2020.0103.BPP0008 3740 - R4 REFRIGERATION DETAILS - 3705 COPYRUN CONDUIT ON UNISTRUT AS NEEDED UNISTRUT P-1000 (TYP.) SIDE VIEW SECTION VIEW REFRIGERATION PIPING SUPP 10 NTS INVERTED SUCTION TRAP AT TOP OF RISER. (TYP.) LIQUID LINE (TYP.) SUCTION LINE (TYP.) REFRIGERANT SUCTION LINES SPACED 8" O.C. MOUNTED ON UNISTRUT INTERMEDIATE SUCTION LINE TRAP IN WALL, VOID SPACE, OR HIDDEN FROM VIEW. INTERMEDIATE TRAP SHOULD BE PLACED AT THE MIDPOINT OF ANY SUCTION LINE RISE WHICH EXCEEDS 16 FEET. CUSH-A-CLAMP FIRMLY CLAMPED TO PIPE (TYP) REFRIGERATION PIPING (TYP) DURA-BLOK DB6-SERIES OR EQUIVALENT CHANNEL SUPPORT. (TYP) SUPPORT PIPING AT 6'-0" MAXIMUM ON CENTERS, 2'-0" FROM ANY ELBOW. DO NOT ATTACH BLOCK TO ROOF ROOF MEMBRANE ORTtON ROOF) ROOF MOUNTED REFRIGERATION UNIT ROOFCURB ELECTRICAL CONDUITS MOUNTED ON UNISTRUT REFRIGERATION SUCTION LINES SPACED 8" OC MOUNTED ON UNISTRUT (TYP.) DO NOT ATTACH UNISTRUT TO CASE REFRIGERATED CASE (TYP) TS TO FLOOR ONLY LINE RACKING BEHIND REFRIGERATED CASES NTS - PIPE SUPPORT. REF HORIZONTAL $ $ a REFRIGERANT LINE SUPPORT DETAIL SUPPORT ROD TYP kK 2'-0" WIDE, 18 GAUGE SHEET METAL DRAIN PAN WITH INTERNAL MASTIC COATING PITCH PVC DRAIN LINE 1" PER 10 FT AND TERMINATE OVER DRAIN OR SERVICE SINK WITH 2" AIR GAP CONDENSATE DRAIN PAN 6 NTS SUCTION LINE TRAP AT THE BASE OF THERISER AT ALL POINTS WHERE SUCTION LINES RISES. INTERMEDIATE SUCTION LINE TRAP DETAIL 7 NTS LIQUID LINE SUCTION LINE ADJUST LOCATION OF DROPS AS REQUIRED. (TYP) PROVIDE TRAP AT BASE. (TYP) WHERE APPLICABLE, INSTALL LIQUID LINE SOLENOID, EVAPORATOR PRESSURE REGULATOR, AND FULL PORT ISOLATION BALL VALVES ON TOP OF CASE. PROVIDE VALVE LOCATION IDENTIFICATION TAG OF ENGRAVED PLASTIC. REFER TO SPECIFICATIONS. PROVIDE 26 GAUGE SHEET METAL DRIP PAN WITH MASTIC COATING WHERE APPLICABLE: REAR HALF OF REFRIGERATED CASE DESIGNATED FOR PIPING AND VALVES. FRONT HALF OF REFRIGERATED CASE DESIGNATED FOR ELECTRICAL AND EMS (TOP OF CASE) COMPONENTS. 1" EXPANDED POLYSTYRENE OR EQUAL. 6" MINIMUM WIDTH. LENGTH AS REQUIRED. REFRIGERATION PIPE ROUTING FOR TOP FED CASES 3 NTS ROUTE SUPPLY AND RETURN HEADERS ON TOP OF CASES WHERE POSSIBLE. REFRIGERATED CASE MANUFACTURER TO PROVIDED TOP CONNECTED CASES. ACE AT 4' INTERVALS. (TYP.) FRONT OF REFRIGERATED CASE. VALANCE FURNISHED BY CASE MANUFACTURER, INSTALLED BY REFRIGERATION CONTRACTOR. LIQUID LINE (TYPICAL INVERTEI LINE TRA SUCTION (TYPICAL CLEANEE PIPING A TO THE E REF ARC INTERME TRAPIN\ INTERME BE PLACI OF ANY WHICH E REFRIGE CASE (TY AT i TYPICAL SUCTION LINE ELEVATION .020" THICK PVC JACKET FOR ALL nrrni�rnnrir�ni i inirc� rvrrni�n BOLT WALL OR BUILDING STRUCTU v.Wrvviro r%iw %.vvE--rx vv i n INSULATION IN A CLEAN AND WORKMAN LIKE MANNER. #022 CUSH-A-CLAMP FIRMLY CLAMPED TO PIPE (TYPICAL) — 1 5/8"x1 5/8" GALVANIZED UNISTRUT P-1000, 10'-0" MAXIMUM ON CENTERS NOTE: MAINTAIN TIGHT SPACING BETWEEN PIPING VERTICAL REFRIGERANT LINE SUPPORT NTS MANUFACTURED METAL — — — CURB, INSULATION AND— SHEET METAL ENCLOSURE. REF ARCHITECTURAL PLANS IIII IIII IIII PIPE SUPPORT REF HORIZONTAL REFRIGERANT LINE SUPPORT DETAIL -0" MAX. ROOF PENETRATION NTS SUPPORT PIPING ON ROOF FOR ADEQUATE SLOPE AND SPACING. ROOF OPENING TO ACCOMMODATE BOTH REFRIGERATION PIPING AND ELECTRICAL CONDUIT TOP CHORD OF JOIST NOTE: LOCATE REFRIGERATED CHASE(S) UNIFORMLY TO AVOID EXISTING LIGHTING, 3 TOP BEAM ROOF 3 SKYLIGHTS, PIPING, CONDUIT, SPRINKLERS AND DUCTWORK. COORDINATE FINAL MAX CLAMP (TYP.) MAX LOCATION WITH WALMART MECHANICAL CONSTRUCTION MANAGER. SINGLE SYSTEM INTERMEDIATE SUCTION LINE TRAP = - 5 NTS = LOADS MUST BE C HUNG WITHIN 3" ZXRODTYP OF PANEL POINTS PROVIDE SHEET METAL ACCESS ENCLOSURE FOR UNITIZED CASES. PVC R NTS SUSPENSION SYSTEM TO -i STRUCTURE; TERMINATE IN A J MANNER 6" BELOW TOP OF HASE ISTRUT SPAN HORIZONTALLY EEN BAR JOISTS ISTRUT VERTICALLY TO SUPPORT HASE P PVC TO VERTICAL UNISTRUT WHITE PVC CHASE CLEAN TO REMOVE ALL MARKINGS REF PLAN FOR LOCATION AND SIZE DUCT FLANGE RIGERATED CASE CLOSURE PANEL/TOP OF RIGERATED CHASE SUPPLIED BY VENDOR IT FOR UNITIZED CASES) REFRIGERATED CASE EFRIGERATION CHASE 1/2" RETAINING NUT, UNSISTRUT P401 OT 1/2" CHANNEL NUT WITH SPRING, UNISTRUT P101 HORIZO 1 NTS /—OF STORUOCTURE\\ // INSUGUARD OR COOPER B -LINE SNAP N' SHIELD PIPE SADDLE SECURED TO UNISTRUT. MATCH COLOR OF INSULATION. (TYP)- PIPING INSULATION �f- - -_ - ��' ----- 7 -------- ��- ----- 7 -- 1- - - k - NOTE: FOR OVERHEAD LINES, UNISTRUT HORIZONTAL, TRAPEZE HUNG 1 5/8"x1 5/8" GALVANIZED UNISTRUT P-1000, 6'-0" MAXIMUM ON CENTERS, 2'-0" MAXIMUM FROM ANY ELBOW. NTAL REFRIGERANT LINE SUPPORT DETAIL EACH SUBCONTRACTOR IS RESPONSIBLE FOR HAVING A THOROUGH KNOWLEDGE OF ALL DRAWINGS AND SPECIFICATIONS IN THEIR RELATED FIELD. THE FAILURE TO ACQUAINT THEMSELF WITH THIS KNOWLEDGE DOES NOT RELIEVE THE RESPONSIBILITY OF PERFORMING THE WORK PROPERLY. NO ADDITIONAL COMPENSATION SHALL BE ALLOWED BECAUSE OF CONDITIONS THAT OCCUR DUE TO FAILURE TO FAMILIARIZE WORKERS WITH THIS KNOWLEDGE. Lu 0 Ww2O~>1 N co a FDO ()Z7Z w � w~zwwaZ z QLLwWDWopo28 F � O d¢ ��o WwcoZo3w w rE< xa-w¢cnafm w �U)z U)ao�oIII a O `-)o WNDO cl) z Z gOWE 0M°U�a�¢�¢W a o0 wmw=Of a--Z&w°g J WZ FFO~O W di7iF W m r�>' a-¢¢lgrrr 00f)0 ¢ 00 C=) C=) 00 0 N co ED = a P ROTO: Z2 o z j N M W 8 DOCUMENT DATE: 03/11/2020 W ° o E°a = I wLa4 z cl) z c ? co Z « ; N H 06 5 3 0 W N J � Ll m 0 m 13 a z O U 00 C=) C=) 00 Z O V N co w J 0 Z D m w a P ROTO: � z 013120 DOCUMENT DATE: 03/11/2020 � = C) M Q W � �o J 1-- (n Lo M 0) o W C) 0 ` r N w m z m O ISSUE BLOCK CHECKED BY: KK DRAWN BY: AG P ROTO: 176 PROTO CYCLE: 013120 DOCUMENT DATE: 03/11/2020 03/11/2020 DOCUMENTS THAT DO NOT HAVE THE ARCHITECT OR ENGINEER OF RECORD SEAL AND SIGNATURE SHALL BE CONSIDERED NOT FOR CONSTRUCTION REFRIGERATION DETAILS SHEET: R4