2020.0015 Energy Credits Property# 22719331301Table 406.2
Energy Credits 2015 Code
OPTION
DESCRIPTION
CREDIT(S)
Estimated Cost
la
EFFICIENT BUILDING ENVELOPE I a:
0,5
Prescriptive compliance is based on Table R402.1.1 with the following modifications:
Vertical fenestration U = 0.28
Floor R-38
Slab on grade R-10 perimeter and under entire slab
Below grade slab R-10 perimeter and under entire slab
or
Compliance based on Section R402.1.4: Reduce the Total UA by 5%.
1b
EFFICIENTBUILDINGENVELOPElb:
I.0
Prescriptive compliance is based on Table R402.1.1 with the following modifications:
Vertical fenestration U = 0.25
Wall R-21 plus R-4
Floor R-38
Basement wall R-21 int plus R-5 ci
Slab on grade R-10 perimeter and under entire slab
Below grade slab R-10 perimeter and under entire slab
or
Compliance based on Section R402.1.4: Reduce the Total UA by I M
I
EFFICIENT BUILDING ENVELOPE I c:
2.0
Prescriptive compliance is based on Table R402.1.1 with the following modifications:
Vertical fenestration U = 0.22
Ceiling and single -rafter or joist -vaulted R-49 advanced
Wood frame wall R-21 int plus R-12 ci
Floor R-38
Basement wall R-21 int plus R- 12 ci
Slab on grade R-10 perimeter and under entire slab
Below grade slab R-10 perimeter and under entire slab
or
Compliance based on Section R402.1.4: Reduce the Total UA by 30%.
Id'
EFFICIENT BUILDING ENVELOPE I d:
0.5
Prescriptive compliance is based on Table R402.1.1 with the following modifications:
Vertical fenestration U = 0.24
2a
AIR LEAKAGE CONTROL AND EFFICIENT VENTILATION 2a:
0.5
Compliance based on 8402.4.1.2: Reduce the tested air leakage to 3.0 air changes per
hour maximum
and
All whole house ventilation requirements as determined by Section M1507.3 of the
International Residential Code shall be met with a high efficiency fan (maximum 0.35
watts/efm), not interlocked with the furnace fan. Ventilation systems using a furnace
including an ECM motor are allowed, provided that they are controlled to operate at
low speed in ventilation only mode.
To qualify to claim this credit, the building permit drawings shall specify the option
being selected and shall specify the maximum tested building air leakage and shall
show the qualifying ventilations stem.
2b
AIR LEAKAGE CONTROL AND EFFICIENT VENTILATION 2b:
1.0
Compliance based on Section R402.4.1.2: Reduce the tested air leakage to 2.0 air
changes per hour maximum
and
All whole house ventilation requirements as determined by Section M1507.3 of the
International Residential Code shall be met with a heat recovery ventilation system
with minimum sensible heat recovery efficiency of 0.70.
To qualify to claim this credit, the building permit drawings shall specify the option
being selected and shall specify the maximum tested building air leakage and shall
show the heat recovery ventilations stem.
Table 406.2
Enerav Credits (2015 Cndpl
OPTION
DESCRIPTION
CREDIT(S)
Estimated Cost
2crAII
EAKAGE CONTROL AND EFFICIENT VENTILATION 2c:
l.5
iance based on Section R402.4.1.2: Reduce the tested air leakage to 1.5 air
s per hour maximum
ole house ventilation requirements as determined by Section MI507.3 of the
International Residential Code shall be met with a heat recovery ventilation system
with minimum sensible heat recovery efficiency of 0.85.
To qualify to claim this credit, the building permit drawings shall specify the option
being selected and shall specify the maximum tested building air leakage and shall
show the heat recovery ventilations stem.
3a b
MGH EFFICIENCY HVAC EQUIPMENT 3a:
l.p
Gas, propane or oil -fired furnace with minimum AFUE of 94°/y or
Gas, propane oroiled-fired boiler with minimum AFUE of 92%
To qualify to claim this credit, the building permit drawings shall specify the option
being selected and shall specify the heating equipment type and the minimum
equip ment efficiency.
36
HIGH EFFICIENCY HVAC EQUIPMENT 3b:
I.0
Air -source heat pump with minimum HSPF of 9.0
To qualify to claim this credit, the building permit drawings shall specify the option
being selected and shall specify the heating equipment type and the minimum
equip ment efficiency.
3c
HIGH EFFICIENCY HVAC EQUIPMENT 3c:
1 5
Closed-loop ground source heat pump; with a minimum COP of 3.3
or
Open loop water source heat pump with a maximum pumping hydraulic head of 150
feet and minimum COP of 3.6
To qualify to claim this credit, the building permit drawings shall specify the option
being selected and shall specify the heating equipment type and the minimum
equipment efficiency.
3d
HIGH EFFICIENCY HVAC EQUIPMENT 3d:
10
Ductless Split System Heat Pumps, Zonal Control: In homes where the primary space
heating system is zonal electric heating, a ductless heat pump system shall be installed
and provide heating to the largest zone of the housing unit.
To qualify to claim this credit, the building permit drawings shall specify the option
being selected and shall specify the heating equipment type and the minimum
equipment efficiene .
4
HIGH EFFICIENCY HVAC DISTRIBUTION SYSTEM:
10
All heating and cooling system components installed inside the conditioned space.
This includes all equipment and distribution system components such as forced air
ducts, hydronie piping, hydronic floor heating loop, convectors and radiators. All
combustion equipment shall be direct vent or sealed combustion.
For forced air ducts: A maximum of 10 linear feet of return ducts and 5 linear feet of
supply ducts may be located outside the conditioned space. All metallic ducts located
outside the conditioned space must have both transverse and longitudinal joints sealed
with mastic. If flex ducts are used, they cannot contain splices. Flex duct connections
must be made with nylon straps and installed using a plastic strapping tensioning tool.
Ducts located outside the conditioned space must be insulated to a minimum of R-8.
Locating system components in conditioned crawl spaces is not permitted under this
option.
Electric resistance heat and ductless heat pumps are not permitted under this option.
Direct combustion heating equipment with AFUE less than 80% is not permitted
under this option.
To qualify to claim this credit, the building permit drawings shall specify the option
being selected and shall specify the heating equipment type and shall show the
location of the heating and cooling equipment and all the ductwork.
Table 406.2
Enerav Credits (2015 Cedp►
OPTION
DESCRIPTION
CREDIT(S)
Estimated Cost
Sa
ENT WATER HEATING 5a:
FAII
0.5
werhead and kitchen sink faucets installed in the house shall be rated at 1.75
GPM or less. All other lavatory faucets shall be rated at 1.0 GPM or less.`
To qualify to claim this credit, the building permit drawings shall specify the option
being selected and shall specify the maximum flow rates for all showerheads, kitchen
sink faucets, and other lavatory faucets.
5b
EFFICIENT WATER HEATING 5b:
l.0
Water heating system shall include one of the following:
Gas, propane or oil water heater with a minimum EF of 0.74
or
Water heater heated by ground source heat pump meeting the requirements of Option
3c.
or
For R-2 occupancy, a central heat pump water heater with an EF greater than 2.0 that
would supply DH W to all the units through a central water loop insulated with R-8
minimum pipe insulation.
To qualify to claim this credit, the building permit drawings shall specify the option
being selected and shall specify the water heater equipment type and the minimum
equipment efficienc .
5c
EFFICIENT WATER HEATING 50:
1,5
Water beating system shall include one of the following:
Gas, propane or oil water heater with a minimum EF of 0.91.
or
Solar water heating supplementing a minimum standard water heater. Solar water
heating will provide a rated minimum savings of 85 therms or 2000 kWh based on the
Solar Rating and Certification Corporation (SRCC) Annual Performance of OG -300
Certified Solar Water Heating Systems
or
Electric heat pump water heater with a minimum EF of 2.0 and meeting the standards
ofNEEA's Northern Climate Specifications for Heat Pump Water Heaters
To qualify to claim this credit, the building permit drawings shall specify the option
being selected and shall specify the water heater equipment type and the minimum
equipment efficiency and, for solar water heating systems, the calculation of the
minimum energy savings.
5d
EFFICIENT WATER HEATING 5d:
0.5
A drain water heat recovery unit(s) shall be installed, which captures waste water heat
from all the showers, and has a minimum efficiency of 40% if installed for equal flow
or a minimum efficiency of 52% if installed for unequal flow. Such units shall be
rated in accordance CSA B55.1 and be so labeled.
To qualify to claim this credit, the building permit drawings shall include a plumbing
diagram that specified the drain water heat recovery units and the plumbing layout
needed to install it and labels or other documentation shall be provided that
demonstrates that the unit complies with the standard.
Table 406.2
Energy Credits (2015 Code)
OPTION DESCRIPTION
CREDIT(S)
Estimated Cost
6 RENEWABLE ELECTRIC ENERGY:
0.5
For each 1200 kWh of electrical generation per each housing unit provided annually
by on-site wind or solar equipment a 0.5 credit shall be allowed, up to 3 credits.
Generation shall be calculated as follows:
For solar electric systems, the design shall be demonstrated to meet this requirement
using the National Renewable Energy Laboratory calculator PV WATTS.
Documentation noting solar access shall be included on the plans.
For wind generation projects designs shall document annual power generation based
on the following factors:
The wind turbine power curve; average annual wind speed at the site; frequency
distribution of the wind speed at the site and height of the tower.
To qualify to claim this credit, the building permit drawings shall specify the option
being selected and shall show the photovoltaic or wind turbine equipment type,
provide docpmentation of solar and wind access, and include a calculation of the
minimum annual energy power production.