2020.0103.BPP0008 3730 - R3 REFRIGERATION SCHEDULES - 3705 COPY*MODIFIED CIRCUIT/**NEW CASE, VALVE OR EVAPORATOR.
REFRIGERATION
SCHEDULE
SYSTEM
M T E
Novar
Refrig. EMS:
Novar
Condenser Type:
Air
H/R Media:
N/A
Subcooler Liquid Temps
SG1 Comp RGT °F:
50
100
DESIGN DB IF:
100
EXTERIOR DRY BULB (DB) OF:
97
Format: Supercenter
Store#: 3705
System Type:
Weather Pac
R404A
Primary Refrigerant:
R404A
System Elec:
460V 3Ph 60Hz
Sat. Cond. Temp °F:
115
H/R Use:
N/A
SG1 Liquid Temp
115
SG2 Comp RGT °F:
N/A
65.5
DESIGN WB OF:
65.5
Based on 5 yr Extreme DB-ASHRAE Pub.:
Year 2017
Proto Size: Renovation
City/State: Yelm, WA
Consultant:
DCE
N/A
Estimated Refrigerant Charge
N/A
Defrost Elec:
208V 60Hz 1 or 3 Ph
Cond Design TD °F:
15
H/R Water GPM:
N/A
SG2 Liquid Temp
N/A
SG3 Comp RGT °F:
N/A
75
DESIGN INTERIOR DRY BULB OF:
75
EXTERIOR WET BULB (WB) OF:
65.5
ProtoCycle Date: 1/31/2020
Date Prepared 3/11/2020
Prepared by:
Alec Gauthier
--
Rack and Condenser (Ibs)
--
Sys.Pilot Elec:
208V 1 Ph
Summer H/R Avail:
N/A
H/R Glycol Type:
N/A
SG3 Liquid Temp
N/A
Evap. Superheat °F:
10
55%
DESIGN INTERIOR RH %
55%
Based on 0.4% Monthly Max WB-ASHRAE Pub.:
Year 2017
2 Dr/4'
3 Dr/6'
Fixture and Field Piping (Ibs)
N/A
Cond. Elec:
Fixture and Field Piping (Ibs)
N/A
Cond. Elec:
460V 3 Ph 60Hz
Winter H/R Avail:
N/A
H/R Glycol %:
N/A
Voltage
RCU-2
2
2
ELEVATION ft:
300
ELEVATION ft:
300
HUSSMANN
CIRCUIT INFORMATION
CIRCUIT INFORMATION
43.3
25
32
E9
OT
-
FIXTURE ELECTRICAL INFORMATION
3
120/1
FIXTURE ELECTRICAL
INFORMATION
50
Case Fixture Length / Quantity
MISC INFORMATION
Case Model
CKT #
Case Fixture Length / Quantity Walk -In Box Size
FT /# of Doors 2 Dr/4' 3 Dr/6' 4 Dr/8' 5 Dr/12' L W H Case Model
Case/Coil Manuf.
Evaporator
Model #
Application
Evaporator
Model #
LSHX Y or N?
& Model #
WI Evaps
Evaporator
Coil TXV /
Distributor Nozzle
Sub -Circuit Load
(MBH)
Circuit
Load (MBH)
Case/
Evap Walk -In
Temp Air Temp
Circuit Control Valves
EPR LLSV
Defrost
Type
Defrost Heaters
Amps Voltage
Amps
Fans
Voltage
Lights Anti -Sweat
Amps Amps
(120v) (120v)
Amps
Comments
E1*
32 FT 1 2
HQD6L1
KYSOR/WARREN
EPR LLSV
M.D. Beer
Voltage Amps
-
-
42.0
30 ETR
SORIT15**
E10**
OT
- -
4.8
115/1
ETR -
EGSE-2-C / 1-1/2
RELOCATED
14.7
E2
24 FT 2
N6DM
TYLER
EL
M.D. Dairy
208/1
-
-
208/1
29.4
21 ETR
SORIT20
ME9
OT
- -
3.2
115/1
ETR -
14 10
EXISTING TO REMAIN
E3
24 FT 2
N6DM
TYLER
EGSE-1-1/2-C / 1
M.D. Dairy
10.0
-
-
SORIT12
29.4
21 ETR
SORIT20
ME9
OT
- -
3.2
115/1
ETR -
EXISTING TO REMAIN
E4
22 62
11
BOHN
22 12
1/3 Dairy Cooler
ADT -312
HXR250A
SSE -4-C / 2-1/2
WK -210
30.8
25 ETR
SORIT12
ME9
OT
- -
12.6
120/1
OT
-
EXISTING TO REMAIN
8.4
E5A
22 62
11
BOHN
1/3 Dairy Cooler
ADT -312
HXR250A
SSE -4-C / 2-1/2
30.8
25 ETR
SORIT20
ME14
OT
- -
12.6
120/1
EXISTING TO REMAIN
-
E5B
22 62
11
BOHN
1/3 Dairy Cooler
ADT -312
HXR250A
SSE -4-C / 2-1/2
30.8
25 ETR
-
-
OT
- -
12.6
120/1
EXISTING TO REMAIN
E6
36 FT 3
N6DMR
TYLER
M.D. Rear Load Dairy
-
-
-
ME6
44.1
21 ETR
SORIT20
ME14
OT
- -
4.8
120/1
ETR -
DEMO CIRCUIT BACK TO RACK
EXISTING TO REMAIN
F6*
E7
8 FT 1
N6DM
TYLER
SMBT
M.D. Dairy
HUSSMANN
-
-
-
9.8
21 ETR
SORIT12
ME6
OT
- -
1.1
120/1
ETR -
-
EXISTING TO REMAIN
E8A
6 46
11
BOHN
REDUCED/RELOCATED
1/3 Dairy Cooler
SM -076
HXR75
EGSE-1-C / 3/4
6.9
27 ETR
SORIT12
ME6
OT
- -
4.2
115/1
16.0
EXISTING TO REMAIN
ETR
E8B
6 46
11
BOHN
-
1/3 Dairy Cooler
SM -076
HXR75
EGSE-1-C / 3/4
-
6.9
27 ETR
-
-
OT
- -
4.2
115/1
ON3UM/EM
EXISTING TO REMAIN
Deli Promo Island
E8C
-
-
BOHN
25.2
1/3 Dairy Cooler
SM -076
HXR75
EGSE-1-C / 3/4
OT
6.9
27 ETR
-
-
OT
- -
4.2
115/1
EXISTING TO REMAIN
EXISTING TO REMAIN
9 FT
E9*
24 FT 2
05DM-NRG
HILL PHOENIX
M.D. Beer
Floral
-
-
-
22.4
34 ETR
SORIT12
E9
OT
- -
1.4
115/1
TBD -
2.6
REDUCED / RELOCATED
120/1
ETR
-
EXISTING TO REMAIN
F10
32 FT 1
Suction Group #1 Required Capacity (MBH)
290.2
19 (°F) Saturated Suction Temperature
N6DL
TYLER
M.D. Produce w/ misters
-
-
43.0
21
ETR
SORIT20
ME14
OT
-
-
General Notes:
120/1
ETR
-
EXISTING TO REMAIN
F11
36 FT
3
1)
The scheduled data for existing to remain components, circuit loads, and electrical conditions are reproduced from original documents and may not reflect as -built conditions.
TYLER
M.D. Produce w/ misters
-
-
48.4
21
ETR
SORIT20
ME14
OT
-
-
4.8
2.)
Contractor shall field verify existing status of data shown for modified racks and notify engineer of any discrepancies.
ETR
-
EXISTING TO REMAIN
F12
12 FT
1
N6DL
TYLER
M.D. Produce w/ misters
-
-
3.)
Owner's designated refrigeration equipment manufacturer: Hill Phoenix
21
ETR
SORIT12
ME6
OT
-
-
1.6
120/1
ETR
-
EXISTING TO REMAIN
F13
8 FT 1
4.)
Original design dry bulb temp used.
BARKER
Service Seafood
-
-
5.0
20
ETR
SORIT12
ME6
OT
-
-
0.9
120/1
ETR
5.)
Case manufacturer shall size and provide mechanical TXVs for new cases.
EXISTING TO REMAIN
Suction Group #1 Required Capacity (MBH)
221.4
16
(°F)
Saturated Suction Temperature
6.)
General Notes:
*MODIFIED CIRCUIT/**NEW CASE, VALVE OR EVAPORATOR.
*MODIFIED CIRCUIT/ **NEW CASE, VALVE OR EVAPORATOR.
REFRIGERATION SCHEDULE
SYSTEM MTF
SYSTEM RCU
Refrig. EMS:
Novar
Condenser Type:
Air
H/R Media:
N/A
Subcooler Liquid Temps
SG1 Comp RGT °F:
50
97
DESIGN DB OF:
100
EXTERIOR DRY BULB (DB) IF:
97
Format: Supercenter
Store#: 3705
Primary Refrigerant:
System Type:
Weather Pac
Primary Refrigerant:
R404A
System Elec:
460V 3Ph 60Hz
Sat. Cond. Temp °F:
115
H/R Use:
N/A
SG1 Liquid Temp
115
SG2 Comp RGT °F:
N/A
DCE
DESIGN WB °F :
65.5
Based on 5 yr Extreme DB-ASHRAE Pub.:
Year 2017
Proto Size: Renovation
City/State: Yelm, WA
EXTERIOR WET BULB (WB) OF:
Consultant:
DCE
Estimated Refrigerant Charge
N/A
Defrost Elec:
208V 60Hz 1 or 3 Ph
Cond Design TD °F:
15
H/R Water GPM:
N/A
SG2 Liquid Temp
N/A
SG3 Comp RGT °F:
N/A
55%
DESIGN INTERIOR DRY BULB IF:
75
EXTERIOR WET BULB (WB) OF:
65.5
ProtoCycle Date: 1/31/2020
Date Prepared 3/11/2020
Case Fixture Length / Quantity
Prepared by:
Alec Gauthier
Rack and Condenser (Ibs)
--
Sys.Pilot Elec:
208V 1 Ph
Summer H/R Avail:
N/A
H/R Glycol Type:
N/A
SG3 Liquid Temp
N/A
Evap. Superheat °F:
10
Lights
Amps
(120v)
DESIGN INTERIOR RH %
55%
Based on 0.4% Monthly Max WB-ASHRAE Pub.:
Year 2017
Liquid Line (in)
FT /# of Doors
2 Dr/4'
3 Dr/6'
Fixture and Field Piping (Ibs)
N/A
Cond. Elec:
460V 3 Ph 60Hz
Winter H/R Avail:
N/A
H/R Glycol %:
N/A
Voltage
RCU-1
2872 ENDS
Voltage
RCU-2
2
2
ELEVATION ft:
300
1
IM -05 -EC (RD4046.452/RD4047.452)
HUSSMANN
CIRCUIT INFORMATION
ON5DMX-NRG (RD4043.042)
43.3
25
32
E9
OT
-
FIXTURE ELECTRICAL INFORMATION
3
120/1
MISC INFORMATION
-
50
Case Fixture Length / Quantity
Walk -In Box Size
Case Model
0.4
Case/Coil Manuf.
Application
Evaporator
Model #
LSHX Y or N?
& Model #
WI Evaps
Evaporator
Coil TXV /
Distributor Nozzle
Sub -Circuit Load
(MBH)
Circuit
Load (MBH)
Evap
Temp
Case/
Walk -In
Air Temp
Circuit Control Valves
Defrost
Type
Defrost Heaters
Fans
Lights
Amps
(120v)
Anti -Sweat
Amps
(120v)
Amps
Comments
CKT # FT /# of Doors 2 Dr/4' 3 Dr/6' 4 Dr/8'
5 Dr/12'
L
W H
EPR LLSV
Amps
Voltage Amps
Voltage
F1
14
14 10
BOHN
Poultry/Deli Cooler W.I.
WKE-155
HXR150A
EGSE-2-C / 1-1/2
14.7
22
ETR
SORIT12
ME6
EL
17.4
208/1
2.2
208/1
EXISTING TO REMAIN
F2
7
14 10
BOHN
Bakery Cooler W.I.
ADT -104
HXR150A
EGSE-1-1/2-C / 1
10.0
25
ETR
SORIT12
ME6
OT
-
-
4.2
120/1
EXISTING TO REMAIN
F3
16
22 12
BOHN
Produce Cooler W.I.
WK -210
HXR250A
EGSE-2-C / 2
17.5
25
ETR
SORIT12
ME9
OT
-
-
8.4
120/1
EXISTING TO REMAIN
F4*
SPARE STUB
-
-
SORIT12
ME6
DEMO CIRCUIT BACK TO RACK
F5*
SPARE STUB
-
-
SORIT12
ME6
DEMO CIRCUIT BACK TO RACK
F6*
12 FT
1
SMBT
HUSSMANN
Service Deli
-
-
5.1
18
ETR
SPORT115**
E3**
OT
-
-
0.9
120/1
TBD
-
REDUCED/RELOCATED
F7
16 FT 2
B3
KYSOR/WARREN
M.D. Cake
-
-
16.0
20
ETR
SORIT12
ME9
OT
-
-
2.2
120/1
ETR
-
EXISTING TO REMAIN
F8
14 FT
ON3UM/EM
HILL PHOENIX
Deli Promo Island
-
-
25.2
22
ETR
SORIT12
ME9
OT
-
-
5.0
120/1
ETR
-
EXISTING TO REMAIN
F9
9 FT
RFCL290
BORGEN
Floral
-
-
20.4
34
ETR
SORIT12
ME9
OT
-
-
2.6
120/1
ETR
-
EXISTING TO REMAIN
F10
32 FT 1
2
N6DL
TYLER
M.D. Produce w/ misters
-
-
43.0
21
ETR
SORIT20
ME14
OT
-
-
4.3
120/1
ETR
-
EXISTING TO REMAIN
F11
36 FT
3
N6DL
TYLER
M.D. Produce w/ misters
-
-
48.4
21
ETR
SORIT20
ME14
OT
-
-
4.8
120/1
ETR
-
EXISTING TO REMAIN
F12
12 FT
1
N6DL
TYLER
M.D. Produce w/ misters
-
-
16.1
21
ETR
SORIT12
ME6
OT
-
-
1.6
120/1
ETR
-
EXISTING TO REMAIN
F13
8 FT 1
BWU-96R-MT
BARKER
Service Seafood
-
-
5.0
20
ETR
SORIT12
ME6
OT
-
-
0.9
120/1
ETR
-
EXISTING TO REMAIN
Suction Group #1 Required Capacity (MBH)
221.4
16
(°F)
Saturated Suction Temperature
General Notes:
1)
The scheduled data for existing to remain components, circuit loads, and electrical conditions are reproduced from original documents and may not reflect as -built conditions.
2.)
Contractor shall field verify existing status of data shown for modified racks and notify
engineer of any discrepancies.
3)
Owner's designated refrigeration equipment manufacturer: HILL PHOENIX
4)
Original design dry bulb temp used.
5.)
Case manufacturer shall size and provide mechanical TXVs for new cases.
6.)
*MODIFIED CIRCUIT/ **NEW CASE, VALVE OR EVAPORATOR.
NOTES:
1.) Owner's designated refrigeration equipment manufacturer: HILL PHOENIX
2.) Furnish with time clock for defrost control, installed inside condensing unit.
3.) Furnish with thermostat and solenoid for temperature control.
4.) RCU-1 AND ALL COMPONENTS ARE NEW
0
w 0~OK
ww
REFRIGERATION SCHEDULE SYSTEM RCU -1
SYSTEM RCU
_2
3Z
� �o��0Z 3ZZcnog
w-zw~�waZ�rZ
Sat. Cond. Temp °F:
112
DESIGN DB IF:
97
EXTERIOR DRY BULB (DB) IF:
EXTERIOR DRY BULB (DB) IF:
97
97
Format:
Supercenter
Store#: 3705
Store#: 3705
System Type:
Condensing Unit
Primary Refrigerant:
R407a
Cond Design TD °F:
15
DESIGN WB OF:
66
Based on 5 yr Extreme DB-ASHRAE Pub.:
Based on 5 yr Extreme DB-ASHRAE Pub.:
Year 2017
Year 2017
Proto Size:
Renovation
City/State: Yelm, WA
City/State: Yelm, WA
Consultant:
DCE
Evap. Superheat °F:
10
Liquid Temp
112
DESIGN INTERIOR DRY BULB OF:
75
EXTERIOR WET BULB (WB) OF:
EXTERIOR WET BULB (WB) OF:
65.5
65.5
ProtoCycle Date:
1/31/2020
Date Prepared 3/11/2020
Date Prepared 3/11/2020
Prepared by:
Alec Gauthier
Elevation ft:
300
Return Gas Temp °F:
50
DESIGN INTERIOR RH %
55%
Based on 0.4% Monthly Max WB-ASHRAE Pub.:
Based on 0.4% Monthly Max WB-ASHRAE Pub.:
Year 2017
Year 2017
CKT #
CKT #
Case Fixture Length / Quantity
Walk -In Box Size
Case Model
Case/Coil Manuf.
Application
Evaporator
Model #
LSHX Y or N?
& Model #
WI Evaps
Evaporator
Coil TXV /
Distributor
Nozzle
Circuit
Load (MBH)
Evap
Temp (F)
Case/
Walk -In
Air Temp (F)
Liquid Line
Solenoid
Valve
Defrost
Type
Defrost Heaters
Fans
Lights
Amps
(120v)
Anti -Sweat
Amps
(120v)
Total Line
Length(ft)Suction
9
Horiz (in)
Suction Riser (in)
Liquid Line (in)
FT /# of Doors
2 Dr/4'
3 Dr/6'
4 Dr/8'
5 Dr/12'
L
W
H
Amps
Voltage
Amps
Voltage
RCU-1
2872 ENDS
Voltage
RCU-2
2
2
1
IM -05 -EC (RD4046.452/RD4047.452)
HUSSMANN
M.D. Beer
ON5DMX-NRG (RD4043.042)
43.3
25
32
E9
OT
-
-
3
120/1
4.41
-
50
1 3/8
1 1/8
7/8
NOTES:
1.) Owner's designated refrigeration equipment manufacturer: HILL PHOENIX
2.) Furnish with time clock for defrost control, installed inside condensing unit.
3.) Furnish with thermostat and solenoid for temperature control.
4.) RCU-1 AND ALL COMPONENTS ARE NEW
NOTES:
1.) Owner's designated refrigeration equipment manufacturer: HILL PHOENIX
2.) Furnish with time clock for defrost control, installed inside condensing unit.
3.) Furnish with thermostat and solenoid for temperature control.
4.) RCU-2 AND ALL COMPONENTS ARE NEW.
EXISTING CONDITIONS WERE TAKEN FROM
ORIGINAL DRAWINGS AND MAY NOT REFLECT
EXACT "AS -BUILT" CONDITIONS. CONTRACTOR
SHALL FIELD VERIFY ALL EXISTING CONDITIONS
PRIOR TO SUBMITTING FINAL BIDS. CONTRACTOR
SHALL CAREFULLY COORDINATE NEW WORK AND
DEMOLITION WITH ALL OTHER DISCIPLINES AND
EXISTING CONDITIONS.
EACH SUBCONTRACTOR IS RESPONSIBLE FOR HAVING
A THOROUGH KNOWLEDGE OF ALL DRAWINGS AND
SPECIFICATIONS IN THEIR RELATED FIELD. THE FAILURE
TO ACQUAINT THEMSELF WITH THIS KNOWLEDGE DOES
NOT RELIEVE THE RESPONSIBILITY OF PERFORMING
THE WORK PROPERLY. NO ADDITIONAL
COMPENSATION SHALL BE ALLOWED BECAUSE OF
CONDITIONS THAT OCCUR DUE TO FAILURE TO
FAMILIARIZE WORKERS WITH THIS KNOWLEDGE.
Lu
0
w 0~OK
ww
REFRIGERATION SCHEDULE
SYSTEM RCU
_2
3Z
� �o��0Z 3ZZcnog
w-zw~�waZ�rZ
z
Sat. Cond. Temp °F:
112
DESIGN DB IF:
97
EXTERIOR DRY BULB (DB) IF:
Z
97
O
Format:
Supercenter
Store#: 3705
a
System Type:
Condensing Unit
Primary Refrigerant:
R407a
Cond Design TD °F:
15
DESIGN WB IF:
66
Based on 5 yr Extreme DB-ASHRAE Pub.:
O
Year 2017
`
r
Proto Size:
Renovation
City/State: Yelm, WA
Consultant:
DCE
Evap. Superheat °F:
10
Liquid Temp
112
DESIGN INTERIOR DRY BULB OF:
75
EXTERIOR WET BULB (WB) OF:
m
O
65.5
ProtoCycle Date:
1/31/2020
Date Prepared 3/11/2020
Prepared by:
Alec Gauthier
Elevation ft:
300
Return Gas Temp °F:
50
DESIGN INTERIOR RH % :
55%
Based on 0.4% Monthly Max WB-ASHRAE Pub.:
Year 2017
CKT #
Case Fixture Length / Quantity
Walk -In Box Size
Case Model
Case/Coil Manuf.
Application
Evaporator
Model #
LSHX Y or N?
& Model #
WI Evaps
Evaporator
Coil TXV /
Distributor
Nozzle
Circuit
Load (MBH)
Evap
Temp (F)
Case/
Walk -In
Air Temp (F)
Liquid Line
Solenoid
Valve
Defrost
Type
Defrost Heaters
Fans
Lights
Amps
(120v)
Anti -Sweat
Amps
(120v)
Total Line
Length(ft)Suction
9
Horiz (in)
Suction Riser (in)
Liquid Line (in)
FT /# of Doors
2 Dr/4'
3 Dr/6'
4 Dr/8'
5 Dr/12'
L
W
H
Amps
Voltage
Amps
Voltage
RCU-2
32
FT
1
2
ON5DMX-NRG (RD4043.042)
HILL PHOENIX
M.D. Deli
43.9
28
31
E9
OT
-
-
1.87
120/1
0.4
-
50
1 3/8
1 1/8
7/8
NOTES:
1.) Owner's designated refrigeration equipment manufacturer: HILL PHOENIX
2.) Furnish with time clock for defrost control, installed inside condensing unit.
3.) Furnish with thermostat and solenoid for temperature control.
4.) RCU-2 AND ALL COMPONENTS ARE NEW.
EXISTING CONDITIONS WERE TAKEN FROM
ORIGINAL DRAWINGS AND MAY NOT REFLECT
EXACT "AS -BUILT" CONDITIONS. CONTRACTOR
SHALL FIELD VERIFY ALL EXISTING CONDITIONS
PRIOR TO SUBMITTING FINAL BIDS. CONTRACTOR
SHALL CAREFULLY COORDINATE NEW WORK AND
DEMOLITION WITH ALL OTHER DISCIPLINES AND
EXISTING CONDITIONS.
EACH SUBCONTRACTOR IS RESPONSIBLE FOR HAVING
A THOROUGH KNOWLEDGE OF ALL DRAWINGS AND
SPECIFICATIONS IN THEIR RELATED FIELD. THE FAILURE
TO ACQUAINT THEMSELF WITH THIS KNOWLEDGE DOES
NOT RELIEVE THE RESPONSIBILITY OF PERFORMING
THE WORK PROPERLY. NO ADDITIONAL
COMPENSATION SHALL BE ALLOWED BECAUSE OF
CONDITIONS THAT OCCUR DUE TO FAILURE TO
FAMILIARIZE WORKERS WITH THIS KNOWLEDGE.
Lu
0
w 0~OK
ww
Cn
FSO
� LL
O zu v
0Z
Z)
W
3Z
� �o��0Z 3ZZcnog
w-zw~�waZ�rZ
z
Qr �SQEW, 000�w0
O
WwEWzoow
ww ro¢JCwW<W,M
L L
CL
(~°Z (% QOF 0=UU FAQ
Z
U)
¢0opNW¢ rwWWW2
O
�`-=o wNz)oZzU)IZF- Z
Ow? ¢�=Ww�E¢=000¢
F_
ZvaiN 0 LL0 O~¢U¢w
a
¢ ao o Oo5ZL,!
2ZJUVJWWOOX>
0
J
D
02 FO¢-2�DZ W'W -j
W J Z F F 0 F< a W W D F W
W
r�>WO00u=ia0WX�lylY¢r
0 O
00
0
N
ch
[7
PROTO:
176
z
_Z
/y j N
N N
DOCUMENT DATE: 03/11/2020
I.r
W o
T
Z
W a
I
G �
Z p W
U)
Q
Q N
c 00
Z
c
Z m 3 N
W06
= 3 0
N
J
D
�
L) o
U)
13 U d
Z
O
O
0 O
00
Z
0
��n
V
N
ch
LU
J
Z
D
CO
of
w
a
U)
PROTO:
176
z
L6
DOCUMENT DATE: 03/11/2020
O
T
Z
O
C'7
U)
Q
(j
z
W
0
J
OLr)U)
M
00
o
LU
rn
0
`
r
N
w
m
Z
m
O
ISSUE BLOCK
CHECKED BY:
KK
DRAWN BY:
AG
PROTO:
176
PROTO CYCLE:
013120
DOCUMENT DATE: 03/11/2020
41741
O� �EGISTER��\��
FSSIONA� EN
03/11/2020
DOCUMENTS THAT DO NOT
HAVE THE ARCHITECT OR
ENGINEER OF RECORD
SEAL AND SIGNATURE
SHALL BE CONSIDERED
NOT FOR CONSTRUCTION
REFRIGERATION
SCHEDULES
SHEET:
R3