2020.0103.BPP0008 4070 - E4 ELECTRICAL ONE-LINE DETAILS AND SCHEDULES - 3705CONNECTED LOADS TABLELOAD BREAKDOWNLOAD*NECDEMANDTOTAL KVA TOTAL AMPSHEATING/COOLING (DOMINANT LOAD ONLY)0.00 1.00 0.00 KVA 0.00 ALIGHTING2.51 1.25 3.14 KVA 3.78 ARECEPTACLES14.46 1.0 / 0.5 12.23 KVA 14.71 AKITCHEN EQUIPMENT24.33 1.00 24.33 KVA 29.27 AREFRIGERATION / MISCELLANEOUS1.92 1.00 1.92 KVA 2.31 ACONTINUOUS0.00 1.25 0.00 KVA 0.00 ALARGEST MOTOR LOAD0.00 1.25 0.00 KVA 0.00 AMOTOR LOADS0.00 1.00 0.00 KVA 0.00 AEXISTING LOAD TO BE DELETED22.08 1.00 22.08 KVA 26.56 A**EXISTING PEAK DEMAND613.2 1.25 766.50 KVA 921.98 A***TOTAL - - - - - - 786.05 KVA 945.49 ASERVICE ENTRANCE CAPACITY3325.44 KVA 4000.00 ASPARE SERVICE CAPACITY2539.39 KVA 3054.51 A* IN ACCORDANCE WITH NEC 220-35 (FOR INFORMATION ONLY)** PEAK DEMAND BASED ON 12 MONTH DEMAND HISTORY FROM OWNER*** POWER COMPANY SHALL APPLY PROPER DEMAND FACTORS TO CALCULATE NEWESTIMATED TOTAL MAXIMUM DEMANDUTILITY TRANSFORMER480Y/277V, 3P, 4W SEC(EXISTING)IF IT IS NECESSARY TO REMOVE A METER, RTU SERVER, CT OR DISRUPT THE COMMUNICATION OF THE SYSTEM, THE CONTRACTOR IS RESPONSIBLE TO RESTORE THE SYSTEM TO THE SAME LEVEL OF OPERATION THAT EXISTED PRIOR TO THE WORK BEING INITIATED. THE EXISTENCE AND FUNCTIONALITY OF THE SYSTEM SHALL BE VERIFIED BY CALLING WALMART BUILDING PERFORMANCE TEAM AT 479-204-0432 BETWEEN THE HOURS OF 7 AM UNTIL 5 PM CT.MSB - 4000 AMP BUS - 480/277V, 3PH, 4W (EXISTING)600A3PA-1L-O"QC" BREAKERSHUNT TRIPGFRST1600A -3P MAIN1600A -3P MAIN800A3P400A3P600A3P300A3P600A3PA|1L-OSHUNT TRIPGFRSTBREAKER4000A -3P MAINEXISTING DISTRIBUTION SYSTEM IS SERIES RATED. E.C. SHALL PROVIDE CIRCUIT BREAKER(S) THAT WILL MAINTAIN EXISTING MANUFACTURER'S U.L. LISTED SERIES RATED SYSTEM.KWH"QC" BREAKER SECTIONMAIN BREAKER SECTIONDISTRIBUTION SECTION500A3PCT CABINETBY CONTRACTORCTEXISTPNLBDH1A480VEXISTPNLBDH1B480/277VEXISTPNLBDH1P1480/277VEXISTPNLBDH1P2480/277VT1D150KVA480V-208Y/120V(EXISTING)T1D325KVA480V-240/120V(EXISTING)150A2PEXISTINGEXISTPNLBDL1D3240/120VEXISTPNLBDL1D1208/120VEXISTPNLBDL1D2208/120VEXISTPNLBDL1U240/120VEXISTUPSSYSTEMUPS ROOMEDC1EXISTPNLBDH2B480/277VEXISTPNLBDH2A480VEXISTPNLBDH2P480/277VEXISTPNLBDL2P208/120VEXISTPNLBDL2D1208/120VEXISTPNLBDL2B208/120VEXISTPNLBDLVC208/120VVISIONCENTEREXISTPNLBDLRX208/120VPHARMACYEXISTPNLBDLHC208/120VHAIRCAREEXISTPNLBDLTS1208/120VTENANTEXISTPNLBDL2D3208/120VEDC2EXISTPNLBDL2D2208/120VEQUIPMENTROOMEXISTPNLBDL2U240/120VEXISTUPSSYSTEMEXISTPNLBDH3B480/277VT3D112.5KVA480V-208Y/120V(EXISTING)EXISTPNLBDL3D208/120VT2D225KVA480V-208Y/120V(EXISTING)175A3PEXISTINGEXISTPNLBDLGC208/120VEXISTPNLBDHGC480/277VGARDEN CENTER400A3PEXISTPNLBDH4B1480/277VEXISTPNLBDH4B2480VEXISTPNLBDH4B3480VEXISTPNLBDH4C480/277VT4D150KVA480V-208Y/120V(EXISTING)TFS75KVA480V-208Y/120V(EXISTING)225A3PEXISTINGEXISTPNLBDL4D1208/120VEXISTPNLBDL4D2208/120VEDC4EXISTDIESELGENERATORTLE STORAGEKWHPLMEXISTPNLBDLFS208/120VFOOD TENANT200A, 3P200A, 3PEXISTFIREPUMPCTRLEXISTFIREPUMP100HPSPRINKLER ROOMI11MSB1MSB2MSB3EMS BACKBOARDTELEPHONEBOARDALARM BOARDH1BH1AH1P2H1P1T1DL1D1L1D2T1D3SPLL1UL1D322 20,22L1D3-18,20,2216.47521L1D3-19,2116.4757' - 2"4' - 2"4' - 2"4' - 2"4' - 2"B9T2DL2BL2D1/L2D2STACKEDL2D3/SPACESTACKEDL2PH2PH2BH2A1H4B3H4B2H4B1H4CTFS/T4DSTACKEDL4D2L4D1architecture2809 Ajax Avenue Suite 100Rogers Arkansas 72758Phone: 479.636.3545Fax: 479.636.1209+engineeringEngineer of RecordKeith Allen Williams, P.E.Washington License No. 43345SHEET:DRAWN BY:CHECKED BY:CONSULTANTSSTIPULATION FOR REUSEPROTO:JOB NUMBER:THIS DRAWING WAS PREPARED FOR USE ON A SPECIFIC SITE AT:CONTEMPORANEOUSLY WITH ITS ISSUE DATE ON AND IT IS NOT SUITABLE FOR USE ON A DIFFERENT PROJECT SITE OR AT A LATER TIME. USE OF THIS DRAWING FOR REFERENCE OR EXAMPLE ON ANOTHER PROJECT REQUIRES THE SERVICES OF PROPERLY LICENSED ARCHITECTS AND ENGINEERS. REPRODUCTION OF THIS DRAWING FOR REUSE ON ANOTHER PROJECT IS NOT AUTHORIZED AND MAY BE CONTRARY TO THE LAW.DOCUMENTS THAT DO NOT HAVE THE ARCHITECT OR ENGINEER OF RECORD SEAL AND SIGNATURE SHALL BE CONSIDERED NOT FOR CONSTRUCTIONDOCUMENT DATE:PROTO:PROTO CYCLE:17601-31-202003-11-2020E4ELECTRICALONE-LINEDETAILS ANDSCHEDULESBMSYELM, WASHINGTON2019.0835YELM, WASHINGTON03/11/2020STORE NO: 3705-232SUPKAWNTS1ONE-LINE DIAGRAMCOORDINATE ALL CHANGES TO EXISTING ELECTRICAL SERVICE AND METERING WITH UTILITY COMPANY.STORE ADDRESS: WALMART SUPERCENTER #3705 GENERAL REMODEL17100 WA-507YELM, WA, 98597UTILITY COMPANY: PUGET SOUND ENTERGYCONTACT:TRISHA STRILEMAIL:PATRICIA.STRIL@PSE.COMPHONE:(425) 766-2961ARC FLASH HAZARD WARNING LABELING REQUIREMENTS PER NEC ARE PROVIDED BY OWNER UNDER SEPARATE CONTRACT.ARC FLASHCOORDINATE ALL WORK THAT REQUIRES POWER INTERRUPTIONS TO THE STORE WITH THE STORE MANAGER AND THE WALMART CONSTRUCTION MANAGER A MINIMUM OF 48 HOURS IN ADVANCE OF ALL STORE POWER INTERRUPTIONS. IN ADDITION, IF THE MAIN ELECTRICAL SWITCHGEAR REQUIRES WORK AND DOES NOT HAVE A MAIN SERVICE DISCONNECTING MEANS, COORDINATE WITH THE UTILITY COMPANY A MINIMUM OF TWO WEEKS IN ADVANCE OF THE STORE POWER INTERRUPTION. IF STORE IS NOT OPEN 24 HOURS PER DAY, ALL STORE POWER INTERRUPTIONS ARE TO BE ACCOMPLISHED AFTER NORMAL STORE BUSINESS HOURS. PROVIDE TEMPORARY POWER AS REQUIRED PER SPECIFICATIONS. INSTALLATION OF NEW EQUIPMENT SHALL BE COMPLETED AND THE POWER SYSTEM TESTED AND RE-ENERGIZED PRIOR TO THE TIME ESTABLISHED BY THE STORE MANAGER AND THE WALMART CONSTRUCTION MANAGER.POWER INTERRUPTION NOTE11.30.18NOTE:ALL OF THE ELECTRICAL DEVICES SHOWN ON THE RISER DIAGRAM ARE EXISTING AND ARE BASED UPON AS-BUILT DRAWINGS. E.C. SHALL VERIFY THE EXACT EXISTING CONDITIONS, SIZES AND LOCATIONS OF EQUIPMENT PRIOR TO ROUGH-IN. THIS RISER IS SHOWN FOR INFORMATIONAL PURPOSES ONLY AND ANY NEW DEVICES ARE SHOWN IN BOLD AND ARE NOTED. DURING CONSTRUCTION, THE STORE SHALL STAY OPEN FOR BUSINESS. ANY NECESSARY POWER DOWNTIME SHALL BE SCHEDULED AND APPROVED BY WALMART CONSTRUCTION MANAGER.NEW EQUIPMENTEXISTING EQUIPMENTEQUIPMENT TO BE DEMOLISHEDONE-LINE DIAGRAM LEGEND11.19.101.2.3.4.5.6.7.8.9.10.11.12.13.14.15.16.17.18.19.20.21.22.1.2.3.4.TERMINATE GROUND ON ISOLATED GROUND BUS.INSTALL LOCKING DEVICE (LOCK-OFF FOR MAINTENANCE). LOCKING DEVICE SHALL BE UL LISTED. MANUFACTURER SHALL MATCH EXISTING PANELBOARD MANUFACTURER.INSTALL LOCKING DEVICE (LOCK-ON FOR CRITICAL LOAD).GFI BREAKER FOR PERSONNEL PROTECTION (5MA).GFI BREAKER FOR EQUIPMENT PROTECTION (30MA).CONDUCTOR SIZE HAS BEEN INCREASED FOR VOLTAGE DROP. SIZE EQUIPMENT GROUNDING CONDUCTOR PROPORTIONATELY PER NEC.REFER TO ONE-LINE DIAGRAM FOR AVAILABLE FAULT CURRENT FOR INTERRUPT RATINGS.REFER TO ONE-LINE DIAGRAMS FOR WIRE SIZES.FACTORY WIRED TO LOAD.BREAKER SHALL BE HIGH MAGNETIC TYPE.FIELD VERIFY BREAKER IS NOT CONNECTED TO ANY LOAD. REMOVE CIRCUIT BREAKER AND REPLACE WITH BLANK COVER. UPDATE TYPEWRITTEN CIRCUIT DIRECTORY IDENTIFYING CIRCUIT AS "SPACE". IF AN EXISTING LOAD IS CONNECTED, REFER TO PANELBOARD NOTE (22).DUAL TAP SOLENOID OPERATED BREAKER. CONNECT EMERGENCY/NIGHT LIGHTING TO UNSWITCHED TERMINATION.EXISTING CIRCUIT TO REMAIN.ROUTE CIRCUIT THROUGH CONTACTOR.PROVIDE INTERLOCK WIRING WITH EXHAUST HOOD ANSUL SYSTEM.RELOCATED CIRCUIT FROM EXISTING PANELBOARD.PROVIDE BLANK CIRCUIT BREAKER FILLER PLATE FOR EXPOSED SPACE IN PANELBOARD.PROVIDE U.L. LISTED OVERCURRENT DEVICE TO COORDINATE AND MAINTAIN MANUFACTURER'S SERIES RATED SYSTEM.EXISTING CIRCUIT BREAKER TO REMAIN. VERIFY CONDITION OF CIRCUIT BREAKER TO ENSURE THAT IT IS OPERATIONAL AND MEETS ALL U.L. RATINGS.ROUTE CIRCUIT THROUGH EXISTING LCU CABINET UTILIZING EXISTING RELAY AND CONTROLS. UPDATE LCU IDENTIFICATION SCHEDULE WITH LOAD IDENTIFICATION.SOLENOID OPERATED CIRCUIT BREAKER. REFER TO ENERGY MANAGEMENT PLANS FOR CIRCUIT BREAKER CONTROL.TRACE EXISTING CIRCUIT, IDENTIFY LOAD AND PROVIDE COMPLETE TYPEWRITTEN PANELBOARD IDENTIFICATION SCHEDULE AND PLACE ON INTERIOR OF PANELBOARD DOOR. IF CIRCUIT IS A "SPARE", REFER TO PANELBOARD NOTE (11).GENERAL NOTES:E.C. SHALL ADD OR REARRANCE CIRCUIT BREAKERS WITHIN PANELBOARDS AS REQUIRED TO MATCH NEW CIRCUIT DESIGNATIONS SHOWN ON DRAWINGS.NEW OVERCURRENT PROTECTIVE DEVICES PLACED IN EXISTING PANELBOARDS OR DISTRIBUTION BOARDS SHALL MATCH THE TYPE AND AIC RATING OF EXISTING OVERCURRENT PROTECTION DEVICES IN SAID BOARD.E.C. SHALL TRACE ALL ELECTRICAL CIRCUITS FOR ALL EXISTING ELECTRICAL PANELBOARDS AFFECTED BY THE REMODEL AND IDENTIFY LOADS ON EACH CIRCUIT. PROVIDE A COMPLETE TYPEWRITTEN PANELBOARD IDENTIFICATION SCHEDULE FOR ALL AFFECTED PANELBOARDS.ALL OVERCURRENT DEVICES ARE NEW UNLESS NOTED OTHERWISE.PANELBOARD NOTES ()07.26.1920A WIRE SIZING SCHEDULE385 FT.770 FT.930 FT.620 FT.1865 FT.255 FT.ALL WIRE SIZES SHOWN ON PANEL SCHEDULES ARE INTENDED TO BE MINIMUM ACCEPTABLE WIRE SIZE.THE FOLLOWING SCHEDULE IS TO BE USED TO SIZE WIRE FOR 20 AMP CIRCUITS (120 AND 277 VOLT). LENGHTS (IN FEET) ARE INTENDED TO BE MAXIMUM.6-10 AMPS1-5 AMPS120 VOLT11-15 AMPS6-10 AMPS1-5 AMPS277 VOLT11-15 AMPS#8#12#10380 FT.760 FT.250 FT.240 FT.480 FT.160 FT.585 FT.1170 FT.390 FT.325 FT.110 FT.160 FT.#12200 FT.70 FT.100 FT.490 FT.165 FT.245 FT.#10#8#6#6 1/4" = 1'-0" 2EDC1 ROOM POWER PLAN 1/4" = 1'-0" 3EDC2 POWER PLAN 1/4" = 1'-0" 4EDC4 POWER PLANISSUE BLOCKKEYNOTES16.475 FURNISH AND INSTALL NEW 20 AMP, 120 VOLTCIRCUIT(S). FEED FROM PANELBOARD ASINDICATED. PROVIDE 20A-1P 5mA GFCI CIRCUITBREAKER FOR PERSONNEL PROTECTION. E.C.SHALL MATCH MANUFACTURER, TYPE AND AICRATINGS OF EXISTING CIRCUIT BREAKERS.