2020.0103.BPP0008 4050 - E2.2 ENLARGED POWER PLANS - 3705JJJJJJJJJJJBADBADH10ETRETR16.775BRANCHCIRCUITRY-REF6E2.2BRANCHCIRCUITRY-REF6E2.2BRANCHCIRCUITRY-REF6E2.216.77516.775BREAKROOM16.492ELECTRICAL DEVICESAND UNUSEDCIRCUITRYELECTRICAL DEVICESAND UNUSEDCIRCUITRYELECTRICAL DEVICESAND UNUSEDCIRCUITRY16.49216.492PLUGMOLD PROCUREMENT:CONTRACTOR TO FURNISH AND INSTALLNEW PLUGMOLD AS SPECIFIED ON PLANS:CONTACT:REXELWILLIAM MARR(479) 751-7123william.marr@rexelusa.comBREAKROOM CABINETS, TECH BAR AND ISLAND ARE MODULAR. RECEPTACLES AND PLUGMOLD ARE INSTALLED AND PREWIRED BY MANUFACTURER. CIRCUITRY SHOWN FOR CLARITY. E.C. TO ROUTE PREWIRED WHIPS TO FINAL CONNECTION POINT AS REQUIRED AND MAKE FINAL CONNECTIONS.DEVICES IN MODULAR CABINETS ARE PREWIRED. E.C. TO ROUTE ELECTRICAL WHIPS THROUGH CHASE AT TOP OF CABINETS TO PREINSTALLED JUNCTION BOX AND MAKE FINAL CONNECTIONSFOUTLET BOX, RECEPTACLE AND ELECTRICAL WHIP PREINSTALLED BY CABINET MANUFACTURER+79"+66"MODULAR TECH BAREC TO PROVIDE JUNCTIONBOX AT +24" FOR CONNECTIONTO MODULAR TECH BAR,TYP OF 3.COFFEE MAKERMICROWAVES,GFI, TYP OF 3EC TO ROUTE CONDUITDOWN WALL AND MAKE FINALCONNECTIONS AT JUNCTINBOX PROVIDED BY MODULARCOUNTER MANUFACTURER.REF ARCH DRAWINGS.MODULARCABINETSFREEZERREFRIGERATORMODULAR ISLANDMODULARCABINETRY1E3E.C. TO MAKE FINAL CONNECTIONTO MODULAR COUNTER.PLUGMOLD S-20GB306TRGFI (STAINLESS STEEL) WITHMATCHING POWER FEED AND END FITTINGS PROVIDEDAND PREINSTALLED BY MODULAR COUNTERMANUFACTURER, TYP OF 2.H10ETR16.131L1D1-6916.145-L1D1 71-L1D1 2016.145-L1D1 2216.145L1D1-33,3516.14516.145-L1D1 2616.145-L1D1 28-L1D1 37-L1D1 68-L1D1 6716.14516.14516.14516.14516.14516.145-L1D1 14-L1D1 16-L1D1 18F F FFFF FF F F F16.508FFFFF FMODULAR TECH BARMODULAR TECH BAR16.410BTYP OF 2BREAKROOMGFIGFIGFIC23-L4D2 73,75,7716.145(40A-3P)#8W-L4D2 79,81,8316.477(20A-3P)-L4D2 6416.470D007GFI, MOUNT TOBASE OF CASE,TYP OF 3RELOCATED SCALES.PROVIDE LOW VOLTAGEROUGH-IN AS REQUIRED,TYP OF 3.RH0135 - 8'RH0122 - 4'5351,53D007D007L4D2-49,51,5316.145-L4D2 66,6816.475BD102PROVIDE NEUTRALWIRE WITH CIRCUIT19' - 6"13' - 1"RD9009 - 8'ROUTE CABLE THROUGH TOPOF ACCESS PANEL ON SIDE OFCASE. MAKE FINALCONNECTIONS WITHIN BASE.4E3-L4D2 70,7216.472(20A-2P)PRODUCE SALESSERVICE DELIROUTE FLEXIBLE CONDUIT UNDER CASES TO MINIMIZE VISIBILITY, TYP.(RELOCATED)(RELOCATED)D005D005(RELOCATED)57L4D2-47,57EXISTING TELEPOWER POLES: EXISTING TELEPOWER POLES IN OPENSTRUCTURE AREAS SHALL BE SECURED SIMILAR TO DETAIL WITHOPTION OF UTILIZING 2-1/2 INCH RIGID PVC SPLIT DUCT TYPE SLEEVEFROM PRIME CONDUIT MWE INC, VIKIMATIC, OR INNERDUCT.COORDINATE WORK WITH WALMART STORE MANAGER ANDCONSTRUCTION MANAGER TO MINIMIZE DISRUPTIONS TO STOREOPERATIONS AND ANY EQUIPMENT SERVED BY EACH POWER POLE.PROVIDE LISTED HANDLE-TIE BETWEEN CIRCUIT BREAKERS SHARING COMMON NEUTRAL FOR SIMULTANEOUS TRIP.L2P-10ETR01AMGH,PD2MOUNT TO BASE OF DISPLAYUNIT. ROUTE 3/4" CONDUIT TOSTRUCTURE AT THE SAMELOCATION AS THE POWER DROP-1E3EXISTING CHECKOUTS IN THIS AREA TO REMAINPOWER ZONE 1C45678EXISTING CHECKOUTS IN THIS AREA TO REMAIN16.492CHECKOUT9' - 1"19' - 6"B16.492TOUCHLESS SINKCIRUCITRYCUSTOMERWOMENCUSTOMERMENH9CUSTOMERWOMENCUSTOMERMEN16.49216.492TOUCHLESS SINKCIRCUITRYTOUCHLESS SINKCIRCUITRYH16.470L1D3-29BIKE ASSEMBLY DESKMOUNT TO RACK FOR BIKE ASSEMBLY, +48".VERIFY LOCATION WITH STORESUPERVISOR PRIOR TO ROUGH-IN, TYP OF 4.architecture2809 Ajax Avenue Suite 100Rogers Arkansas 72758Phone: 479.636.3545Fax: 479.636.1209+engineeringEngineer of RecordKeith Allen Williams, P.E.Washington License No. 43345SHEET:DRAWN BY:CHECKED BY:CONSULTANTSSTIPULATION FOR REUSEPROTO:JOB NUMBER:THIS DRAWING WAS PREPARED FOR USE ON A SPECIFIC SITE AT:CONTEMPORANEOUSLY WITH ITS ISSUE DATE ON AND IT IS NOT SUITABLE FOR USE ON A DIFFERENT PROJECT SITE OR AT A LATER TIME. USE OF THIS DRAWING FOR REFERENCE OR EXAMPLE ON ANOTHER PROJECT REQUIRES THE SERVICES OF PROPERLY LICENSED ARCHITECTS AND ENGINEERS. REPRODUCTION OF THIS DRAWING FOR REUSE ON ANOTHER PROJECT IS NOT AUTHORIZED AND MAY BE CONTRARY TO THE LAW.DOCUMENTS THAT DO NOT HAVE THE ARCHITECT OR ENGINEER OF RECORD SEAL AND SIGNATURE SHALL BE CONSIDERED NOT FOR CONSTRUCTIONDOCUMENT DATE:PROTO:PROTO CYCLE:17601-31-202003-11-2020E2.2ENLARGEDPOWER PLANSBMSYELM, WASHINGTON2019.0835YELM, WASHINGTON03/11/2020STORE NO: 3705-232SUPKAW 1/8" = 1'-0" 4BREAKROOM DEMO POWER PLAN 1/4" = 1'-0" 6BREAKROOM POWER PLAN 1/8" = 1'-0" 7FRONT GROCERY POWER PLANA.B.C.D.E.F.G.H.I.J.K.L.PROVIDE CORROSION RESISTANT PLUG, CONNECTOR, AND WEATHERPROOF BOOTS. CONNECTOR AND WEATHERBOOTS SHALL BE FROM THE SAME MANUFACTURER.PROVIDE MATCHING CORD AND MALE PLUG.WIRING DEVICE ON DROP CORD FROM CEILING. REFER TO SUSPENDED DROP CORD DETAILS.WIRING DEVICE CIRCUITED TO SHUNT-TRIP BREAKER.PROVIDE WEATHERTIGHT FLEX CONDUIT AND WIRING FROM DISCONNECT SWITCH OR JUNCTION BOX TO EQUIPMENT KNOCKOUT OR ELECTRICAL CONNECTION POINT.MAKE FINAL CONNECTIONS TO EQUIPMENT.PROVIDE CORROSION PROOF PLUGS AND RECEPTACLES FOR EQUIPMENT SPECIFIED ON ELECTRICAL EQUIPMENT SCHEDULE NOTES.VERIFY EXACT POINT(S) OF CONNECTION(S) AND FIELD WIRING REQUIREMENTS WITH EQUIPMENT INSTALLER.IF NOT FURNISHED WITH EQUIPMENT, FURNISH AND INSTALL 6'-0" LONG SJO CORD WITH GROUNDING CONDUCTOR, SIZED AS FOLLOWS:5 CONDUCTORS: #8W.(28A), #10W.(20A), #12W.(16A), #14W.(12A). 4 CONDUCTORS: #4,(60A), #8W.(35A), #10W.(25A), #12W.(20A), #14W.(15A).3 CONDUCTORS: #8W.(40A), #10W.(30A), #12W.(25A), #14W.(18A). FURNISH AND INSTALL GROUNDING TYPE ATTACHMENT CAPSEE ELECTRICAL SPECIFICATIONS FOR RECEPTACLE, CONNECTOR, AND PLUG INFORMATION. PROVIDE AS REQUIRED.CORD AND PLUG FURNISHED WITH EQUIPMENT.FAN CONNECTED THROUGH 120V RELAY, 10A MAXKITCHEN DEVICE SCHEDULENUMBERDESCRIPTIONMANUFACTURER MODEL VOLT/PHASE AMPSTERMINATION MTG. HT. NOTESDELI EQUIPMENT SCHEDULED005WRAPPER(RELOCATED)EXISTINGEXISTINGEXISTING8.00 A WP GFI DUPLEX, NEMA: 5-20R44"JD007SLICER(RELOCATED)EXISTINGEXISTINGEXISTING3.50 A GFI DUPLEX, NEMA: 5-20R44"KD102BLAST CHILLERTRAULSENTBC-13208/120/116.00 A WP, RECEPTACLE, NEMA: L14-20R20"KREFRIGERATED AND HOT CASE SCHEDULERD9009 - 8'ISLAND MERCHANDISERSTRUCTURAL CONCEPTS MI48R208/212.20 A NEMA 6-20R x230"C, KRH0122 - 4'4' HOT DELI SELF-SERVICE MULTI-DECK CUSTOM DELI'SDILW-SS120/208/310.00 A WP JUNCTION BOX12"E,FRH0135 - 8'8' HOT DELI SELF-SERVICE MULTI-DECK CUSTOM DELI'SILW-CB-SS120/208/326.00 A WP JUNCTION BOX12"E,F 1/8" = 1'-0" 1FRONT CHECKOUT AREA POWER PLAN 1/8" = 1'-0" 2FRONT RESTROOM POWER PLAN 1/8" = 1'-0" 3REAR RESTROOM POWER PLAN 1/4" = 1'-0" 5BIKE ASSEMBLYDESK POWER PLANKEYNOTES16.131 CONNECT TO EXISTING CIRCUIT.16.145 CONNECT CIRCUIT(S) TO EXISTING BRANCHCIRCUITRY. MINIMUM WIRE SIZE ANDPANELBOARD CIRCUIT ARE NOTED. VERIFY SIZE,RATING AND CONDITION OF EXISTING BRANCHCIRCUIT CONDUIT AND WIRE PRIOR TO USE TOENSURE THAT THEY MEET REQUIRED SIZE, ANDALL U.L. RATINGS AND REPLACE AS REQUIRED.16.410B COUNTER MOUNTED DEVICES: ROUTE BRANCHCIRCUITRY THROUGH OWNER FURNISHED BLANKPOWER POLE. ROUTE FLEXIBLE METALCONDUITS ALONG INSIDE BACK WALL OFCABINET.16.470 FURNISH AND INSTALL NEW 20 AMP, 120 VOLTCIRCUIT(S). FEED FROM PANELBOARD ASINDICATED. PROVIDE 20A-1P CIRCUIT BREAKERIF NEEDED. E.C. SHALL MATCH MANUFACTURER,TYPE AND AIC RATINGS OF EXISTING CIRCUITBREAKERS.16.472 FURNISH AND INSTALL NEW CIRCUIT BREAKER(##A-#P) IN EXISTING PANELBOARD INDICATED.E.C. SHALL MATCH MANUFACTURER, TYPE ANDAIC RATINGS OF EXISTING CIRCUIT BREAKERS.16.475B PROVIDE 20A-2P 5mA GFCI CIRCUIT BREAKERFOR PERSONNEL PROTECTION. E.C. SHALLMATCH MANUFACTURER, TYPE AND AIC RATINGSOF EXISTING CIRCUIT BREAKERS.16.477 FURNISH AND INSTALL NEW CIRCUIT BREAKER(##A-#P) IN EXISTING PANELBOARD INDICATED.PROVIDE CIRCUIT BREAKER LOCKING DEVICE(LOCK-OFF FOR MAINTENANCE). E.C. SHALLMATCH MANUFACTURER, TYPE AND AIC RATINGSOF EXISTING CIRCUIT BREAKERS.16.492 E.C. SHALL COORDINATE WITH GENERALCONTRACTOR AND ARCHITECTURALDEMOLITION PLANS THE EXTENT OF ELECTRICALDEMOLITION. REMOVE UNUSED DEVICES,BOXES, CONDUITS, AND WIRING BACK TOORIGINATING JUNCTION BOXES ORPANELBOARDS. REFERENCE POWER PLANS FORCIRCUITRY TO BE REUSED. DEMOLITION SHALLNOT AFFECT ACTIVE CIRCUITS. IF CIRCUIT ISDEMOLISHED ALL THE WAY TO PANELBOARD,REMOVE CIRCUIT BREAKER AND REPLACE WITHFILLER PLATER. UPDATE TYPEWRITTEN CIRCUITDIRECTORY IDENTIFYING CIRCUIT AS "SPACE".COORDINATE EXACT REQUIREMENTS WITHEXISTING CONDITIONS PRIOR TO BID.16.508 INSECT CONTROL: PROVIDE BROWN DEVICE ANDMATCHING COVERPLATE.16.775 E.C. SHALL DISCONNECT, EXTEND, ANDRECONNECT ALL ELECTRICAL CIRCUITRY FORNEW OR RELOCATED EQUIPMENT. REFERENCEPOWER PLANS AS APPLICABLE. VERIFYCONDITION OF BRANCH CIRCUIT, CONDUIT, ANDWIRE PRIOR TO USE TO ENSURE THAT THEYMEET ALL U.L. RATINGS AND REPLACE ASREQUIRED. COORDINATE THIS PROCESS WITHCONSTRUCTION MANAGER TO MINIMIZEDOWNTIME. LABEL ALL ASSOCIATEDPANELBOARD SCHEDULES TO REFLECT LOADDESCRIPTIONS.DESCRIPTIONMOUNT RECEPTACLE(S) ON TOP OF DISPLAY UNIT(S)MOUNT RECEPTACLE(S) 6" ABOVE BASE OF DISPLAY ON UNIT(S) SO THAT RECEPTACLE(S) AND CONDUIT DO NOT INTERFERE WITH SHELF HEIGHT ADJUSTMENTSPROVIDE DIRECT CONNECTION TO EQUIPMENTOPEN STRUCTURE: MOUNT RECEPTACLE AT BAR JOIST AND INSTALL FURNISHED CORD REEL.LAY-IN CEILING: PROVIDE RECESSED CEILING RECEPTACLE AND INSTALL FURNISHED CORD REEL BELOW CEILING. CORD REEL SHALL BE MOUNTED TO CEILING FAN RATED JUNCTION BOX SECURED TO LAY-IN CEILING WITH T-BAR BOX HANGER. PROVIDE 1/2" THREADED STEEL ROD FROM JUNCTION BOX TO BOTTOM OF STRUCTURAL JOIST OR CHANNEL STRUT BRIDGING ABOVE FOR SUPPORT.POWER DROP SCHEDULE07.28.17NO.PD1PD2PD3PD4POWER DROP NOTES07.26.191.2.A.B.C.3.4.5.6.POWER DROPS WILL BE IDENTIFIED BY AN IPTV TAG OR POWER TAG, I.E. 44A, 46E, ETC. ALL CHECKOUT POWER SHALL BE CONSIDERED POWER DROPS.A REVISION OF THIS PLAN BASED ON THE FINAL MERCHANDISE LAYOUT MAY BE ISSUED TO SHOW FINAL LOCATIONS FOR THE POWER DROPS. IF THE MERCHANDISE PLAN DOES NOT CHANGE, THIS PLAN WILL NOT BE REISSUED. PROVIDE CIRCUITRY TO DISPLAY RACKS AS THE RACKS ARE SET. IN ADDITION, THE FOLLOWING POWER DROP NOTES APPLY:THERE WILL BE NO ADDITIONAL CHARGE FOR DROP RELOCATION WITHIN POWER DROP ZONES DEFINED ON DRAWING.AT CLOSE OF PROJECT THE GENERAL CONTRACTOR AND CONSTRUCTION MANAGER SHALL REVIEW ADDITIONAL OR DELETED POWER DROPS WITHIN EACH ZONE TO VERIFY ANY ADDITIONAL CHARGES OR CREDITS THAT APPLY DUE TO CHANGES.ADDING OR SUBTRACTING A POWER DROP TO ANY ZONE WILL RESULT IN A CHARGE OR CREDIT ACCORDING TO SPECIAL CONDITIONS.PROVIDE JUNCTION BOX AND CIRCUITRY TO NEAREST JOIST ABOVE LOCATION SHOWN ON DRAWING. EXTEND CONDUIT AND CIRCUITRY FROM JUNCTION BOX TO ENDCAP OF DISPLAY RACK.WHEN EXPOSED VERTICAL CONDUIT FROM STRUCTURAL CONNECTION TO GONDOLA EXCEEDS 10 FEET, INTERMEDIATE METALLIC CONDUIT (IMC) SHALL BE USED IN LIEU OF ELECTRICAL METALLIC CONDUIT (EMT). THE IMC CONDUIT AND COUPLINGS SHALL BE THREADED AND BE SECURELY FASTENED AT THE GONDOLA AND AT STRUCTURE.PROVIDE CONDUIT, RECEPTACLE(S) AND FINAL CONNECTIONS AT DISPLAY RACK SHELVING PER POWER DROP SCHEDULE UNLESS NOTED OTHERWISE ON DRAWING. VERIFY EXACT HEIGHT AND LOCATION OF RECEPTACLE(S) WITH STORE PLANNING SET-UP SUPERVISOR PRIOR TO INSTALLATION.POWER DROPS FED FROM TRACK BUSWAY:INSTALL PLUG-IN UNIT AT A POINT ON TRACK BUSWAY NEAREST POWER DROP(S).ISSUE BLOCK