2020.0103.BPP0008 4030 - E2 POWER PLAN - 3705BADBADE42E2.26E2.27E44E43REF GENERAL ELECTRICAL CONNECTIONS TO STRUCTURE DETAIL FOR GENERAL INFORMATION ON MAKING CONNECTIONS TO STRUCTURE.EXISTING TELEPOWER POLES: ALL EXISTING TELEPOWER POLES IN OPEN STRUCTURE AREAS THROUGHOUT THE STORE SHALL BE SECURED SIMILAR TO DETAIL 1-E3 WITH OPTION OF UTILIZING 2-1/2 INCH RIGID PVC SPLIT DUCT TYPE SLEEVE FROM PRIME CONDUIT MWE INC, VIKIMATIC, OR INNERDUCT. COORDINATE WORK WITH WALMART STORE MANAGER AND CONSTRUCTION MANAGER TO MINIMIZE DISRUPTIONS TO STORE OPERATION AND ANY EQUIPMENT SERVED BY EACH POWER POLE.SALESCONTROL BOX PROVIDED BY SIGN INSTALLER WITH FACTORY INSTALLED DISCONNECT SWITCH. VERIFY LOCATION WITH SIGN INSTALLER PRIOR TO INSTALLATIONREUSE EXISTING SIGNAGE CIRCUIT L2P-2 EXTENDCIRCUITRY AS REQUIRED TO NEW CONNECTIONS. REUSE ALL CONTROLS ASSOCIATED WITH THE CIRCUIT.EDC44E2.2EDC2ABCDEFGHIJ12345678910111213ROOFTOPREFRIGERATIONRACK AROOFTOPREFRIGERATIONRACK DROOFTOPREFRIGERATIONRACK BROOFTOPREFRIGERATIONRACK EPANELCHFAPANELCHFDPANELCHFBPANELCHFEPANELCHLROOFTOPREFRIGERATIONRACK FPANELCHFFROOFTOPREFRIGERATIONRACK CPANELCHFCEDC116.201PANELLVCPANELLHCPANEL L2UEXISTING UPSPANELLTS1VISION CENTER HAIRCAREEQUIPMENTROOMTENANTSPACEPHARMACYPANELLRXGARDEN CENTERPANELHGCPANELLGCPANEL H3BTRANSFORMERT3DPANEL L3DSTORAGETLEE2.25E2.22E2.23PANELLFSFOODTENANTIF ANY EXISTING EXTERIOR DOORS ARE TO BEREPAIRED/REPLACED BY GC, COORDINATE ALLDISRUPTIONS TO THE STORE'S SECURITYSYSTEM WITH THE STORE MANAGER.architecture2809 Ajax Avenue Suite 100Rogers Arkansas 72758Phone: 479.636.3545Fax: 479.636.1209+engineeringEngineer of RecordKeith Allen Williams, P.E.Washington License No. 43345SHEET:DRAWN BY:CHECKED BY:CONSULTANTSSTIPULATION FOR REUSEPROTO:JOB NUMBER:THIS DRAWING WAS PREPARED FOR USE ON A SPECIFIC SITE AT:CONTEMPORANEOUSLY WITH ITS ISSUE DATE ON AND IT IS NOT SUITABLE FOR USE ON A DIFFERENT PROJECT SITE OR AT A LATER TIME. USE OF THIS DRAWING FOR REFERENCE OR EXAMPLE ON ANOTHER PROJECT REQUIRES THE SERVICES OF PROPERLY LICENSED ARCHITECTS AND ENGINEERS. REPRODUCTION OF THIS DRAWING FOR REUSE ON ANOTHER PROJECT IS NOT AUTHORIZED AND MAY BE CONTRARY TO THE LAW.DOCUMENTS THAT DO NOT HAVE THE ARCHITECT OR ENGINEER OF RECORD SEAL AND SIGNATURE SHALL BE CONSIDERED NOT FOR CONSTRUCTIONDOCUMENT DATE:PROTO:PROTO CYCLE:17601-31-202003-11-2020E2POWER PLANBMSYELM, WASHINGTON2019.0835YELM, WASHINGTON03/11/2020STORE NO: 3705-232SUPKAWKEYNOTES16.201 EXTERIOR SIGN POWER: WHERE ELECTRICALCONNECTIONS FOR SIGNAGE OCCUR BELOWROOF LINE, MOUNT JUNCTION BOX(ES) TO WALLAT SIGN CONNECTION POINT AND PROVIDE 3/4"CONDUIT TO CONTROL BOX FOR LOW VOLTAGEWIRING (INSTALLED BY OTHERS). REFER TOARCHITECTURAL DRAWINGS FOR EXACT SIGNLOCATION(S) PRIOR TO INSTALLATION. WHEREELECTRICAL CONNECTIONS FOR SIGNAGEOCCUR ABOVE ROOF LINE, PROVIDE UNISTRUTTO MOUNT JUNCTION BOXES TO BACK SIDE OFPARAPET AND PROVIDE 3/4" CONDUIT TOCONTROL BOX FOR LOW VOLTAGE WIRING(INSTALLED BY OTHERS). PROVIDE ONLY ONEPENETRATION THROUGH THE ROOF. REFARCHITECTURAL EXTERIOR WALL SECTIONSAND SIGN ATTACHMENT FOR ROOF ANDPARAPET PENETRATION REQUIREMENTS. 1" = 20'-0" 1POWER PLAN1.2.3.4.A.B.C.5.A.B.C.TELEPOWER POLE(S): MOUNT JUNCTION BOX(ES) TO TOP SIDE OF BOTTOM CHORD OF BAR JOIST. INSTALL FURNISHED POWER POLE AND TERMINATE WIRING TO JUNCTION BOX. PROVIDE UNISTRUT SUPPORTS AND HARDWARE TO SECURE TELEPOWER POLE PLUMB TO BUILDING STRUCTURE. REF POWER POLE CONNECTION DETAIL.PROVIDE LIQUID-TIGHT FLEXIBLE METAL CONDUIT AND WIRING FROM DISCONNECT SWITCH OR JUNCTION BOX TO EQUIPMENT KNOCKOUT OR ELECTRICAL CONNECTION POINT.WHERE EQUIPMENT NAMEPLATE PROTECTIVE DEVICE RATING DIFFERS FROM SIZE PROVIDED, NOTIFY WALMART CONSTRUCTION MANAGER IMMEDIATELY TO COORDINATE RESOLUTION.ELECTRONIC FIRE PROTECTION/SECURITY ALARM BOXES AND CONDUITS SHOWN ON POWER PLANS SHALL BE PROVIDED UNDER THIS CONTRACT. IN ADDITION, UNLESS NOTED OTHERWISE, THE FOLLOWING GENERAL NOTES APPLY:ALL ALARM JUNCTION BOXES SHALL BE 4"X4"X2-1/8" MINIMUM.ALARM RACEWAYS SHALL BE 3/4" MINIMUM WITH PULL WIRE AND INSULATING BUSHINGS AT END OF VERTICAL RACEWAY RUN.VERTICAL RACEWAYS FROM ALARM BOXES SHALL BE EITHER CONCEALED INSIDE WALL OR SURFACE MOUNTED (TO MATCH JUNCTION BOX MOUNTING). ALL VERTICAL RUNS SHALL BE TURNED 90-DEGREES AT TOP SIDE OF BOTTOM CHORD OF BAR JOIST AND EXTENDED HORIZONTALLY TO A LOCATION ACCESSIBLE BY VERTICAL FLOOR TYPE LIFT.UPON COMPLETION OF ELECTRICAL INSTALLATION AND PRIOR TO ENERGIZING CIRCUIT:INSPECT WIRE AND CABLE FOR PHYSICAL DAMAGE.PERFORM CONTINUITY TEST.VERIFY PROPER PHASING CONNECTION TO ALL THREE PHASE MOTOR LOADS.GENERAL POWER NOTES07.26.19ISSUE BLOCK