOREINFORMATION.3839401" EMT FROM DATA RACK TO EACH PHONE/DATA LOCATION -TERMINATE WITH J-BOX @ 18" AFF, STUB CONDUIT TO ABOVE CEILING.PROVIDE DEDICATED OUTLET FOR FAX.VERIFY LOCATION WITH OWNER.VERIFY OFFICE RECEPTACLES LAYOUT WITH QUALITY SOLUTIONSDATA PLANS PRIOR TO ROUGH-IN WORK. SEE ARCHITECTURAL OFFICEINTERIOR ELEVATIONS FOR OUTLET HEIGHTS.41IF A SOLID WALL (I.E. CONCRETE) OCCURS BETWEEN THE CHECKSTANDS AND OFFICE, CONTRACTOR TO PROVIDE AN OPENING INWALL AS REQUIRED FOR WIRING / CABLING TO PASS THROUGH WALL.TWO (2) QUAD OUTLETS AT THE BACK OF DATA RACK:ONE (1) AT +16" AFF, ONE (1) AT +48" AFF. VERIFY EXACT LOCATIONWITH QUALITY SOLUTIONS PRIOR TO ROUGH-IN.PROVIDE #6 GROUND FOR DATA RACK TO NEAREST GROUNDINGELEMENT OF BUILDING STRUCTURE.FOUR (4) 2"C FROM RACK STUBBED 6'-0" THROUGH CEILINGCONNECTING TO WIRE MOLDING FOR CABLING:ONE (1) VOICE/DATA, ONE (1) CAMERA, ONE (1) LOW VOLTAGE ANDONE (1) SPEAKER.7563RECEPTACLE MOUNTED AT +18" AFF. SURFACE MOUNT WITH ALLMETAL J-BOX AND COVER PLATE, TYPICAL. ON REFRIGERATION CHASEFOR SAMPLE CART. VERIFY LOCATION WITH GOI PROJECT MANAGERPRIOR TO ROUGH-IN.4E.C. SHALL POWER CONNECTIONS TO AUTO DOORS.RECEPTACLE FOR STORE OPEN SIGN. VERIFY MOUNTING HEIGHT ANDLOCATION WITH GOI PROJECT MANAGER PRIOR TO ROUGH-IN.31NEW INDOOR J-BOX WITH A TOGGLE SWITCH FOR CONNECTION OFSIGNAGE. E.C. TO VERIFY FUNCTIONALITY, CONNECTIONS AND EXACTLOCATION. REFER TO PANEL SCHEDULE FOR CIRCUIT NUMBER INFO.PROVIDE POWER AND LOW VOLTAGE RECEPTACLES FOR MEATSCALE. PROVIDE MINIMUM 3/4"C FOR POWER. PROVIDE RING ANDSTRING FOR DATA. VERIFY LOCATION WITH GOI PROJECT MANAGERPRIOR TO ROUGH-IN.RECEPTACLES MOUNTED AT +5'-0" AFF. SURFACE MOUNT WITH ALLMETAL J-BOX AND COVER PLATE, TYPICAL.PROVIDE A DISCONNECT SWITCH FOR CONNECTION OF FORKLIFTCHARGER. VERIFY OUTLET, VOLTAGE, AMPERAGE REQUIREMENTSAND LOCATION WITH STORE OWNER PRIOR TO ROUGH-IN. EQUIPMENTBY OWNER. DISCONNECT, CONDUIT, WIRING AND CONNECTION BY E.C.332627RECEPTACLE FOR SMART CART CHARGER. VERIFY MOUNTING HEIGHTAND LOCATION WITH GOI PROJECT MANAGER PRIOR TO ROUGH-IN.BURGLAR ALARM PANEL. PROVIDE DUPLEX OUTLET AT AT 12" BELOWCEILING, ABOVE SAFE. VERIFY LOCATION AND REQUIREMENTS WITHGOI PROJECT MANAGER.28PROVIDE RECEPTACLE FOR TELEPHONE SWITCHING CPU. VERIFYLOCATION AND REQUIREMENTS WITH GOI PROJECT MANAGER PRIORTO ROUGH-IN.29NOT USED.304'X4'X3/4" THICK FIRE RESISTIVE PLYWOOD WITH CODE APPROVEDGROUNDING MEANS FOR TELEPHONE. VERIFY LOCATION WITH GOIPROJECT MANAGER PRIOR TO ROUGH-IN. EXTEND TELEPHONESERVICE CONDUIT STUB TO BACKBOARD.MINIMUM OF 3' CLEARANCE IN FRONT OF THE ELECTRICAL EQUIPMENTSHALL BE PROVIDED. MARKINGS ON FLOOR TO INDICATE CLEARANCEAREA. RECTANGLE, PAINT WITH CONTRASTING COLOR, 4" BRUSHSTROKES WITH DIAGONAL LINES INSIDE WITH 6" LETTERS "NOSTORAGE" BLOCKED IN AND/OR LARGE STICKER SAYING THE SAMETHING.321ELECTRICAL CONTRACTOR SHALL FULLY REVIEW REFRIGERATION AND H.V.A.CDRAWINGS AND SHALL INCLUDE IN BID ALL WORK THAT IS TO BE COMPLETED BYELECTRICAL CONTRACTOR, INCLUDING ALL SWITCHES, CONDUITS, BELDENCABLES, CONTROL WIRES, POWER WIRES ETC, AS CALLED OUT ON REFRIGERATIONDRAWINGS FOR A COMPLETE AND OPERABLE REFRIGERATION SYSTEM.NO CHANGE ORDER SHALL BE ALLOWED.4647EVAC VACUUM DRAINAGE SYSTEM LOCATION.1.INSTALLATION OF CONDUITS AND WIRES SHALL BE CONCEALED ABOVE THE CEILING AND BEHIND WALLS. WHERE NOT POSSIBLE, CONTRACTORSHALL OBTAIN APPROVAL FOR EXPOSED LOCATIONS PRIOR TO ROUGH IN. USE WIREMOLD IN EXPOSED AREAS.2.REFER TO VOLTAGE DROP TABLE TO DETERMINE POWER CONDUIT AND WIRE SIZE FOR 20A, 120/208V CIRCUITS, BASED ON THE EXACT LOAD ANDDISTANCE FROM THE ELECTRICAL PANEL.3.PROVIDE APPROVED HANDLE TIE FOR ALL MULTIWIRE BRANCH CIRCUITS AS REQUIRED PER NEC ART. 210.4(B).4.THE BOTTOM OF THE RECEPTACLE OUTLET BOXES SHALL NOT BE LESS THAN FIFTEEN INCHES ABOVE FINISHED FLOOR AND THE TOP OF THEOUTLET BOXES FOR CONTROLS AND SWITCHES SHALL NOT BE MORE THAN FORTY-EIGHT INCHES ABOVE THE FINISHED FLOOR.20A, 120V, 1P COMBO SELF-TEST BLANK FACE GFCI OUTLET TO SERVETHE DRINKING FOUNTAIN IN ACCESSIBLE LOCATION.NOT USED.MOTORIZED VOLUME DAMPER, SUPPLIED AND INSTALLED BY H.V.A.C.,WIRED BY E.C., CONTROLS BY REFRIGERATION EMS. PROVIDE ALLWORK AS NECESSARY FOR A COMPLETE AND OPERABLE SYSTEM.EXACT LOCATION TO BE DETERMINED IN FIELD.NOT USEDLIGHTING CONTROL AND EVAC ALARM PANEL. FOR INDOOR/OUTDOORLIGHTING CONTROL AND DEMAND RESPONSE. FIELD-VERIFY EXACTLOCATION. (SEE EVAC LOCATION AND FRONT OFFFICE)TIME CLOCK SCHEDULING CONTROL SHALL BE 365 DAY, 24 HR, TYPE("HOLIDAY SKIP") PER T24 130.1(c)(4).CONTROL PANEL CAPABLE OF REDUCING LIGHTING OUT PUT BY AMINIMUM OF 15%. SEE REFRIGERATION DRAWINGS.PROVIDE 2C-18 AWG SHIELDED CABLE IN CONDUIT TO RACK.PROVIDE 2C-18 AWG SHIELDED CABLE IN CONDUIT TO AHU CONTROLPANEL.PROVIDE 2C-18 AWG CABLE TO FLOW SENSOR SWITCH.COORDINATE WITH R.C. SEE REFRIGERATION DRAWINGS.PROVIDE A DISCONNECT SWITCH FOR CONNECTION OF WATERHEATER. EQUIPMENT BY OWNER. DISCONNECT, CONDUIT, WIRING,AND CONNECTION BY E.C. VERIFY LOCATION PRIOR TO INSTALLATIONNOT USED.PROVIDE A DISCONNECT SWITCH FOR CONNECTION OF WATER HEATER.EQUIPMENT BY OWNER. DISCONNECT, CONDUIT, WIRING AND ELECTRICALCONNECTION B E.C. COORDINATE WITH PLUMBING CONTRACTOR ANDVERIFY LOCATION WITH GOI PRIOR TO ROUGH-IN.6PHONE AND DATA CABLECLEAN AND DIRTY POWER1/8"=1'-0"ELECTRICAL POWER PLAN11/4"=1'-0"ENLARGED OFFICE POWER PLAN24275 N Palm St, Suite 100
Fullerton, CA 92835
(714) 578-2300 office
www.coolsysenergydesign.com N.T.S.POWER POLE DETAIL3
BBCCDDFFGGAA123456EELTGCONTMDPP1MAINSWITCHP2RPLP1414RP-28RP-30,32FLFLRP-16RP-14FLFLFLRP-17RP-19F-ALF-ALD4DRP-1RP-3F-ALF-ALDD4RP-7222423202521RP-31SALES FLOORWOMENSMENSEMPLOYEEFLRP-12RP-10FLFLRP-13RP-1512P1-54F-ALRP-5D112711FREEZER27GFIRP-25FLRP-9RP-11BACK OFFICEFRONT OFFICEVESTIBULESDS1S DS11515
F-ALF-ALDD4RP-8F-ALRP-6D1515F-ALF-ALRP-2RP-4D4D1515D4DF-ALF-ALRP-34RP-36F-ALF-ALF-ALD4DDRP-40RP-386RP-2137DAIRY COOLERRP-279TSRP-261635342DS S
TS8(TYP. OF 2)MEAT COOLER1127RP-39EQUIPMENT ROOM3331RP-37MDP-71736P1-58EXISTINGELECTRICALROOMBACKROOM2DSS35347RP-237RP-412S DS3534RP-23TS TS 4(TYP. OF 2)RP-(22,24)8165 5RP-23RP-(18,20)8(TYP. OF 2)TSTS42635291830323#6+1#10G IN 3/4"C TO RACK POWERPANEL FOR CONDENSER POWERCONNECTION BY E.C. IN FIELDGFI,WPP1-4419RP-(33,35)FE23GENERAL NOTES1. INSTALLATION OF CONDUITS AND WIRES SHALL BE CONCEALED ABOVE THE CEILING, BEHIND WALLS, AND SHALL NOT BE UNDER THE SLAB. WHERE NOTPOSSIBLE, CONTRACTOR SHALL OBTAIN APPROVAL FOR EXPOSED LOCATIONS PRIOR TO ROUGH IN. USE WIREMOLD IN EXPOSED AREAS.2. REFER TO VOLTAGE DROP TABLE TO DETERMINE POWER CONDUIT AND WIRE SIZE FOR 20A, 120/208V CIRCUITS, BASED ON THE EXACT LOAD ANDDISTANCE FROM THE ELECTRICAL PANEL.3. PROVIDE APPROVED HANDLE TIE FOR ALL MULTIWIRE BRANCH CIRCUITS AS REQUIRED PER NEC ART. 210.4(B).4. THE BOTTOM OF THE RECEPTACLE OUTLET BOXES SHALL NOT BE LESS THAN FIFTEEN INCHES ABOVE FINISHED FLOOR AND THE TOP OF THE OUTLETBOXES FOR CONTROLS AND SWITCHES SHALL NOT BE MORE THAN FORTY-EIGHT INCHES ABOVE THE FINISHED FLOOR.ELECTRICAL CONTRACTOR SHALL FULLY REVIEW REFRIGERATION AND H.V.A.C DRAWINGS AND SHALL INCLUDE IN BID ALL WORK THAT IS TO BE COMPLETED BYELECTRICAL CONTRACTOR, INCLUDING ALL SWITCHES, CONDUITS, BELDEN CABLES, CONTROL WIRES, POWER WIRES ETC, AS CALLED OUT ON REFRIGERATIONDRAWINGS FOR A COMPLETE AND OPERABLE REFRIGERATION SYSTEM. NO CHANGE ORDER SHALL BE ALLOWED.CODED NOTES12ROLL UP DOOR SWITCH, USE BELDEN 8761 CABLE TO LIGHTING ANDEVAC PANEL DR. SWITCH CLOSED WHEN DOOR CLOSED. PROVIDEDAND INSTALLED BY R.C.FREEZER DOOR SWITCH PROVIDED AND INSTALLED BY R.C., WIRED BYE.C. BELDEN 8761 CABLE TO REFRIGERATION RACK. REFER TOREFRIGERATION DRAWINGS FOR WIRING REQUIREMENTS ANDPROVIDE ALL WORK FOR A COMPLETE AND OPERABLE SYSTEM.416171819MRLDS FOR COOLERS/FREEZERS. MOUNT BETWEEN 12"-18" AFF.FIELD VERIFY LOCATION. PROVIDE 2C-18 AWG. SHIELDED CABLE TOBOARD IN RACK PANEL BY E.C.PROVIDE 2C-18 AWG. CABLE TO XFMR IN RACK PANEL BY E.C.20A, 120V GFCI RECEPTACLE IN WEATHERPROOF ENCLOSUREAND IDENTIFIED AS "HEAVY-DUTY", PER NEC 406.9(A)(1).1514131112PROVIDE A J-BOX FOR CONNECTION OF REFRIGERATION BOX LIGHTS.FIXTURES AND LAMPS PROVIDED BY OWNER, INSTALLED BY E.C.REFER TO REFRIGERATION DRAWINGS FOR MORE INFORMATION.RECEPTACLE FOR PRODUCE MISTING SYSTEM LOCATED BEHINDPRODUCE CASE SURFACE MOUNTED ON WALL. COORDINATE FINALINSTALLATION LOCATION WITH GOI DIRECTOR OF REFRIGERATIONPRIOR TO ROUGH-IN.NOT USED.CORD DROP RECEPTACLE, TWISTLOCK L530, 120V, 30A, FROM CEILINGMOUNTED JUNCTION BOX FOR MED TEMP REFRIGERATION CASE.POWER CORDS SHALL REACH THE FLOOR + 10'-0" OF SLACK. VERIFYREQUIREMENTS WITH GOI PROJECT MANAGER PRIOR TO ROUGH-IN.RISER FOR ELECTRICAL CONDUITS. COORDINATE WITHREFRIGERATION AND ARCHITECTURAL PLANS. FIELD VERIFY FINALLOCATION WITH GOI REPRESENTATIVE.10PROVIDE 2#12+1#12G IN 3/4"C FOR 208V/1P HOT GAS DEFROST CONTROLTO RACK DEFROST CONTROL PANEL. REFER TO REFRIGERATIONDRAWINGS TO VERIFY ALL POWER AND CONTROL REQUIREMENTS ANDPROVIDE ALL REQUIRED WORK FOR A COMPLETE AND OPERABLE SYSTEM.98PROVIDE A DISCONNECT MEANS FOR REFRIGERATION BOX COILFAN/ANTI-SWEAT OR CASE LIGHTS. REFER TO REFRIGERATIONDRAWINGS FOR ADDITIONAL REQUIREMENTS.1/2"C FROM INSIDE THE DAIRY COOLER (CENTERED OVER DOOR, AND1" BACK) TO STRUCTURE ABOVE, WITH A 90 DEGREE SWEEP AT TOP,TERMINATING AT NEAREST STRUCTURAL MEMBER, SECURE CONDUITAT BOTH ENDS. THIS MUST BE SEPARATE FROM ANY HIGH VOLTAGECONDUIT.7563PROVIDE AN OUTLET FOR LIGHTED CANOPY SIGN ON TOP OF CASE,WIRE TO CASE LIGHT CIRCUIT FOR CONTROL. COORDINATE FINALLOCATION WITH GOI PROJECT MANAGER PRIOR TO ROUGH-INPROVIDE A J-BOX FOR CONNECTION OF DRAIN LINE HEATER.PROVIDE A J-BOX FOR CONNECTION OF REFRIGERATION BOX DOORSLIGHTS. LIGHTS PROVIDED BY DOOR MANUFACTURER. REFER TOREFRIGERATION DRAWINGS FOR MORE INFORMATION.PROVIDE A J-BOX FOR CONNECTION OF FREEZER/COOLER DOORHEATER. REFER TO REFRIGERATION DRAWINGS FOR MOREINFORMATION. PROVIDE ALL CONNECTIONS AS REQUIRED.EVAC PANEL POWER. REFER TO DRAWING E-3.0 FOR POWERAND DRAWING R-9 DETAIL #4 FOR CONTROLS.2021291"C FROM EMS CONTROL PANEL TO DATA RACK.120V DEDICATED OUTLET FOR UPS SERVING THE EMS TOUCHSCREEN. REFER TO REFRIGERATION DRAWINGS FOR ADDITIONALREQUIREMENTS.222324252627EMS (TOUCH SCREEN).FIELD VERIFY LOCATION WITH CUSTOMER.ALARM LIGHT AND HORN.FIELD VERIFY LOCATION WITH CUSTOMER.PROVIDE A CAT5 CABLE FROM EMS TOUCH SCREEN TONETWORK BACKBOARD.PROVIDE 5C-18 AWG. CABLE IN CONDUIT FROM REFRIGERATIONPANEL (ALARM LIGHT AND HORN) TO COMPRESSOR RACK PANEL.EMS SECURITY PANELTO BE WIRED BY E.C.E.C. TO COORDINATE WORK WITH REFRIGERATION CONTRACTORWHILE INSTALLING NEW ELECTRICAL EQUIPMENT PRIOR TOCONSTRUCTION TO AVOID CONDUIT / REFRIGERATION LINE CONFLICT.KEEP REQUIRED CLEARANCE.28NOT USED.STORE POWER MONITORING METER SUPPLIED, INSTALLED ANDWIRED TO 3 POWER IN RACK BY R.C. E.C. TO RUN CT CLAMPS(SUPPLIED BY R.C.) TO MAIN STORE DISTRIBUTION POWER. SEEDETAIL ON REFRIGERATION DRAWINGS. PROVIDE 2C-18 AWG.SHIELDED CABLE TO E2 CONTROLLER IN RACK PANEL, BY R.C. FIELDVERIFY REQUIREMENTS AND LOCATION.3031MRLDS, PRE-MOUNTED ON RACK. FIELD VERIFY LOCATION.PROVIDE A J-BOX FOR DEDICATED RACK UPS BACKUP POWER. VERIFYEXACT LOCATION AND COORDINATE WORK WITH R.C., REFER TOREFRIGERATION DRAWINGS FOR MORE INFORMATION.321/2"C FROM THE COMPRESSOR CONTROL CABINET STUBBED WITHIN2" OF CEILING, TO STRUCTURE ABOVE WITH A 90 DEGREE SWEEP ATTOP, TERMINATING AT NEAREST STRUCTURAL MEMBER. SECURECONDUIT AT BOTH ENDS. THIS MUST BE SEPARATE FROM ANY HIGHVOLTAGE CONDUIT.33E.C. TO RUN THREE (3) POWER WIRES, TWO (2) CONTROL WIRES ANDTWO (2) DISC. AUX WIRES FROM COMPRESSOR RACK POWER PANELUP TO CONDENSER PANEL ON ROOF IN SEPARATE CONDUITS.34PROVIDE 2C-18 AWG TO BOARD IN RACK PANEL FOR REFRIGERANTLEAK ALARM (BLUE). REFER TO REFRIGERATION DRAWINGS FORMORE INFORMATION.35PROVIDE 2C-18 AWG TO BOARD IN RACK PANEL FOR DOOR OPENALARM (AMBER). REFER TO REFRIGERATION DRAWINGS FOR MOREINFORMATION.36PROVIDE 2C-18 AWG SHIELDED CABLE IN CONDUIT TO AIR HANDLERCONTROL PANEL BY E.C. (SEE SHEET R3)2C-18 AWG SHIELDED CABLE IN CONDUIT TO RACK BY E.C.(SEE SHEET R3)SYMBOL LEGEND- CONTROL WIRES REQUIRED TO THIS LOCATION, PROVIDED AND INSTALLED BY E.C. (SEE ELECTRICAL REQUIREMENTS SCHEDULE SHEET)- LOW VOLTAGE CONTROL WIRES REQUIRED TO THIS LOCATION, PROVIDDED AND INSTALLED BY E.C.(SEE ELECTRICAL REQUIREMENTS SCHEDULE SHEET)- ELECTRICAL CONDUIT STUB-UP LOCATION, PROVIDED, INSTALLED AND WIRED BY E.C.- PHOTOCELL ON THE ROOF (FACING NORTH) WITH 3C-18 AWG SHIELDED CABLE & CONDUIT TO RACK PANEL BY E.C..- FIXTURE TEMPERATURE SENSOR, RUN ENERGY MANAGEMENT CABLE IN SEPARATE CONDUIT (FORLOW VOLTAGE TEMPERATURE SENSOR) FROM EACH SENSOR TO RACK PANEL, PROVIDED,INSTALLED BY E.C. CABLE TYPE 2C-18 AWG SHIELDED CABLE. SEE INSTALLATION DETAIL &COORDINATE W/R.C. FOR EXACT LOCATION.- OUTSIDE HUMIDITY SENSOR, 3C-18 AWG SHIELDED CABLE TO CONDENSER PANELBY E.C.- INDOOR PHOTOCELL, MOUNTED BY R.C., SUPPORT ROD BY G.C., WIRED BY E.C.1/8"=1'-0"REFRIGERATION POWER PLAN11/8"=1'-0"ROOF REFRIGERATION POWER PLAN24275 N Palm St, Suite 100
Fullerton, CA 92835
(714) 578-2300 office
www.coolsysenergydesign.com
BBCCDDFFGGAA112233445566EEGFI,WPP1-42P2-(11,13)P2-(12,14)91130NF30NFP2-(15,17)130NFGFI,WPP1-429GFI,WPP1-44GFI,WPP1-4299GFI,WPP1-4460NF10MDP-3MDP-13100NFMDP-14100NFMDP-11100NF100NF9MDP-1211P2-(37,39,41)WPWPWPWPWPWPWPWPWPGENERAL NOTES1. INSTALLATION OF CONDUITS AND WIRES SHALL BE CONCEALED ABOVE THE CEILING AND BEHIND WALLS. WHERE NOT POSSIBLE, CONTRACTOR SHALLOBTAIN APPROVAL FOR EXPOSED LOCATIONS PRIOR TO ROUGH IN. USE WIREMOLD IN EXPOSED AREAS.2. REFER TO T24 VOLTAGE DROP TABLE TO DETERMINE POWER CONDUIT AND WIRE SIZE FOR 20A, 120/208V CIRCUITS, BASED ON THE EXACT LOAD ANDDISTANCE FROM THE ELECTRICAL PANEL.3. ALL EXIT AND EMERGENCY LIGHTS TO BE CONNECTED AHEAD OF ALL LIGHT SWITCHES AND CONTROLS.4. REFER TO ARCHITECTURAL DRAWINGS FOR MOUNTING HEIGHT AND EXACT LOCATION OF LIGHT FIXTURES.5. E.C. SHALL REFER TO REFRIGERATION DRAWINGS FOR LIGHTING AND EMS CONTROL INFORMATION AND REQUIREMENTS.6. COORDINATE ALL LIGHTING WORK WITH MECHANICAL AND FIRE SPRINKLER WORK.7. PROVIDE APPROVED HANDLE TIE FOR ALL MULTIWIRE BRANCH CIRCUITS AS REQUIRED PER NEC ART. 210.4(B).8. THE BOTTOM OF THE RECEPTACLE OUTLET BOXES SHALL NOT BE LESS THAN FIFTEEN INCHES ABOVE FINISHED FLOOR AND THE TOP OF THE OUTLETBOXES FOR CONTROLS AND SWITCHES SHALL NOT BE MORE THAN FORTY-EIGHT INCHES ABOVE THE FINISHED FLOOR.9. E.C. SHALL PROVIDE ADDITIONAL EMERGENCY EGRESS LIGHTING AND EXIT SIGNAGE PER FIRE INSPECTOR REQUIREMENTS.10. EXIT SIGNS SHALL BE INTERNALLY OR EXTERNALLY ILLUMINATED AT ALL TIMES. EXTERNALLY ILLUMINATED EXIT SIGNS SHALL BE CONNECTED TO ANEMERGENCY POWER SYSTEM (BATTERIES, UNIT EQUIPMENT OR AN ON-SITE GENERATOR) THAT WILL ILLUMINATE THE EXIT SIGNS FOR A DURATION OFNOT LESS THAN 90 MIN IN CASE OF PRIMARY POWER LOSS (C.B.C. 1011).CODED NOTES1920A, 120V GFCI RECEPTACLE IN WEATHERPROOF ENCLOSURE AND IDENTIFIED AS "HEAVY-DUTY", PER NEC 406.9(A)(1).456732E.C. TO PROVIDE CONDENSING UNIT MOUNTED NON-FUSED DISCONNECT SWITCH.CONDENSING UNIT LOCATED ON THE ROOF. VERIFY LOCATION.NOT USED.ELECTRICAL CONTRACTOR SHALL FULLY REVIEW REFRIGERATION AND H.V.A.CDRAWINGS AND SHALL INCLUDE IN BID ALL WORK THAT IS TO BE COMPLETED BYELECTRICAL CONTRACTOR, INCLUDING ALL SWITCHES, CONDUITS, BELDENCABLES, CONTROL WIRES, POWER WIRES ETC, AS CALLED OUT ON REFRIGERATIONDRAWINGS FOR A COMPLETE AND OPERABLE REFRIGERATION SYSTEM.NO CHANGE ORDER SHALL BE ALLOWED.810NOT USED.NOT USED.NOT USED.NOT USED.NOT USED.NOT USED.REFER TO DRAWING M-1 AND M-3 FOR POWER REQUIREMENTS FOR DAMPER ACTUATORS FOR DOAS-111DISCONNECT SWITCH FOR CONNECTION OF AIR HANDLING UNIT WITH INTERNAL FUSE, POWERED BY DISTRIBUTIONPANEL. PROVIDE ALL WORK AS NECESSARY FOR A COMPLETE AND OPERABLE SYSTEM, CONTROLLED BY C.P.C.SYSTEM. VERIFY LOCATION. E.C. TO PROVIDE 2C-18 AWG. SHIELDED CABLE IN CONDUIT TO COMPRESSOR PANEL.REFER TO SINGLE LINE DIAGRAM ON SHEET E0.3 FOR WIRING INFO.1/8"=1'-0"ELECTRICAL ROOF POWER PLAN14275 N Palm St, Suite 100
Fullerton, CA 92835
(714) 578-2300 office
www.coolsysenergydesign.com
LOCAL SWITCH(WHEN USED)NORMAL OUTPUTOFFICES / LOUNGE / RESTROOMSLTGLOADNHLighting_panelVIOLET (0-10VDC+)GRAY (0-10VDC-)BLUE (LOAD)WHITE (NEUT)BLK(120)/ORG(277)BLUE (LINE)J-BOX / FIXT. HOUSINGON/OFFNHEQUIPMENT ROOMLTGLOADLighting_panelBLUE (LOAD)WHITE (NEUT)BLK(120)/ORG(277)BLUE (LINE)J-BOX / FIXT. HOUSINGON/OFFNHLTGLOADLighting_panelVIOLET (0-10VDC+)GRAY (0-10VDC-)BLUE (LOAD)WHITE (NEUT)BLK(120)/ORG(277)BLUE (LINE)J-BOX / FIXT. HOUSINGON/OFFHEXIT CORRIDORLTGLOADLighting_panelVIOLET (0-10VDC+)GRAY (0-10VDC-)BLACK (LOAD)BLACK (120/277)NHLIGHTINGCONTACTORLTGLOADLighting_panelVIOLET (0-10VDC+)GRAY (0-10VDC-)BLUE (LOAD)WHITE (NEUT)BLK(120)/ORG(277)BLUE (LINE)J-BOX / FIXT. HOUSING120V CKTSEE LIGHTING PLAN FORCIRCUIT USED FOR EACHROWNEUTRALGROUNDSWITCHEDUNSWITCHEDEMERGENCYINVERTERSWITCHED EM OUTPUTEMFIXTURENEUTRALNON-EMFIXTUREnWSX LV PDT DXIN-WALL DIGITAL SWITCH/SENSORPIR1-CHANNEL ON/OFF + RAISE/LOWERINTEGRAL PHOTOCELLLOW VOLTAGEnPP16 DCONTROL PACK16A RELAY0-10V DIMMING SINKCHASE NIPPLE MOUNT120/277VACnPP16 PL T24CONTROL PACK16A RELAYCHASE NIPPLE MOUNT120/277VACnWSX LV PDT DXIN-WALL DIGITAL SWITCH/SENSORPIR1-CHANNEL ON/OFF + RAISE/LOWERINTEGRAL PHOTOCELLLOW VOLTAGEnPP16 DCONTROL PACK16A RELAY0-10V DIMMING SINKCHASE NIPPLE MOUNT120/277VACnCM PDT 9OCCUPANCY SENSOR500SQFT 360° PIR0-10V DIMMINGCEILING MOUNT5A RELAY 120/277VACnWSX LV PDT DXIN-WALL DIGITAL SWITCH/SENSORPIR1-CHANNEL ON/OFF + RAISE/LOWERINTEGRAL PHOTOCELLLOW VOLTAGEnPP16 DCONTROL PACK16A RELAY0-10V DIMMING SINKCHASE NIPPLE MOUNT120/277VACUNSWITCHED120V CKTNEUTRALCPC DIMMINGMODULECONNECTION LINETYPE LEGENDCLASS II LOW VOLTAGE CAT5e CABLECLASS II LOW VOLTAGEOVERRIDING DIMMING RELAY(EMERGENCY MODE ACTIVATION)18 AWG/2C (TYP.)TYPICAL STAND ALONE LIGHTING DETAIL FOR ROOMSSCALENTS1DIMMING MODULE CONTROL ZONESSCALENTS2LIGHTING CONTACTOR WIRING DIAGRAMSCALENTS3CONTROLLED OUTLET TO BELEVITON 5362-S2B COLOR BLUENON-CONTROLLED IG OUTLETTO BE LEVITON 5462-IG COLORORANGEPROVIDE CONTROLLEDRECEPTACLE STICKER ONCIRCUIT THAT ARE RUNTHRU OCCUPANCY SENSOR1.IN OFFICES AND AREA ALL GENERAL OUTLETS ARE TO BE DUPLEX TYPE WHERE ONE OUTLET IS CONTROLLED BY OCCUPANCY SENSOR2.IN OFFICE AREA IG QUADS FOR COMPUTERS SHALL HAVE THE COMPUTER PLUGGED INTO THE NON-CONTROLLED RECEPTACLE AND THE MONITOR CAN BE PLUGGED INTO THE CONTROLLED.3.NO COPY MACHINES OR PRINTERS SHALL BE PLUGGED INTO THE CONTROLLED OUTLETS.4.THE CONTROL POWER OUTLETS CAN HAVE ITEMS SUCH AS TASK LIGHTING, FANS, HEATERS, PENCIL SHARPENERS ETC PLUGGED INTO THE CONTROLLED OUTLETS,LED DIMMING FIXTURELED DIMMING FIXTURELVLOW VOLTAGEOCCUPANCYSENSORDIMMING SWITCHW/MANUAL OVERRRIDEPOWERPACKLVLVZONE RELAYBASE MANUFACTURERS FOR LIGHTING CONTOL ARELISTED BELOWCONTRACTOR SHALL SUBMIT SYSTEM FOR REVIEW.1.LEVITON2.ACRUITY3.WATT STOPPERSIGNAL FROM WALLSWITCH, EMS, OROCCUPANCY SENSOR1.OFFICES ARE TO BE CAPABLE OF AUTOMATIC OFF/ON VIAOCCUPANCY SENSOR CEILING MOUNTED WITH MANUAL OVERRIDEWALL SWITCH.2.WALL SWITCH SHALL BE CAPABLE OF DIMMING LIGHT FIXTURES3.ALL LED DIMMABLE LIGHT FIXTURES SHALL BE CAPABLE OF DEMANDDIMMNG FROM DIMMING MODULE VIA EMS4.CONTROLLED RECEPTACLES SHALL BE CONTROLLED BYOCCUPANCY SENSOR.OCCUPANCYCONTROLLEDRECEPTACLELV CONTROLLED RECEPTACLESTYPICAL OFFICE LIGHTING CONTROL TYPICAL CONTROL RECEPTACLES WITH LIGHT SWITCHSCALENTS44275 N Palm St, Suite 100
Fullerton, CA 92835
(714) 578-2300 office
www.coolsysenergydesign.com
1/8"=1'-0"PANEL SCHEDULES1SHEET NOTES:1. ALL ELECTRICAL EQUIPMENTS AND FEEDERS ARE NEW UNLESS OTHERWISE NOTED. TORQUEALL TERMINATIONS PER MANUFACTURER RECOMMENDATION.ALL EQUIPMENT SHOWN IS THAT OF EATON BRAND, OTHER MANUFACTURER IS ACCEPTABLE -SUBJECT TO ENGINEER'S APPROVAL.2. CONTRACTOR TO COORDINATE THE AVAILABLE SHORT CIRCUIT CURRENT WITH THE UTILITYCOMPANY AND MAKE ADJUSTMENTS AS REQUIRED. MAIN SWITCHBOARD SHALL BE FULLY RATED.3. ALL GROUNDING ELECTRODES AS DESCRIBED IN NEC 250.52 THAT ARE PRESENT AT THEBUILDING OR STRUCTURE SERVED SHALL BE BONDED TOGETHER TO FORM THE GROUNDINGELECTRODE SYSTEM. PROVIDE BONDING TO THE UNDERGROUND METAL WATER PIPE, ALLMETAL PIPING SYSTEM AND STRUCTURAL METAL (IF AVAILABLE) TO THE GROUNDINGELECTRODE SYSTEM USING #3/0 CU.4. THE CALCULATED AVAILABLE FAULT CURRENT THAT COULD BE PROVIDED TO THE SERVICEEQUIPMENT SHALL BE FIELD MARKED AS REQUIRED BY NEC 110.24(A). INCLUDE THE DATE THEFAULT CURRENT CALCULATION WAS PERFORMED, AND THE MAXIMUM AVAILABLE FAULTCURRENT.5. PER NEC 230-95(c) WHERE A SERVICE DISCONNECT IS 1000 AMPS OR MORE, A PERFORMANCETEST OF THE GROUND-FAULT PROTECTION SYSTEM IS TO BE CONDUCTED.6. ALL WIRE IS COPPER.7. ALL EQUIPMENT IS NEW, UNLESS OTHERWISE NOTED AS EXISTING, "(E)".8. ALL DEVICES ARE 3 POLE UNLESS OTHERWISE NOTED.9. ONLY U.L. LISTED EQUIPMENT SHALL BE USED.10. RATING OF ALL OVERCURRENT PROTECTION DEVICES, SWITCHES AND MAGNETIC STARTERS TOBE VERIFIED WITH NAMEPLATE RATING OF ASSOCIATED UNIT AND TO BE REVISED ASREQUIRED.11. NEW PANELBOARD BREAKERS AIC RATINGS SHALL MATCH EXISTING BREAKER'S RATINGS.12. PROVIDE NEW DEADFRONT COVERS AT DISTRIBUTION SECTION AS NECESSARY.13. ALL ELECTRICAL EQUIPMENT SHALL BE TOP-EXIT. PROVIDE TOP-EXIT WIREWAYS WHEREREQUIRED. NO UNDERSLAB CONDUIT ALLOWED.VERIFY ALL UTILITY REQUIREMENTS PRIORTO BID AND COORDINATE ALL WORK PRIORTO CONSTRUCTION WITH UTILITY PLANNER.NOTE #1 & 2 (TYPICALFOR ALL FEEDERS.)2321231GROUNDING DETAILNTS14. ALL INTERIOR POWER WIRE,LUGS AND TERMINATIONS ARE TO BE 75 DEGREES RATED100A100A100A225A100A225A400A200A100A1200AMAINSERVICE ELEVATION1200A @208Y/120V100ASPDNEW 1200A MAIN DISTRIBUTION PANEL MDP:1200A MCB IS EXISTING TO REMAIN ON INTERIOR120/208V 3PH, 4W+GNEMA 1 ENCLOSURE, 22 KAIC225A100A225A60ADOASON ROOFPANEL'P2'LIGHTINGCONTROLDIMMINGPANELPANEL'RP'ELECTRICAL ROOMUTILITY FEEDERSEXISTING TO REMAINNEW FEEDERS3 SETS OF 3#600KCMIL IN (3)4" CONDUITFROM SERVICE CABINET AT REAR OFBUILDING TO EXISTING 1200A SWITCHGEAR.EXITING SWITCHGEAR IS RATED AT 22,000AICTHE NEW SWITCH GEAR WILL BE RATEDSAME AS PREVIOUSLY RATED FOR THISSPACE. E.C. SHALL COORDINATE ALLEFFORTS WITH UTILITY COMPANY.INTERIOR WALLREF.SYSTEMS3#350Kcmil+1#4G IN 3"30ASEE GROUNDDETAILEM20AVD - 20' -.4VOLTS - 0.3%PANEL'LP'30A60ABALERFORKLFTCHARGERREFRIGRACK300A3#6 + 1#8G IN 1"CVD - 103' -4.5 VOLTS - 2.2%3#6 + 1#8G IN 1"CVD - 40' -1.1 VOLTS - 0.5%3#10+ 1#8G IN 3/4"CVD - 45' -.2.4 VOLTS - 1.2%ROOF TOPCONDENSERMNEW 1200A MAIN SWITCH LOCATED INELECTRICAL AREA NEMA 1 ENCLOSUREEXTERIOR NEMA 3R CABINETTO REMAINCONNECTION TOCONDENSER BY E.C.3#8+ 1#8G IN 1"CVD - 30' -.6VOLTS - 0.3%EXISTING EXTERIORSERVICE SWITCHES INNEMA 3R CABINETPANEL'P1'NEWPANEL'P1'NEW4#3/0 + 1#6G IN 2"CVD - 10' -.2 VOLTS - 0.1%ISOLATED GROUND BUSS CONNECTDIRECT TO MAIN GROUND BUSFOR REGISTERS, OFFICES ANDSERVER POWER CIRCUITSNEWNEWNEW4#2 + 1#8G IN 1-1/4"CVD - 15' -.4 VOLTS - 0.2%4#4/0 + 1#4G IN 2-1/2"CVD - 25' -.4 VOLTS - 0.2%4#2 + 1#8G IN 1-1/4"CVD - 30' -.7 VOLTS - 0.3%4#4/0 + 1#4G IN 2-1/2"CVD - 10' -.2 VOLTS - 0.1%70A70A80A80AVRFCU-1 AVRFCU-1 BVRFCU-2 AVRFCU-2 B3#4+1#8G IN 1"CVD - 156' -5.1VOLTS - 2.4%3#4+1#8G IN 1"CVD - 156' -5.1VOLTS - 2.4%3#3+1#8G IN 1"CVD - 188' -6.1VOLTS - 2.9%3#3+1#8G IN 1"CVD - 188' -6.1VOLTS - 2.9%100A100A100A100A100A4275 N Palm St, Suite 100
Fullerton, CA 92835
(714) 578-2300 office
www.coolsysenergydesign.com
PART 1 - GENERALPART 2 - PRODUCTS1.01 SCOPE OF WORKA. FURNISH AND INSTALL ALL MATERIALS AND EQUIPMENT AND PROVIDE ALL LABOR, TOOLS, TRANSPORTATION, SUPERINTENDENCE AND SERVICESREQUIRED AND NECESSARY TO COMPLETE THE WORK SHOWN ON THE DRAWINGS AND/OR SPECIFIED HEREIN. ALSO INCLUDE ALL OTHER WORK ANDMISCELLANEOUS ITEMS, NOT SPECIFICALLY MENTIONED, BUT REASONABLY INFERRED FOR A COMPLETE INSTALLATION INCLUDING ALL ACCESSORIESAND APPURTENANCES REQUIRED FOR TESTING THE SYSTEM. IT IS THE INTENT OF THE DRAWINGS AND SPECIFICATIONS THAT ALL SYSTEMS BECOMPLETE, AND READY FOR OPERATION.1.02 REGULATORY REQUIREMENTA. CODE COMPLIANCE IS MANDATORY. NOTHING IN THESE DRAWINGS AND SPECIFICATIONS PERMITS WORK NOT CONFORMING TO THESE CODES.WHERE WORK IS SHOWN TO EXCEED MINIMUM CODE REQUIREMENTS, COMPLY WITH DRAWINGS AND SPECIFICATIONS. ALL WORK AND MATERIALSSHALL COMPLY WITH THE LATEST RULES, CODES AND REGULATIONS, INCLUDING, BUT NOT LIMITED TO THE FOLLOWING:1. OCCUPATIONAL SAFETY AND HEALTH ACT STANDARDS (OSHA).2. NFPA #70: NATIONAL ELECTRIC CODE (NEC).3. NFPA #101: LIFE SAFETY CODE.4. STATE FIRE MARSHAL5. LOCAL UTILITY COMPANIES6. LANDLORD REQUIREMENTS1.03 LICENSE, FEES, AND PERMITSA. ELECTRICAL CONTRACTOR SHALL PAY FOR ALL LICENSES, PERMITS AND INSPECTION FEES REQUIRED BY THE AUTHORITY HAVING JURISDICTION ANDSHALL ARRANGE FOR ALL REQUIRED INSPECTIONS.1.04 SAFETY AND INDEMNITYA. THE CONTRACTOR SHALL BE SOLELY AND COMPLETELY RESPONSIBLE FOR CONDITIONS OF THE JOB SITE, INCLUDING SAFETY OF ALL PERSONS ANDPROPERTY DURING PERFORMANCE OF WORK. THIS REQUIREMENT WILL APPLY CONTINUOUSLY AND NOT BE LIMITED TO NORMAL WORKING HOURS.NO ACT, SERVICE, DRAWING REVIEW OR CONSTRUCTION REVIEW BY THE OWNER, THE ENGINEERS OR THEIR CONSULTANTS, IS INTENDED TO INCLUDEREVIEW OF THE ADEQUACY OF THE CONTRACTOR'S SAFETY MEASURES, IN, ON, OR NEAR THE CONSTRUCTION SITE.1.05 DRAWINGS AND SPECIFICATIONSA. ALL DRAWINGS AND ALL DIVISIONS OF THESE SPECIFICATIONS SHALL BE CONSIDERED AS A WHOLE AND WORK OF THIS DIVISION SHOWN ANYWHERETHEREIN SHALL BE FURNISHED UNDER THIS DIVISION. DRAWINGS ARE DIAGRAMMATIC AND INDICATE THE GENERAL ARRANGEMENT OF EQUIPMENT ANDWIRING. MOST DIRECT ROUTING OF CONDUITS AND WIRING IS NOT ASSURED. EXACT REQUIREMENTS SHALL BE GOVERNED BY CONDITIONS OF THEJOB. CONSULT ALL OTHER DRAWINGS IN PREPARATION OF THE BID. EXTRA LENGTHS OF WIRING OR ADDITION OF PULL OR JUNCTION BOXES, ETC.,NECESSITATE BY SUCH CONDITIONS SHALL BE INCLUDED IN THE BID.1.06 CONDITIONS AT SITEA. VISIT SITE OF THE WORK, COMPARE IT WITH THE DRAWINGS AND SPECIFICATIONS AS TO THE CONDITIONS UNDER WHICH WORK IS TO BE PERFORMED,ASCERTAIN AND CHECK ALL CONDITIONS AND ELEVATIONS AND TAKE ALL MEASUREMENTS WHICH MAY AFFECT THE WORK. NO ALLOWANCE SHALLSUBSEQUENTLY BE MADE FOR ANY EXTRA EXPENSE OR CLAIMS DUE TO FAILURE OR NEGLECT UNDER THIS REQUIREMENT TO MAKE SUCHEXAMINATION, INCLUDING EXAMINATION OF RESTRICTED WORKING CONDITIONS OR SUCH OTHER DIFFICULTIES VISUALLY OBSERVED DURING SITEVISIT. CONTRACTOR IS RESPONSIBLE FOR BECOMING COMPLETELY FAMILIAR WITH THE ARCHITECTURAL AND STRUCTURAL CONDITIONS ANDLIMITATIONS WHICH WILL EXIST IN THE BUILDING AND TO PROVIDE ALL LABOR, TOOLS AND MATERIALS REQUIRED TO PRODUCE A COMPLETELYCONCEALED INSTALLATION AS INDICATED ON THE PLANS, SPECIFICATIONS, AND REQUIRED BY THE CODE.1.07 WORKMANSHIP AND CONTRACTOR'S QUALIFICATIONSA. ONLY QUALITY WORKMANSHIP WILL BE ACCEPTED. HAPHAZARD OR POOR INSTALLATION WILL BE CAUSE FOR REJECTION OF WORK.1.08 SUBMITTALSA. SUBMITTALS, UNLESS OTHERWISE NOTED, SHALL BE A SINGLE PACKAGE OF SIX (6) COPIES SUBMITTED TO OWNER FOR REVIEW. WORK SHALL NOTCOMMENCE UNLESS SUBMITTALS HAVE BEEN APPROVED.B. SUBMIT CUTSHEETS, MATERIAL DATA, AND SHOP DRAWINGS, AS NOTED BELOW. FOR REVIEW WITHIN FIFTEEN (15) DAYS AFTER AWARD OF CONTRACT.SUBMITTALS REQUIRED AS FOLLOWS:1. BASIC ELECTRICAL MATERIALS INCLUDING BUT IS NOT LIMITED TO:A.) WIRING DEVICES - RECEPTACLES, SWITCHES, FACEPLATESB.) WIRES, CONNECTORS, TAPES, SPLICES, TERMINATIONS, AND ACCESSORIESC.) RACEWAYS AND ACCESSORIESD.) DEVICE IDENTIFICATION2. ELECTRICAL EQUIPMENTA.) POWER DISTRIBUTION EQUIPMENT - PANELBOARDS, SWITCHBOARDS, SWITCHGEAR, DISCONNECT SWITCHES, CIRCUIT BREAKERS,TRANSFORMERS, GENERATORS, INVERTERS, UPS, POWER DISTRIBUTION UNITS, ETC. B.) SERVICE ENTRANCE EQUIPMENT - BUS DUCT,TERMINATION CANS, METERED SWITCHBOARDS, ETC.3. LIGHTINGA.) LIGHT FIXTURES AND SUPPORT DEVICESB.) LAMPS AND BALLASTS - INCLUDE BALLASTS CERTIFICATION. BALLAST SHALL HAVE LOCAL DISCONNECTS.C.) POLESD.) CONTROLS - OCCUPANCY SENSORS, PHOTOCELL, LIGHTING CONTACTORS, LIGHTING CONTROL PANELS, DIMMERS, ETC.E.) FIXTURE AND ASSEMBLY WATTAGESC. SUBMIT COMPLETE TEST REPORTS AND ANALYSIS FOR REVIEW WITHIN FIFTEEN (15) DAYS AFTER TESTING.D. SUBMIT VERIFIED PUNCHLIST TWO (2) WEEKS AFTER ISSUANCE DATE. INDICATE PUNCHLIST ITEMS THAT HAVE BEEN COMPLETED BY CONTRACTOR.INCLUDE DATE FOR REPUNCH.1.09 SUBSTITUTIONSA. ONE OR MORE MAKES OF MATERIALS OR METHODS MAY HAVE BEEN SPECIFIED TO ESTABLISH THE STANDARD OF QUALITY, WORKMANSHIP, FINISH,AND DESIGN REQUIRED, BUT OTHER MATERIALS OR METHODS EQUAL OR BETTER IN QUALITY, WORKMANSHIP, FINISH, DESIGN, AND GUARANTEEDPERFORMANCE, MAY BE SUBMITTED FOR REVIEW AND APPROVAL AS SUBSTITUTION. ALL SUBSTITUTIONS ARE SUBJECT TO REVIEW AND APPROVAL BYARCHITECT, ENGINEER, AND OWNER.B. SUBSTITUTIONS SHALL BE REQUESTED IN A WRITTEN FORM AND SHALL BE ACCOMPANIED WITH A SIGNED STATEMENT THAT PROPOSED SUBSTITUTIONIS EQUAL, OR BETTER THAN SPECIFIED. ADDITIONAL DOCUMENTATION TO SUBSTANTIATED PROPOSED SUBSTITUTION MAY BE REQUIRED BY OWNER,ARCHITECT, AND ENGINEER. CONTRACTOR SHALL SUBMIT AS DIRECTED.C. CONTRACTOR SHALL ACCOMPANY REQUEST FOR SUBSTITUTION LETTER WITH A COMPLETED CSI SUBSTITUTION FORM INCLUDE THE COMPARISON FORFOLLOWING:1. ELECTRICAL RATING2. FINISHES3. SPARE PARTS4. PERFORMANCE DATA5. COSTS AND SCHEDULED. A WRITTEN SIGNED STATEMENT FROM THE GENERAL CONTRACTOR SHALL ACCOMPANY SUBSTITUTION REQUEST FORM ASSURING THAT:1. HE HAS VERIFIED DIMENSIONS WITH PROJECT CONDITIONS AND HAS COORDINATED WITH OTHER TRADES. SUBSTITUTION DOES NOT AFFECTDIMENSIONS SHOWN ON DRAWINGS.2. HE SHALL PAY AND BURDEN THE COSTS FOR CHANGES TO THE PROJECT INCLUDING RE-DESIGN, RE-ENGINEERING AND REVIEW OF SUBSTITUTION.ONLY ONE (1) ENGINEERING REVIEW TIME IS ALLOWED FOR EACH PRODUCT SUBSTITUTION. CONTRACTOR SHALL BE RESPONSIBLE FOR ADDITIONALREVIEW TIME AND SHALL PAY ARCHITECT AND ENGINEER'S TIME AT THEIR PROFESSIONAL RATE SCHEDULE.3. HE HAS CONFIRMED THAT THE PROPOSED SUBSTITUTION WILL HAVE NO ADVERSE AFFECT ON OTHER TRADES, THE CONSTRUCTION SCHEDULE, ORSPECIFIED WARRANTY REQUIREMENTS.4. HE HAS CONFIRMED THAT MAINTENANCE AND SERVICE PARTS WILL BE LOCALLY AVAILABLE FOR THE PROPOSED SUBSTITUTION.E. COST SAVINGS RESULTING FROM SUBSTITUTION SHALL BE RETURNED TO THE CONTRACT OR THE OWNER IF THE SUBSTITUTION IS PERMITTED.F. NO WORK INVOLVING MATERIALS SUBMITTED FOR SUBSTITUTION SHALL PROCEED UNTIL WRITTEN ACCEPTANCE IS RECEIVED FROM THE OWNER. THEOWNER IS THE FINAL JUDGE OF ACCEPTABILITY OF PREFERRED SUBSTITUTIONS.1.10 COORDINATIONA. COORDINATE WORK WITH OTHER TRADES TO AVOID CONFLICT AND TO PROVIDE CORRECT ROUGH-IN AND CONNECTION FOR EQUIPMENT FURNISHEDUNDER OTHER TRADES THAT REQUIRE ELECTRICAL CONNECTIONS. INFORM CONTRACTORS OF OTHER TRADES OF THE REQUIRED ACCESS TO ANDCLEARANCES AROUND ELECTRICAL EQUIPMENT TO MAINTAIN SERVICE ABILITY AND CODE COMPLIANCE.B. VERIFY EQUIPMENT DIMENSIONS AND REQUIREMENTS WITH PROVISIONS SPECIFIED UNDER THIS SECTION. CHECK ACTUAL JOB CONDITIONS BEFOREFABRICATING WORK. REPORT NECESSARY CHANGES IN TIME TO PREVENT NEEDLESS WORK. CHANGES OR ADDITIONS, SUBJECT TO ADDITIONALCOMPENSATION, WHICH ARE MADE WITHOUT WRITTEN AUTHORIZATION AND AN AGREED PRICE, SHALL BE AT THE CONTRACTOR'S RISK AND EXPENSE.1.11 CUTTING AND PATCHINGA. ALL CUTTING AND PATCHING REQUIRED FOR WORK OF THIS DIVISION IS INCLUDED HEREIN. COORDINATION WITH GENERAL CONTRACTOR AND OTHERTRADES IS IMPERATIVE. CONTRACTOR SHALL BEAR THE RESPONSIBILITY FOR AND THE ADDED EXPENSE OF ADJUSTING FOR IMPROPER HOLES,SUPPORTS, ETC.1.12 ACCEPTANCE AND DEMONSTRATIONA. UPON COMPLETION OF THE WORK, AT A TIME TO BE DESIGNATED BY THE OWNER, THE CONTRACTOR SHALL DEMONSTRATE FOR THE OWNER THEOPERATION OF THE ELECTRICAL INSTALLATION, INCLUDING ANY AND ALL SPECIAL ITEMS INSTALLED BY HIM OR INSTALLED UNDER HIS SUPERVISION.B. PROPERLY SET LIGHTING CONTROL PANELS, AUTOMATIC TIME SWITCHES, ETC. TO PERFORM SWITCHING OPERATIONS IN ACCORDANCE WITHSCHEDULES PROVIDED BY THE OWNER'S REPRESENTATIVE, AND DEMONSTRATE (USING THE MANUFACTURER'S OPERATING INSTRUCTIONS) HOW TOOVERRIDE CONTROLS AND/OR TEST TIME SWITCHES PROGRAMMING.1.13 RECORD DRAWINGS AND EQUIPMENT DATAA. MAINTAIN ONE SET OF CLEAN WORKING DRAWINGS AT THE JOB SITE AND ENTER DAILY SUCH "AS-BUILT" INFORMATION AS FEEDER AND SERVICEROUTES, PULL BOX LOCATIONS AND CHANGES IN LAYOUT OR ARRANGEMENT WHICH OCCUR DURING CONSTRUCTION. DELIVER COMPLETED "RED LINEAS-BUILTS" DRAWINGS TO THE OWNER.B. SUBMIT TO THE OWNER'S REPRESENTATIVE A SET OF "AS BUILT" DRAWINGS IN VELLUM AND CAD FILE. AS BUILT COMMENTS SHALL BE WRITTEN IN ALEGIBLE MANNER IN THE SAME STYLE AS THE CONTRACT DOCUMENTS. ALSO SUBMIT THREE COPIES OF DATA SHEETS OR OTHER CURRENTMANUFACTURERS' PUBLICATIONS FOR EACH ITEM OF ELECTRICAL EQUIPMENT FURNISHED FOR THE PROJECT INCLUDING AT LEAST THESE DATA:1. TECHNICAL DESCRIPTION AND REPLACEABLE PARTS LIST.2. PHYSICAL DESCRIPTION AND INSTALLATION INSTRUCTIONS.3. USER'S MANUAL AND OPERATING INSTRUCTIONS.4. MANUFACTURER'S WARRANTY.1.14 CLEAN-UPA. RID THE PREMISES OF SCRAP MATERIALS, TRASH AND DEBRIS BOTH DURING CONSTRUCTION AND AT COMPLETION OF THE PROJECT. LEAVE THEBUILDING AND SURROUNDING AREA IN A CLEAN AND ORDERLY CONDITION.1.15 GUARANTEEA. GUARANTEE THE INSTALLATION FREE FROM DEFECTS OF WORKMANSHIP AND MATERIALS FOR A PERIOD OF ONE YEAR AFTER DATE OF CERTIFICATIONOF FINAL PAYMENT AND PROMPTLY REMEDY ANY DEFECTS DEVELOPING DURING THIS PERIOD, WITHOUT CHARGE.1.16 TEMPORARY SERVICESA. PROVIDE ADEQUATE AND SAFE TEMPORARY ELECTRICAL POWER AND LIGHTING THROUGHOUT THE CONSTRUCTION AND FINISHING OF THE PREMISES.IN ADDITION TO SPECIAL OR UNUSUAL REQUIREMENTS, PROVIDE AT LEAST THESE ITEMS:1. THREE (3) 20-AMP CIRCUITS FOR CONSTRUCTION POWER TOOLS. PROVIDE GFI TEMPORARY CIRCUITS WITH COVERPLATES TO MEET OSHAREQUIREMENTS.2. THREE OR MORE LIGHT STRINGS SUSPENDED APPROXIMATELY ONE FOOT BELOW THE HEIGHT OF FINISH CEILING WITH LAMPS SPACED NOT MORETHAN TWELVE FEET ON CENTERS. STRINGS SHALL BE RUN THE LENGTH OF THE STORE SPACE PARALLEL TO THE DEMISING WALLS, WITH ONESTRING WITHIN EIGHT FEET OF EACH WALL AND ONE (OR MORE) INTERMEDIATE STRING(S) ARRANGED TO LIMIT THE SPACING BETWEEN ROWS TOSIXTEEN FEET OR LESS.3. FLOOD LIGHTING AND TASK LIGHTING FOR PAINTING AND OTHER FINISH WORK.B. WHERE SCOPE INCLUDES THE REMOVAL OF EXTERIOR LIGHTING, CONTRACTOR SHALL PROVIDE TEMPORARY EXTERIOR LIGHTING UNTIL THE NEWEXTERIOR LIGHTING HAS BEEN ACCEPTED BY THE OWNER. TEMPORARY EXTERIOR LIGHTING SHALL COMPLY WITH IESNA STANDARDS FOR SECURITYLIGHTING.C. WHERE SCOPE INCLUDES THE DISABLING OF A FIRE ALARM SYSTEM, CONTRACTOR SHALL PROVIDE A FIRE WATCH. FIRE WATCH SHALL COMPLY WITHNFPA AND LOCAL FIRE MARSHAL REQUIREMENTS.D. WHEN PERMANENT ELECTRICAL SERVICE IS OPERABLE, DISCONNECT AND REMOVE FROM THE PREMISES THE MATERIALS AND EQUIPMENT USED FORTEMPORARY POWER AND LIGHTING. RESTORE MODIFICATIONS AND REPAIR DAMAGE CAUSED BY THE INSTALLATION, USE OR REMOVAL OFTEMPORARY SERVICE PROVISIONS.2.01 MATERIAL APPROVALA. ALL MATERIALS MUST BE NEW AND BEAR UNDERWRITER'S LABORATORIES LABEL. MATERIALS THAT ARE NOT COVERED BY UL TESTING STANDARDSSHALL BE TESTED AND APPROVED BY AN INDEPENDENT TESTING LABORATORY OR A GOVERNMENTAL AGENCY. MATERIAL NOT IN ACCORDANCE WITHTHESE SPECIFICATIONS MAY BE REJECTED EITHER BEFORE OR AFTER INSTALLATION.B. FOR LEED QUALIFIED BUILDINGS, PRODUCTS SHALL BE MANUFACTURED WITHIN 100 MILES OF PROJECT SITE.2.02 BASIC ELECTRICAL MATERIALSA. CONDUITS AND RACEWAYS1. RIGID STEEL: HOT-DIPPED GALVANIZED.2. INTERMEDIATE METAL CONDUIT (IMC): HOT-DIPPED GALVANIZED.3. ELECTRICAL METALLIC TUBING (EMT): ELECTRO-GALVANIZED.4. RIGID NON METALLIC CONDUIT (PVC SCHEDULE 40)5. WIREWAY: CODE GAUGE STEEL, WITH KNOCKOUTS AND HINGED COVER, CORROSION RESISTANT GRAY BAKED ENAMEL FINISH.6. PROVIDE FITTINGS AND ACCESSORIES APPROVED FOR THE PURPOSE EQUAL IN ALL RESPECTS TO THE CONDUIT OR RACEWAY. EMTCONNECTORS AND COUPLINGS SHALL BE STEEL SETSCREW TYPE INDOORS AND STEEL COMPRESSION TYPE IN WET LOCATIONS AND OUTDOORS.B. WIRES AND CABLES1. FOR POWER AND LIGHTING SYSTEM 600V OR LESS:A.) CONDUCTOR: MINIMUM SIZE #12 AWG.i. #12 AND #10 AWG SOLID COPPERii. #8 AWG AND LARGER SHALL BE STRANDED COPPER. B.) INSULATION TYPE:i. #12 TO #1 AWG: THWN FOR WET OR UNDERGROUND AND THHN FOR DRY LOCATIONS.ii. #1/0 THROUGH #4/0 AWG: XHHW (55 MILS). iii.#250 MCM AND LARGER: XHHW (65 MILS). iv.GROUNDING WIRE: TW. v.) METAL CLAD (MC)CABLESi. CONDUCTORS ARE MADE FROM CLASS B COPPER. SIZES 14AWG, 12 AWG AND 10 AWG MAY BE EITHER SOLID OR STRANDED, 8AWG ANDLARGER ARE STRANDED. THE CONDUCTORS ARE CONSTRUCTED WITH THHN/THWN OR XHHW-2 INSULATION RATED FOR 90OC DRY OR WETAT 600 VOLTS MAX. A COPPER GROUNDING CONDUCTOR IS CABLED WITH THE PHASE CONDUCTORS. THE GROUND CONDUCTOR HAS AGREEN INSULATION. AN INTERLOCKED ALUMINUM ARMOR IS HELICALLY FORMED AROUND THE CONDUCTOR. ASSEMBLY AND IS 45% LIGHTERTHAN STEEL MC CABLE.2. FOR SIGNAL AND COMMUNICATIONS CIRCUIT:A.) SPECIAL CABLES SHALL BE AS SPECIFIED ON DRAWINGS.B.) CONDUCTORS FOR GENERAL USE SHALL BE STRANDED COPPER CONDUCTOR, #16 AWG MINIMUM, WITH THWN INSULATION FOR UNDERGROUNDOR WET LOCATIONS AND THHN INSULATION FOR DRY LOCATIONS.3. ACCEPTABLE PRODUCTS: GENERAL ELECTRIC, ANACONDA, OKONITE, PARANITE OR TRIANGLE PRODUCTS CONFORMING OR EXCEEDINGAPPLICABLE IPCEA STANDARDS.C. OUTLET BOXES, JUNCTION AND PULLBOXES1. OUTLET BOXES: 4" SQUARE X 1-1/2" DEEP (OR LARGER) GALVANIZED SHEET STEEL KO-TYPE WITH PLASTER RING AND COVER FOR GENERALINTERIOR USE AND CAST METAL TYPE FS OR FD WITH MATCHING SCREW COVERS FOR EXTERIOR AND EXPOSED INTERIOR LOCATIONS (GASKETEDIN DAMP OR WET LOCATIONS).2. JUNCTION BOXES (FLOOR BOX NOT INCLUDED) SHALL BE SAME AS OUTLET BOXES UP TO 42 CU. IN. AND CODE-GAUGE STEEL IN LARGER SIZES WITHSURFACE OR FLUSH-TYPE SCREW-MOUNTED TRIMCOVERS, BOTH BOXES AND COVERS INHIBITOR-PRIMED AND PAINTED INSIDE OUT.3. PULL BOXES SHALL BE SAME AS JUNCTION BOXES UNLESS INDICATED OTHERWISE ON THE DRAWINGS, WITH COVERS.4. TELEPHONE OUTLET BOXES SHALL BE THE TYPE AND SIZE REQUIRED BY THE SERVING TELEPHONE COMPANY BUT NOT SMALLER THAN 4-11/16"SQUARE X 2-1/8" DEEP WITH SINGLE-GANG RING AND SIERRA #S-754N SPLIT PLATE BUSHING.5. UNDERGROUND AND SITE JUNCTION BOXES, HANDHOLES, AND MANHOLESA.) SHALL BE MADE UP OF PRECAST CONCRETE WITH TRAFFIC RATED STEEL COVERS. EXTENSIONS SHALL BE PROVIDED AS NECESSARY TO MAINREQUIRED COVERAGE FOR DUCT BANKS. B.) PROVIDE 10" X 17' (MIN) FOR PULLBOXES, 36" X 60" (MIN) FOR HANDHOLES, AND 6'X8'X6' (MIN)MANHOLES.D. WIRING DEVICES AND PLATES1. WIRING DEVICES AND PLATES SHALL BE LISTED FOR SPECIFIC USE.2. ALL POWER RECEPTACLES AND SWITCHES FOR GENERAL PURPOSE CIRCUITS SHALL BE NEMA SPECIFICATION GRADE, RATED AS FOLLOWS:A.) GENERAL PURPOSE RECEPTACLES: NEMA 5-15R OR 5-20RB.) LAB BENCH RECEPTACLES: NEMA 5-20RC.) DEDICATED RECEPTACLES: NEMA 5-20R3. SWITCHES: TWENTY (20) AMPERE.A.) IN MECHANICAL AND ELECTRICAL EQUIPMENT ROOMS, ILLUMINATED LIGHT SWITCHES SHALL BE PROVIDED.4. ALL GENERAL PURPOSE TWENTY (20) A, 125/250 V RECEPTACLES AND 120/277 V SWITCHES SHALL CONFORM TO NEMA WD-1 SPECIFICATIONS.5. UNLESS OTHERWISE INDICATED, WIRING DEVICES AND COVER PLATES SHALL BE FURNISHED AND INSTALLED IN COLOR TO MATCH FINISH SURFACEWHERE IT IS LOCATED ON, I.E., DARK BROWN, BEIGE, WHITE OR STAINLESS STEEL.A.) OUTLETS SERVED FROM AN EMERGENCY POWER SYSTEM SHALL BE RED.B.) OUTLETS SERVED FROM THE NORMAL POWER SYSTEM SHALL BE IVORY OR WHITE, TO MATCH ADJACENT FINISH.C.) OUTLETS SERVED FROM AN ISOLATED GROUND SHALL BE ORANGE WITH ISOLATED GROUND (TRIANGULAR) MARKING.E. CONDUIT HANGERS1. FOR INDIVIDUAL CONDUIT RUNS NOT DIRECTLY FASTENED TO THE STRUCTURE, USE ROD HANGERS MANUFACTURED BY CADDY, UNISTRUT ORPOWERSTRUT. FOR MULTIPLE CONDUIT RUNS, USE UNISTRUT OR POWERSTRUT TRAPEZE TYPE CONDUIT SUPPORT DESIGNED FOR MAXIMUMDEFLECTION NOT GREATER THAN 1/8".2.03 PANELBOARDSA. UNLESS OTHERWISE NOTED ACCEPTABLE MANUFACTURERS ARE CUTLER HAMMER, SQUARE D, SIEMENS, GENERAL ELECTRIC, OR APPROVED EQUAL.ELECTRICAL EQUIPMENT ARE BASED ON THE FOLLOWING:1. LIGHTING AND APPLIANCE PANELBOARDS - SQUARE D NF AND NQOD2. POWER PANELBOARDS - SQUARE D, I LINEA.) CONSTRUCTION: CABINETS SHALL BE OF CODE GAUGE, GALVANIZED STEEL, SURFACE OR FLUSH MOUNTED AS INDICATED. DOORS SHALL BE OFCOLD-ROLLED STEEL WITH CONCEALED HINGES AND FLUSH CATCH AND LOCK. ALL PANELS SHALL BE KEYED ALIKE. PANELS LOCATED ADJACENTTO EACH OTHER SHALL HAVE IDENTICALLY SIZED ENCLOSURE AND TRIMS. MINIMUM PANEL WIDTH SHALL BE 20". FINISH EXPOSED PART WITHONE COAT OF PRIMER AND ONE COAT OF LIGHT GREY ENAMEL SUITABLE FOR OVER PAINTING IN FIELD IF DESIRED.B.) BUS BARS: PROVIDE GROUND BLOCK WITH FULL COMPLEMENT OF TERMINALS IN ADDITION TO INSULATED NEUTRAL BUS. FUTURE BREAKERSPACES SHALL HAVE COMPLETE PROVISION INCLUDING BUSSES AND CONNECTING HARDWARE.C.) CIRCUIT BREAKERS: SHALL BE QUICK-MAKE, QUICK-BREAK, MOLDED CASE TYPE:i. 120/240 VOLT PANELS: SHALL BE SQUARE D TYPE "QOB" LINE, BOLT-ON TYPE, WITH MINIMUM SYMMETRICAL INTERRUPTING CAPACITY ASSHOWN.ii. PROVIDE MULTI-POLE UNITS WITH COMMON TRIP ELEMENT. iii.CIRCUIT BREAKERS USED ON "ON-OFF" CONTROL OF FLUORESCENT LIGHTING(PANELBOARD SWITCHING) SHALL BE UNDERWRITERS' LABORATORIES LISTED AND MARKED "SWD" TO INDICATE THEIR SUITABILITY.B. IDENTIFICATION: PROVIDE SCREWED-ON (NO ADHESIVES) BAKELITE OR PHOTO-ETCHED METALLIC NAMEPLATE IDENTIFICATION ON OUTSIDE OF EACHPANEL SHOWING PANEL DESIGNATION, VOLTAGE AND PHASE IN MINIMUM 1/8" HIGH LETTERS. EACH PANEL SHALL CONTAIN A METAL-FRAMED CIRCUITDIRECTORY INSIDE COVER, WITH PLASTIC PROTECTOR.C. COMPLETE SHOP DRAWINGS ARE REQUIRED. DIMENSIONS SHALL MATCH FLOOR PLANS AND ELEVATIONS.2.04 LOAD CENTERSA. LOAD CENTERS TO BE FURNISHED AND INSTALLED AT LOCATIONS AS SHOWN ON THE DRAWINGS. LOAD CENTERS SHALL BE OF THE TYPE APPROVED,INDICATED, AND SPECIFIED HEREIN.B. ENCLOSURE SHALL BE FABRICATED OF COLD ROLLED STEEL FOR NEMA 1 AND GALVANNEALED STEEL OR EQUIVALENT RUST-RESISTANT STEEL FORNEMA 3R. INDOOR TYPE L ENCLOSURES SHALL HAVE A FLUSH FRONT, WITH FINISH TO BE AS SELECTED BY ARCHITECT. WHEN USED, OUTDOOR TYPE 3RENCLOSURES SHALL HAVE A HASP TO SECURE THE COVER. A DIRECTORY LABEL SHALL BE PROVIDED WITH CIRCUITS IDENTIFIED AS INDICATED ON THESCHEDULEC. BUS BAR CONNECTIONS TO THE BRANCH CIRCUIT BREAKERS SHALL BE THE DISTRIBUTED PHASE TYPE AND SHALL ACCEPT PLUG-ON CIRCUITBREAKERS. 300-400 A LOAD CENTERS SHALL ACCEPT A 150 A MAXIMUM BOLT-ON BREAKER IN ADDITION TO PLUG-ON TYPES. C. SHORT CIRCUITCURRENT RATINGS AMPERE RMS SYMMETRICAL SHORT CIRCUIT RATINGS SHALL BE COORDINATED WITH PG&E.D. CIRCUIT BREAKERS SHALL BE SQUARE D TYPE QO (PLUG-ON) THERMAL MAGNETIC TRIP OR APPROVED EQUAL, WITH AN INTEGRAL CROSSBAR TOENSURE SIMULTANEOUS OPENING OF ALL POLES IN MULTI-POLE CIRCUIT BREAKERS. CIRCUIT BREAKERS SHALL HAVE AN OVERCENTER, TRIPFREE,TOGGLE-TYPE OPERATING MECHANISM WITH QUICK-MAKE, QUICK-BREAK ACTION AND POSITIVE HANDLE INDICATION. HANDLES SHALL HAVE ON, OFF,AND "TRIPPED" POSITIONS. IN ADDITION, TRIP INDICATION SHALL INCLUDE A VISI-TRIP INDICATOR APPEARING IN THE WINDOW OF THE CIRCUIT BREAKERCASE (THROUGH 125 AMPERES). CIRCUIT BREAKERS SHALL BE UL LISTED IN ACCORDANCE WITH UL STANDARD 489 WITH CURRENT RATINGS AS NOTEDON THE PLANS. INTERRUPTING RATINGS SHALL BE SELECTED TO PROVIDE THE REQUIRED LOAD CENTER SHORT CIRCUIT CURRENT RATING.SINGLE-POLE, 15 AND 20 AMPERE CIRCUIT BREAKERS INTENDED TO SWITCH FLUORESCENT LIGHTING LOADS ON A REGULAR BASIS SHALL HAVE THESWD MARKING. TWO- AND THREE-POLE CIRCUIT BREAKERS 15-60 AMPERES INTENDED FOR USE WITH AIR CONDITIONING, HEATING, ANDREFRIGERATION EQUIPMENT HAVING MOTOR GROUP COMBINATIONS AND MARKED AS SUCH SHALL HAVE THE HACR MARKING.E. MANUFACTURERS: PANELBOARDS SHALL BE GENERAL ELECTRIC TYPE "AQ" OR TYPE "AE" OR EQUIVALENT PRODUCTS OF WESTINGHOUSE, SQUARE-DOR SIEMENS-ITE.2.05 SERVICE ENTRANCE EQUIPMENTA. SERVICE ENTRANCE EQUIPMENT ARE SUBJECT TO THE REQUIREMENTS OF THE UTILITY COMPANIES PROVIDING SERVICES TO PROJECT SITE.EQUIPMENT SHOWN ON THE CONSTRUCTION DOCUMENTS IS A GENERAL GUIDELINE AND SHALL BE ADJUSTED TO MEET SPECIFIC UTILITIESREQUIREMENTS.B. ENCLOSURES, PULL SECTIONS, AND TERMINATIONS SHALL BE TOTALLY ENCLOSED, DEAD FRONT, FREE-STANDING, FRONT AND REAR ALIGNED.ACCESSIBILITY SHALL BE FROM THE FRONT. THE EQUIPMENT SHALL BE NEMA TYPE 1 OR NEMA TYPE 3R NON-WALK-IN RAINPROOF. THE FRAMEWORKSHALL BE STEEL, SECURED TOGETHER TO SUPPORT ALL COVER PLATES, BUSSING, AND COMPONENT DEVICES DURING SHIPMENT AND INSTALLATION.ALL COVERS SHALL HAVE UTILITY SEALING PROVISIONS WHERE REQUIRED BY THE UTILITY.C. THE ENTIRE SERVICE ENTRANCE EQUIPMENT SHALL BE SUITABLE FOR OPERATION AT THE SPECIFIED AVAILABLE FAULT CURRENT. THE EQUIPMENTSHALL BE LABELED TO INDICATE THE MAXIMUM AVAILABLE FAULT CURRENT RATING, TAKING INTO ACCOUNT THE STRUCTURE, BUSSING, MAINDISCONNECTS, AND TENANT MAIN DISCONNECTS.D. THE METERING EQUIPMENT THROUGH BUS SHALL BE TIN-PLATED ALUMINUM. THE BUSSING SHALL BE OF SUFFICIENT CROSS-SECTIONAL AREA TO MEETUL STANDARD 891 FOR TEMPERATURE RISE. THE THROUGH BUS SHALL EXTEND THE FULL LENGTH OF THE EQUIPMENT AND BE 100% RATEDTHROUGHOUT THE LINE-UP. TAPERED BUS IS NOT ACCEPTABLE. THERE SHALL BE PROVISIONS FOR FUTURE SPLICING OF ADDITIONAL SECTIONS FROMEITHER END. THE NEUTRAL BUS SHALL ALSO BE 100% RATED. THE GROUND BUS SHALL BE SIZED PER UL STANDARD 891, AND OF THE SAME MATERIALAS THE THROUGH BUS. BUS CONNECTIONS SHALL BE BOLTED WITH GRADE 5 BOLTS AND CONICAL SPRING WASHERS.E. UTILITY COMPARTMENTS SHALL BE ARRANGED IN HOT SEQUENCE. THE METERING COMPARTMENTS SHALL BE BARRIERED AND COVERS SHALL HAVESEALING PROVISIONS. THE METERING COMPARTMENTS SHALL MEET EUSERC STANDARDS, OR THE APPLICABLE UTILITIES STANDARDS.F. THE MAIN DISCONNECT SHALL BE CIRCUIT BREAKER. EQUIPMENT GROUND FAULT SHALL BE PROVIDED WHEN REQUIRED PER THE NATIONALELECTRICAL CODE (NEC), OR WHEN REQUESTED BY THE CUSTOMER.G. METER SOCKETS SHALL BE RING TYPE METER SOCKETS SHALL BE RATED AS NOTED IN THE DRAWINGS. THE METER SOCKET SHALL HAVE PROVISIONSFOR A EUSERC APPROVED TEST BLOCK. THE METER SOCKET SHALL PLUG ON TO A VERTICAL BUS ASSEMBLY ON THE LINE SIDE AND BE CABLED FROMTHE LOAD SIDE OF THE METER SOCKET TO THE LINE SIDE OF THE TENANT MAIN DISCONNECT.H. BRANCH DEVICES - CIRCUIT BREAKERS SHALL BE COMMON TRIP FOR SIMULTANEOUS OPENING OF ALL POLES. BREAKERS SHALL HAVE ANOVER-CENTER, TRIP-FREE, TOGGLE-TYPE OPERATING MECHANISM WITH QUICK-MAKE, QUICK-BREAK ACTION AND POSITIVE HANDLE INDICATION.CIRCUIT BREAKERS SHALL BE UL LISTED IN ACCORDANCE WITH UL STANDARD 489 AND SHALL BE RATED FOR THE MAXIMUM VOLTAGE SPECIFIED ANDWITH CONTINUOUS CURRENT RATINGS AS NOTED ON THE PLANS. THE CIRCUIT BREAKERS SHALL BE CURRENT LIMITING.I. COMMERCIAL MULTI-METERING SHALL BE TOTALLY ENCLOSED, DEAD FRONT, FREE-STANDING, FRONT AND REAR ALIGNED. ACCESSIBILITY SHALL BEFROM THE FRONT. THE EQUIPMENT SHALL BE NEMA TYPE 1 OR NEMA TYPE 3R NON-WALK-IN RAINPROOF.2.06 INDIVIDUALLY MOUNTED MOTOR CONTROLLERSA. FOR POLYPHASE MOTORS: MAGNETIC STARTER OR COMBINATION MOTOR CIRCUIT PROTECTOR AND MAGNETIC STARTER, WITH 3-LEG OVERLOADPROTECTION. PROVIDE TWO INTERLOCK CONTACTS OF THE INTERCHANGEABLE OPEN-CLOSE TYPE. PROVIDE HAND-OFF-AUTOMATIC SELECTORSWITCH, MOTOR RUNNING PILOT LIGHT AND RESET BUTTON IN COVER. CIRCUITS 300V AND OVER SHALL BE PROVIDED WITH 120V CONTROLTRANSFORMERS.B. STARTERS FOR FRACTIONAL HORSEPOWER 120V MOTORS SHALL BE MANUAL TYPE UNLESS SHOWN OTHERWISE, EQUIPPED WITH BUILT-IN OVERLOADPROTECTION.C. ACCEPTABLE MANUFACTURERS: GENERAL ELECTRIC, SIEMENS, SQUARE D, WESTINGHOUSE, AND ALLEN BRADLEY.2.07 DISCONNECT SWITCHESA. SAFETY SWITCHES: HEAVY DUTY TYPE, 480 OR 240V, HORSEPOWER RATED FOR MOTORS, FUSED OR NON-FUSED AS REQUIRED.B. PROVIDE FUSE AS SHOWN IN CONSTRUCTION DOCUMENTS. MOUNT IN ENCLOSURE WITH NEMA RATING AS REQUIRED FOR THE SPECIFIC APPLICATION.C. ACCEPTABLE MANUFACTURERS: GENERAL ELECTRIC, SQUARE D OR WESTINGHOUSE.2.08 LOW VOLTAGE DRY TYPE DISTRIBUTION TRANSFORMERSA. TRANSFORMER 15KVA UP TO 500 KVA SHALL BE TP-1. TRANSFORMER COILS SHALL BE OF THE CONTINUOUS WOUND CONSTRUCTION. CORE AND COILSHALL BE OF COPPER. THE COMPLETED CORE AND COIL SHALL BE BOLTED TO THE BASE OF THE ENCLOSURE BUT ISOLATED BY MEANS OF RUBBERVIBRATION-ABSORBING MOUNTS. THERE SHALL BE NO METAL-TO-METAL CONTACT BETWEEN THE CORE AND COIL AND THE ENCLOSURE EXCEPT FOR AFLEXIBLE SAFETY GROUND STRAP. SOUND ISOLATION SYSTEMS REQUIRING THE COMPLETE REMOVAL OF ALL FASTENING DEVICES WILL NOT BEACCEPTABLE. THE CORE OF THE TRANSFORMER SHALL BE VISIBLY GROUNDED TO THE ENCLOSURE BY MEANS OF A FLEXIBLE GROUNDINGCONDUCTOR SIZED IN ACCORDANCE WITH APPLICABLE UL AND NEC STANDARDS.B. THE TRANSFORMER ENCLOSURES SHALL BE VENTILATED AND BE FABRICATED OF HEAVY GAUGE, SHEET STEEL CONSTRUCTIONC. SOUND LEVELS SHALL BE WARRANTED BY THE MANUFACTURER NOT TO EXCEED THE FOLLOWING -15 TO 50KVA - 45DB; 51 TO 150KVA - 50DB; 151 TO300KVA - 55DB;2.09 INTERGRATED POWER CENTERSA. INTEGRATED POWER CENTER (IPC(2)) SHALL BE COMPRISED OF COMBINATION OF POWER PANEL, LIGHTING AND APPLIANCE PANELS, LIGHTINGCONTROLS, DRY TYPE TRANSFORMERS, METERING, AND THIRD PARTY AUTOMATION. EACH COMPONENT OF INTEGRATED POWER CENTER IS SUBJECTTO OTHER PARTS OF THESE SPECIFICATIONS. AS A WHOLE, THE CONSTRUCTION OF THE IPC SHALL BE SUITABLE AND CERTIFIED FOR SPECIFIC USEAND MEETS APPLICABLE LOCAL CODES SEISMIC GUIDELINES.PART 3 - EXECUTION3.01 GENERALA. ELECTRIC SYSTEM LAYOUTS INDICATED ON THE DRAWINGS ARE GENERALLY DIAGRAMMATIC AND SHALL BE FOLLOWED AS CLOSELY AS ACTUALCONSTRUCTION AND WORK OF OTHER TRADES WILL PERMIT. GOVERN EXACT ROUTING OF CABLE AND WIRING AND THE LOCATIONS OF OUTLETS BYTHE STRUCTURE AND EQUIPMENT SERVED. TAKE ALL DIMENSIONS FROM ARCHITECTURAL DRAWINGS.B. CONSULT ALL OTHER DRAWINGS, VERIFY SCALES AND REPORT ANY DIMENSIONAL DISCREPANCIES OR OTHER CONFLICTS WITH OWNER BEFORESUBMITTING BID.C. ALL HOME RUNS TO PANELBOARDS ARE INDICATED AS STARTING FROM THE OUTLET NEAREST THE PANEL AND CONTINUING IN THE GENERALDIRECTION OF THAT PANEL. CONTINUE SUCH CIRCUITS TO THE PANEL AS THOUGH THE ROUTES WERE COMPLETELY INDICATED. TERMINATEHOMERUNS OF SIGNAL, ALARM, AND COMMUNICATION SYSTEMS IN A SIMILAR MANNER.D. AVOID CUTTING AND BORING HOLES THROUGH STRUCTURE OR STRUCTURAL MEMBERS WHEREVER POSSIBLE. OBTAIN PRIOR APPROVAL OF OWNERAND CONFORM TO ALL STRUCTURAL REQUIREMENTS WHEN CUTTING OR BORING THE STRUCTURE IS NECESSARY AND PERMITTED.E. FURNISH AND INSTALL ALL NECESSARY HARDWARE, HANGERS, BLOCKING, BRACKETS, BRACING, RUNNERS, ETC. REQUIRED FOR EQUIPMENT SPECIFIEDUNDER THIS SECTION. INSTALLATION SHALL MEET SEISMIC 4 REQUIREMENTS.F. PROVIDE NECESSARY BACKING REQUIRED TO INSURE RIGID MOUNTING OF OUTLET BOXES.G. ELECTRICAL INSTALLATION IN PUBLIC LOCATIONS SHALL BE ACCESSIBLE AND INSTALLATION SHALL COMPLY WITH AMERICAN DISABILITIES ACT (ADA)REQUIREMENTS. ELECTRICAL INSTALLATION SHALL COMPLY WITH APPLICABLE CODES AS LISTED IN CONSTRUCTION DOCUMENTS.3.02 WIRING METHODSA. IN CONCEALED SPACES WHERE THE USE OF "ROMEX" AND "BX" WIRING IS PERMITTED BY ALL APPLICABLE CODES AND REGULATIONS, PROVIDEFACTORY-FABRICATED, PRE-ASSEMBLED UL LABELED TYPE "NMC" AND TYPE "AC" CABLES AS PREFERRED WIRING METHOD FOR BRANCH CIRCUITS. AGROUNDING CONDUCTOR SHALL BE PROVIDED IN EACH CABLE.B. WHEN CONDITIONS DETERMINED IN "A" ABOVE ARE NOT MET, INSTALL ALL WIRING IN RACEWAY, OR USE MC CABLE WHERE APPROVED BY ALLAPPLICABLE CODES AND REGULATIONS. CONDUIT SHALL BE RIGID STEEL, IMC OR EMT AS FOLLOWS:1. ABOVE GROUND: USE RIGID STEEL, IMC OR EMT.2. WET LOCATIONS: RIGID STEEL OR IMC ONLY.3. LOCATIONS SUBJECT TO MECHANICAL INJURY: RIGID STEEL OR IMC ONLY.4. DRY LOCATIONS AND NOT SUBJECT TO MECHANICAL INJURY: EMT, IMC OR RIGID STEEL CONDUIT.5. UNDERGROUND: USE RIGID STEEL AT LAST TRANSITION TO ABOVE GROUND.C. USE FLEXIBLE CONDUITS OR MC CABLE IN THE FOLLOWING APPLICATIONS:1. FINAL CONNECTIONS TO MOTOR.2. FINAL CONNECTIONS INTO AND OUT OF THE TRANSFORMER.3. FINAL CONNECTIONS TO VIBRATING EQUIPMENT.4. INTER-CONNECTIONS BETWEEN ALL LIGHT FIXTURES (NOT TO INCLUDE HOMERUN FROM FIXTURE OR DEVICE TO PANELBOARD, WHICH MUST BERIGID).5. FINAL CONNECTIONS WHERE RIGID CONDUIT IS NOT PRACTICAL.6. IN WALLS (FOR LIGHT SWITCHES AND 120V POWER RECEPTACLES AND HVAC CONTROL EQUIPMENT).D. FLEXIBLE METALLIC CONDUIT OR MC CABLE MUST BE THE SAME SIZE AS THE RIGID CONDUIT TO WHICH IT IS CONNECTED.E. THE CONNECTION TO OUTDOOR EQUIPMENT MUST BE WEATHERPROOF, I.E. LIQUIDTIGHT OR SEALTIGHT.F. MINIMUM SIZE OF CONDUIT SHALL BE 1/2" FOR INDIVIDUAL LIGHTING FIXTURE CONNECTIONS OR TO INDIVIDUAL LIGHT SWITCHES IF APPROVED BY ALLAPPLICABLE CODES. MINIMUM SIZE FOR ALL OTHER LOCATIONS SHALL BE 3/4". IF HVAC CONTROL WIRING IS REQUIRED TO BE RUN IN CONDUIT, IT SHALLBE A 3/4" MINIMUM, UNLESS OTHERWISE NOTED ON DRAWINGS. ALL IN/UNDER FLOOR CONDUITS SHALL BE 3/4" MINIMUM SIZE.G. USE OF RIGID NON METALLIC CONDUIT IS LIMITED TO OUTDOOR, UNDERGROUND UP TO THE LAST PULLBOX PRIOR TO ENTERING OR TRANSITIONING TOABOVE GROUND. TRANSITION SHALL BE TAPED WRAPPED RIGID STEEL CONDUIT.3.03 INSTALLATION OF CONDUITSA. GENERAL:1. RUN ALL CONDUITS CONCEALED UNLESS OTHERWISE NOTED OR SHOWN. RUN ALL CONDUIT PARALLEL TO OR AT RIGHT ANGLES TO CENTER LINESOF COLUMNS AND BEAMS. CONDUITS ABOVE CEILINGS SHALL NOT OBSTRUCT REMOVAL OF CEILING TILES, LIGHTING FIXTURES, AIR DIFFUSERS,ETC. CONDUITS SHALL NOT CROSS ANY DUCT SHAFT OR AREA DESIGNATED AS FUTURE DUCT SHAFT HORIZONTALLY. CONDUIT RISERS WHENALLOWED IN DUCT SHAFT MUST BE COORDINATED WITH MECHANICAL WORK TO AVOID ANY CONFLICT.B. CONDUIT SUPPORTS:1. SUPPORT CONDUITS WITH UNDERWRITER'S LABORATORIES LISTED STEEL CONDUIT SUPPORTS AT INTERVALS REQUIRED BY THE NATIONALELECTRIC CODE. WIRES OR SHEET METAL STRIPS ARE NOT ACCEPTABLE FOR CONDUIT SUPPORT. USE CONDUIT HANGERS FOR ALL CONDUITS NOTDIRECTLY FASTENED TO STRUCTURE AND FOR ALL MULTIPLE CONDUIT RUNS. DO NOT ATTACH ANY CONDUIT TO MECHANICAL DUCTS OR PIPES.2. INDIVIDUAL CONDUITS 1/2" AND 3/4" SIZE FOR LIGHTING MAY BE SUPPORTED FROM CEILING SUPPORT WIRES WITH CADDY CLIPS ONLY IFACCEPTABLE TO LOCAL CODE. ONLY ONE CONDUIT IS PERMITTED TO BE ATTACHED TO ANY CEILING SUPPORT WIRE. HANG SUCH CONDUIT SO ASNOT TO AFFECT LEVEL OF CEILING.3. AVOID ATTACHING CONDUIT TO FAN PLENUMS. WHEN IT IS NECESSARY TO SUPPORT CONDUIT FROM FAN PLENUM, PROVIDE A LENGTH OF FLEXIBLECONDUIT BETWEEN PORTION ATTACHED FAN PLENUM AND PORTION ATTACHED TO THE BUILDING TO MINIMIZE TRANSMISSION OF VIBRATION TOTHE BUILDING STRUCTURE.C. CONDUIT PENETRATION:1. PENETRATING FIRE RATED FLOOR OR WALL: INSTALL CONDUIT IN CONDUIT SLEEVE OR FRAMED OPENING. SEAL PENETRATION WITH FIRERETARDANT SEALANT TO MATCH CONSTRUCTION FIRE RATING.2. PENETRATING ROOF OR EXTERIOR WALL: AVOID PENETRATING ROOF OR EXTERIOR WALL WHERE POSSIBLE. WHERE PENETRATIONS ARENECESSARY, BUILDING WEATHERPROOF INTEGRITY MUST BE PRESERVED.3. PENETRATING SOUND INSULATED OR AIR PLENUM WALL: INSTALL CONDUIT IN CONDUIT SLEEVE AND SEAL PENETRATION AS DETAILED ON THEDRAWINGS.4. PENETRATING NON-FIRE RATED DRY WALL: CONDUIT SLEEVES ARE NOT REQUIRED. PENETRATIONS MUST BE SEALED WITH PLASTER PRIOR TOPAINTING. PENETRATIONS MADE AFTER WALL FINISH IS APPLIED MUST BE AS SMALL AS POSSIBLE AND PROVIDED WITH ESCUTCHEONS, ONE ONEACH SIDE OF WALL.5. PENETRATING SUSPENDED CEILING: CUT HOLE AS SMALL AS POSSIBLE TO PERMIT CONDUIT PENETRATION. PROVIDE ESCUTCHEON FOR EACHCONDUIT BELOW CEILING.3.04 CONNECTIONS TO EQUIPMENTA. GENERAL1. FURNISH AND INSTALL REQUIRED POWER SUPPLY CONDUIT AND WIRING TO ALL EQUIPMENT IDENTIFIED IN THE CONSTRUCTION DOCUMENTS.2. FURNISH AND INSTALL A DISCONNECT SWITCH IMMEDIATELY AHEAD OF AND ADJACENT TO EACH MAGNETIC MOTOR STARTER OR APPLIANCEUNLESS THE MOTOR APPLIANCE IS LOCATED ADJACENT AND WITHIN SIGHT OF THE SERVING PANELBOARD, CIRCUIT BREAKER OR SWITCH. VERIFYALL EQUIPMENT NAMEPLATE CURRENT RATINGS PRIOR TO INSTALLATION.3. INSTALL ALL ROUGH-IN WORK FOR EQUIPMENT FROM APPROVED SHOP DRAWINGS TO SUIT THE SPECIFIC REQUIREMENTS OF THE EQUIPMENT.4. FURNISH AND INSTALL MANUAL THERMAL PROTECTION FOR ALL MOTORS NOT INTEGRALLY EQUIPPED WITH THERMAL PROTECTION.5. FURNISH 120 VOLT POWER TO EACH CONTROL PANEL AND TIME SWITCH REQUIRING A SOURCE OF POWER TO OPERATE.3.05 INSTALLATION OF WIRESA. PULL NO WIRE INTO ANY PORTION OF THE CONDUIT SYSTEM UNTIL ALL CONSTRUCTION WORK WHICH MIGHT DAMAGE THE WIRE HAS BEENCOMPLETED.B. INSTALL ALL WIRE CONTINUOUS FROM OUTLET TO OUTLET OR TERMINAL TO TERMINAL. SPLICES IN CABLES WHEN REQUIRED SHALL BE MADE INHANDHOLES, PULL BOXES OR JUNCTION BOXES. MAKE BRANCH CIRCUIT SPLICES IN OUTLET BOXES WITH 8" OF CORRECTLY COLOR-CODED TAILS LEFTIN THE BOX.C. SPLICES IN WIRES AND CABLES SHALL BE MADE UTILIZING MATERIALS AND METHODS DESCRIBED HEREIN BEFORE.D. MAKE ALL GROUND, NEUTRAL AND LINE CONNECTIONS TO RECEPTACLE AND WIRING DEVICE TERMINALS AS RECOMMENDED BY MANUFACTURE.PROVIDE GROUND JUMPER FROM OUTLET BOX TO GROUND TERMINAL OF DEVICES WHEN THE DEVICE IS NOT APPROVED FOR GROUNDING THROUGHTHE MOUNTING SCREWS.E. PROVIDE BRADY WIRE MARKERS WHERE NUMBER OF CONDUCTORS IN A BOX EXCEEDS FOUR.3.06 WIRE COLOR CODE:A. COLOR CODING SHALL BE CONTINUOUS FOR WIRE #12 THROUGH #10 AWG. PHASE CONDUCTORS #8 AND LARGER AND CONDUCTORS OF ANY SIZE INCABLE ASSEMBLIES MAY HAVE COLORED PHASING TAPE AT TERMINATIONS. WHERE MORE THAN ONE NOMINAL VOLTAGE SYSTEM EXISTS IN ABUILDING, EACH UNGROUNDED SYSTEM CONDUCTOR SHALL BE IDENTIFIED BY PHASE AND SYSTEM. THE MEANS OF IDENTIFICATION SHALL BEPERMANENTLY POSTED AT EACH BRANCH CIRCUIT PANELBOARD. THE PHASE COLOR CODING OF THE INSULATION OF CONDUCTORS SHALL BE:1. VOLTAGE 120/208VA.) PHASE AB.) PHASE BC.) PHASE CD.) NEUTRALE.) GROUNDBLACKREDBLUEWHITEGREENF.) ISOLATED GROUND2. VOLTAGE 277/480VA.) PHASE AB.) PHASE BC.) PHASE CD.) NEUTRALE.) GROUNDF.) ISOLATED GROUNDGREEN WITH ORANGE STRIPEBROWNPURPLEYELLOWGRAYGREENGREEN WITH ORANGE STRIPE3.07 IDENTIFICATIONA. PROVIDE NAMEPLATES FOR ALL ELECTRICAL EQUIPMENT AND ALL SIMILAR EQUIPMENT AND DEVICES. NAMEPLATES SHALL BE SCREWED (NOADHESIVES) ENGRAVED BAKELITE OR PHOTO-ETCHED METALLIC NAMEPLATE IDENTIFICATION SHOWING PANEL DESIGNATION, VOLTAGE AND PHASE INMINIMUM 1/4" HIGH LETTERS.B. PROVIDE DEMO LABELS ON ALL LIGHTING SWITCHES AND CONVENIENCE AND SPECIAL PURPOSE RECEPTACLES TO SHOW PANEL AND CIRCUIT NUMBERTO WHICH THE DEVICE IS CONNECTED.C. EACH PANELBOARD SHALL CONTAIN A METAL-FRAMED CIRCUIT DIRECTORY INSIDE COVER, WITH PLASTIC PROTECTOR.D. PANELBOARD SCHEDULE: AFTER COMPLETION OF WORK, PROVIDE ELECTRONIC UPDATED PANELBOARD SCHEDULES FOR ALL PANELBOARDS. USEEXCEL FORMAT.3.08 GROUNDINGA. ELECTRICAL SERVICE AND SEPARATELY DERIVED ALTERNATING CURRENT SYSTEM SHALL BE GROUNDED IN ACCORDANCE WITH NEC 2014, ARTICLE250.B. GROUND NON-CURRENT CARRYING METAL PARTS OF ELECTRICAL EQUIPMENT ENCLOSURES, FRAMES, CONDUCTOR RACEWAYS OR CABLE TRAYS TOPROVIDE A LOW IMPEDANCE PATH FOR LINE-TO-GROUND FAULT CURRENT AND TO BAND ALL NON-CURRENT CARRYING METAL PARTS TOGETHER.PROVIDE GROUND CONDUCTOR IN EACH RACEWAY SYSTEM IN ADDITION TO CONDUCTORS SHOWN. EQUIPMENT GROUND CONDUCTOR SHALL BEELECTRICALLY AND MECHANICALLY CONTINUOUS FROM THE ELECTRICAL CIRCUIT SOURCE TO THE EQUIPMENT TO BE GROUNDED. SIZE GROUNDCONDUCTORS PER NEC 2014 UNLESS LARGER CONDUCTORS ARE SHOWN ON DRAWINGS.C. GROUNDING CONDUCTORS SHALL BE IDENTIFIED WITH GREEN INSULATION. WHERE GREEN INSULATION IS NOT AVAILABLE ON LARGER SIZES, BLACKINSULATION SHALL BE USED AND SUITABLY IDENTIFIED WITH GREEN TAPE AT EACH JUNCTION BOX OR DEVICE ENCLOSURE.3.09 REMODELING WORKA. EXISTING ELECTRICAL WIRING WHICH WILL NOT BE MADE OBSOLETE AND WHICH WILL BE DISTURBED DUE TO CONSTRUCTION CHANGES REQUIRED BYTHIS CONTRACT SHALL BE RESTORED TO OPERATING CONDITION. WHERE CONSTRUCTION CHANGES REQUIRE, OUTLETS AND CONDUIT RUNS SHALL BERELOCATED. EXTEND CONDUITS AND PULL IN NEW WIRING OR INSTALL JUNCTION BOXES AND SPLICE IN NEW WIRING.B. OUTLETS FROM WHICH FIXTURES, SWITCHES, RECEPTACLES, AND/OR OTHER ELECTRICAL DEVICES ARE MOVED AND WHICH ARE NOT REPLACED ORREUSED SHALL BE REMOVED, WHERE OUTLETS BOXES, ETC., ARE COMPLETELY REMOVED, THE CONTRACTOR SHALL CUT OFF CONDUITS AND REMOVEWIRING.C. WHERE CONDUITS EXTENDING THROUGH FLOORS ARE TO BE ABANDONED, THE CONTRACTOR SHALL CUT AND CAP OR PLUG CONDUIT, AND THECONDUIT SHALL NOT PROTRUDE ABOVE THE FLOOR.D. WHERE EXISTING CONDUIT IS TO BE ABANDONED, THE CONDUIT SHALL BE REMOVED IF IT IS EXPOSED, IN A CRAWL SPACE OR IN ACCESSIBLE CEILING.WHERE IT IS IMPOSSIBLE TO REMOVE THE CONDUIT, IT SHALL BE CUT OFF AND CAPPED OR PLUGGED.E. REMOVE ALL EXISTING WIRING NOT REUSED OR REQUIRED TO MAINTAIN CONTINUITY TO CIRCUITS TO REMAIN.F. THE CONTRACTOR SHALL BE HELD FULLY RESPONSIBLE FOR THE PROPER RESTORATION OF ALL EXISTING SURFACES REQUIRING PATCHING,PLASTERING, PAINTING AND/OR OTHER REPAIRS DUE TO THE INSTALLATION OF ELECTRICAL WORK UNDER THE TERMS OF THIS SPECIFICATION. CLOSEALL OPENINGS, REPAIR ALL SURFACES, ETC., AS REQUIRED.G. FIRESTOP ALL PENETRATIONS.H. MAINTAIN CIRCUIT CONTINUITY TO AREAS OUTSIDE OF THIS WORK. PROVIDE NEW CONDUIT AND CONDUCTORS AS REQUIRED TO MAINTAIN CONTINUITYAND MAINTAIN AREA AS EXISTING.3.10 ELECTRICAL ACCEPTANCE TESTINGA. PERFORM PHYSICAL AND VISUAL INSPECTION OF ELECTRICAL INSTALLATION. ENSURE THAT ALL WIRES HAVE BEEN TERMINATED, CONNECTIONSTIGHTENED, AND OPENINGS ARE PROTECTED.B. PERFORM PHASE ROTATION, CONTINUITY TEST, AND PHASE BALANCE1. VOLTAGE READINGS SHALL BE TAKEN AT VARIOUS TEST POINTS, OR AT THE DISCRETION OF THE AHJ.2. VOLTAGE, PHASE, AND AMP READINGS SHALL BE TAKEN ON ALL THREE PHASES UNDER LOAD CONDITIONS.3. VERIFY THAT MOTORS ARE ROTATING IN THE CORRECT DIRECTION. VERIFY THAT EACH PHASE LOAD IS WITHIN 20% OF EACH OTHER. ADJUST ASNECESSARY.C. INSULATION TEST1. PERFORM MEGGER AND RECORD INSULATION RESISTANCE, 1000 VOLT MEGGER FOR ONE MINUTE. MAKE TESTS WITH CIRCUITS ISOLATED FROMSOURCE AND LOAD. A.) 600V CONDUCTORS SIZE #4/0 AND LARGER B.) MCC, SWITCHGEAR, SWITCHBOARD, AND PANELBOARD BUSS BARS C.) MOTORAND TRANSFORMER WINDINGSD. TESTING SHALL BE PER NEMA ACCEPTANCE STANDARDS.E. SUBMIT TEST RESULTS TO ENGINEER. EQUIPMENT THAT HAVE FAILED TESTS SHALL BE REPLACED WITHIN 2 WEEKS AND PRIOR TO PROJECTCOMPLETION.END OF SECTIONELECTRICAL SPECIFICATIONSSCALENTS14275 N Palm St, Suite 100
Fullerton, CA 92835
(714) 578-2300 office
www.coolsysenergydesign.com