2020.0098.BP0007 20200303BE Jahner Butcher Pole 36x36 - Calcs eseal (2)Designed By:
Eric J. Sniezak, P.E.
EJS Engineering, PLLC
183 Mountain View Dr
Packwood, WA 98361
(360)880-0524 or (253)405-2200
eric@ejs-engineering.com
Job # 20200303BE
Structural Calculations for:
Dale Butcher Pole Building
Thurston County
3/3/2020
10711 Mill Road SE, Yelm, WA
Jahner Construction
EJS Engineering, PLLC
Eric J. Sniezak, P.E.
20200303BE Jahner Butcher Pole 36x36 - Calcs.xlsx
183 Mountain View Dr
Packwood, WA 98361
(360) 880-0524 /(253) 405-2200
Scope of Work
Eric J. Sniezak, P.E.
EJS Engineering, PLLC
183 Mountain View Dr
Packwood, WA 98361
(360)880-0524 or (253)405-2200
eric@ejs-engineering.com
EJS Engineering, PLLC was asked to provide structural calculations and structural plans to the
designer/architect/owner/contractor for use in obtaining a building permit for the referenced
project at the referenced location.
The application and use of these calculations is limited to a single site referenced
on the cover sheet. The attached calculations may or may not apply to other sites and
the designer/architect/owner/contractor assumes all responsibility and liability for sites not
expressly reviewed and approved. Please contact EJS Engineering PLLC for use at other sites.
The scope of this agreement covers the design phase only. If site inspections are required by the
building department, these will be performed at an additional hourly fee of $150.00 per hour
(including travel time). Also, revisions to the original design will be billed at the hourly rate of
$150.00 per hour-including site visits and travel time due to construction not following original
engineering.
EJS Engineering PLLC will use that degree of care and skill ordinarily exercised under similar
circumstances by members of the engineering profession in this local. No other warranty, either
expressed or implied is made in connection with our rending of professional services. For any
dispute, claim, or action arising out of this design, EJS Engineering shall have liability limited to the
amount of the total fee received by EJS Engineering.
All work done by EJS Engineering, PLLC is valid only for the specific project invoiced. Unless
otherwise noted, payment for services are due at delivery. Failure to pay for services rendered
will result in the invalidity of the professional stamp and will be reported to the proper
state/county/city jurisdiction.
Questions about the attached information should be addressed to EJS Engineering, PLLC
Scope of Work 2 of 9
EJS Engineering, PLLC
Eric J. Sniezak, P.E.
20200303BE Jahner Butcher Pole 36x36 - Calcs.xlsx
General Notes:Job # 20200303BE
3/3/2020
Project:
Dale Butcher Pole Building
Jahner Construction
10711 Mill Road SE, Yelm, WA
Thurston County
Job # 20200303BE
Applicable Codes and Specifications:
2015 International Building Code [IBC]
2015 International Residential Code [IRC]
ASCE 7-10 [ASCE]
2015 NDS/ASD Wood Design Manuals [NDS]
ANSI/AF&PA SDPWS-2015 Special Design Provisions for wind and seismic [AF&PA]
Simpson Strong-Tie Wood Construction Connectors C-2011 [Simpson]
Boise Engineered Wood Products-WSG 11/2005 [BCI]
WABO-SEAW White Paper Snow Load Regulations and Engineering Practices [WABO-SEAW]
Risk Category:II
Vertical Loads:
Dead Loads Live Loads
RoofH (Heated)5 psf 25 psf [ASCE Tbl 4-1]
RoofU (Unheated)5 psf 25 psf
Floor 12 psf 40 psf [ASCE Tbl 4-1]
Deck or Balcony 12 psf 60 psf [ASCE Tbl 4-1]
Storage 12 psf 100 psf [ASCE Tbl 4-1]
Timber Wall 10 psf n/a
Concrete 150 pcf n/a
Steel 490 pcf n/a
Lateral Loads:
Seismic Design Criteria D1
Wind Speed, Vult 110 mph
Exposure Category C
Site Condition:
Vertical Founation Pressure 1500 psf [IBC Tbl 1806.2]
Lateral Bearing Pressure 150 psf/ft [IBC Tbl 1806.2]
Ground Snow Load 30 psf
Frost Depth 18 inches
Jurisdiction:
Thurston County
[ASCE Tbl 1.5-1 &
IBC Tbl 1604.5]
General Notes 3 of 9
EJS Engineering, PLLC
Eric J. Sniezak, P.E.
20200303BE Jahner Butcher Pole 36x36 - Calcs.xlsx
Wind Loads Job # 20200303BE
Risk Category II
Basic Wind Speed, Vult 110 MPH
Wind Directionality Factor, Kd 0.85 [ASCE table 26.6-1]
Exposure Category C [ASCE 26.7]
Topographic Factor, Kzt 1.0 [ASCE 26.8]
Enclosure Classification Enclosed [ASCE 26.10]
net pressure top, ph 19.70 psf [ASCE table 27.6-1]
net pressure bot, p0 18.10 psf [ASCE table 27.6-1]
net pressure roof, pz 14.05 psf [ASCE table 27.6-2]
[ASCE 27.4.7]
walls 16.0 psf
roof 8.0 psf
Basic Load Combination = 1.0D + 0.6W [IBC 16-12]
= 0.6D + 0.6W [IBC 16-14]
Calc Min
ph=19.7 16.0 19.7 psf
p0=18.1 16.0 18.1 psf
pz=14.0 8.0 14.0 psf
Control
Wind loads for the MWFRS (Main Wind-Force Resisting System) shall be
determined in accordance with Chapter 26-30 of ASCE 7.
Minimum design wind load shall be:
Wind Loads 4 of 9
EJS Engineering, PLLC
Eric J. Sniezak, P.E.
20200303BE Jahner Butcher Pole 36x36 - Calcs.xlsx
Seismic Loads Job # 20200303BE
Diaphragms are considered flexible for wood framing [ASCE12.14.5]
Simplified method used [ASCE12.14.1.1 & table 12.6-1]
Seismic Design Category =D1 [ASCE Tbl 11.6-1]
E=Eh+Ev [ASCE Eqn 12.14-3]
Eh=QE [ASCE Eqn 12.14-5]
Ev=0.2*Sds*D [ASCE Eqn 12.14-6]
QE = effective horz. Seismic force = V
V = F*SDS*W/R -Seismic Base Shear [ASCE Eqn 12.14-11]
where SDS = 2/3*FaSS 100%
Fa = Acceleration based Site Coefficient 1.2 [ASCE Tbl 11.4-1]
Ss = Mapped spectral accel.125%[ASCE Fig 22-1]
F = # of storys modifer, 1.0, 1.1, 1.2; 1, 2, 3 stories 1.1 [ASCE 12.14.8-1]
R = Response mod factor 6.5 Rwood [ASCE Tbl 12.14-1]
1.25 Rcanti [ASCE Tbl 12.2-1]
W = The Effective Seismic weight **lbs
** Weights are as follows:
Roofs 5 psf [ASCE 12.14.8-1 note 2]
Floors 12 psf
Walls 10 psf
Basic Load Combination = 1.0D +0.7E [IBC 16-12]
= 0.6D +0.7E [IBC 16-16]
DESIGN SEISMIC LOADS:
E = Eh = V = F*SDS*W/Rwood 0.169 *W
E = Eh = V = F*SDS*W/Rcanti 0.880 *W
0.7E wood = 0.118 *W
0.7E canti = 0.616 *W
note: 0.2*Sds*D is the v.c. Structure is adequate for this load by inspection.
Seismic Loads 5 of 9
EJS Engineering, PLLC
Eric J. Sniezak, P.E.
20200303BE Jahner Butcher Pole 36x36 - Calcs.xlsx
Snow Loads Job # 20200303BE
Snow Loads
Ground Snow Load, pg 30.0 psf
pf=0.7*Ce*Ct*Is*Pg Ce 1.0
heated Ct 1.0
Cold Ct 1.2
Is 1.0
Heated Flat Roof Snow Load, prh 21.0 psf
UnHeated Flat Roof Snow Load, prc 25.2 psf
Ps=Cs*pf heated Cs 0.80
Cold Cs 0.85
Heated sloped Roof Snow Load, prhs 16.8 psf Min use 25 psf
UnHeated sloped Roof Snow Load, prcs 21.4 psf Min use 25 psf
Snow Loads 6 of 9
EJS Engineering, PLLC
Eric J. Sniezak, P.E.
20200303BE Jahner Butcher Pole 36x36 - Calcs.xlsx
Gravity Analysis Job # 20200303BE
(A) Roof System
A1-Trusses and Attic trusses
Standard trusses in house. Typical H2.5a hold down at each truss. Have
manufacture specifications on site during construction.
Gravity Analysis 7 of 9
EJS Engineering, PLLC
Eric J. Sniezak, P.E.
20200303BE Jahner Butcher Pole 36x36 - Calcs.xlsx
Gravity Analysis Job # 20200303BE
A2-14' bays
Span and Member Properties
Type No. of pieces Section Species Δ Crit Span (ft)Moist Cont.
S4S 1 2x6 DF#2 Roof 12.0 <19%
b 1.50 in Wt factor 0.233 lb/(in2-ft)
h 5.50 in WtInc factor 1.000 factor
Ax 8.25 in2 E 1,300,000 psi
Sx 7.6 in3 Fb 900 psi
Ix 20.8 in4 Fv 180 psi
Adjustment Factors Adjusted Design Values
M V E E'1,300,000 psi
CF = 1.3 N/A N/A F'b 1,346 psi
Cr = 1.15 N/A N/A F'v 180 psi
CM = 1 1 1 Vxall 990 lbs
Cfu = 1 N/A N/A Mxall 848 ft-lbs
Ci = 1 1 1 ùLLMax 0.600 in
Ct = 1 1 1 ùTotMax 0.800 in
Uniform Loads
Roof Floor Deck Storage
Dead (psf)5 12 12 12
Live (psf)25 40 60 100
Trib (ft)1.3 0.0 0.0 0.0
Total Loads 40.0 0.0 0.0 0.0 1.92 plf
Point Loads Reactions/forces/stresses
Load 1 Load 2 Ra 251.5 lbs
Dead 0 0 Rb 251.5 lbs
Live 0 0 Vxmax 251.5 lbs
Location 0.0 0.0 Mxmax 754.6 ft-lbs
Design Check Stress/Deflection/Load Check------------------->OK
Max fv (psi) & V (lbs)46 252 180 990 25%
Max fb (psi) & M (ft-lbs)1,197 755 1,346 848 89%
Live Load Max Defl. (in)0.575 L/250 0.600 L/240 96%
Total Load Max Defl. (in)0.723 L/199 0.800 L/180 90%Self-Weight Actual Allowable
Gravity Analysis 8 of 9
EJS Engineering, PLLC
Eric J. Sniezak, P.E.
20200303BE Jahner Butcher Pole 36x36 - Calcs.xlsx
Pole Building Design Job # 20200303BE
P1-Main Frame
Length 55.0 ft
Width 30.0 ft
Post Height 18.5 ft
Roof Pitch 4.0 :12
Roof Type Std
Roof Height (for horz. Projected area calculation)5.0 ft
Frame Spacing 14.0 ft
Number of Posts in Frame (typicall in width)2 each
Braced ht in Frame 18.5 ft
Number of Post Perpendicular (down length)5 each
Trib area for Perpendicular Loading 15 ft
Braced ht Perpendicular 2 ft
Axial Load 4,987.5 lbs
Roof Lateral Load, top of post 620.6 lbs
Uniform Wind Load on Post 124.1 plf
Post Size 6x6 HF#1
fc/F'c = 12%fb/F'b =70%fv/F'v=72%
Fc&Fb=91%
Top Connection
Load per side 2,493.8 lbs
block length 24 in
3/4" Diam Thru bolts 1,040.0 lbs/bolt
16d Nails per side 133.0 lbs/bolt
Bolts 2 Nails/side 6 2,878.0 Capacity OK
Foundation Design
Required Area 3.3 sq ft
Punch pad min dimension 21.881 in x in min
Constrained?yes [IBC 18-3]
1806.3.4- increase for isolated poles yes
Hole Size 24 in square
Base Pad Thickness 6 in
Post Embedment 4.8 ft
Requied post embement, d 4.48 ft OK
SUMMARY:
6x6 HF#1
(2) 3/4" Diam Thru bolts and (6) 16d Nails per side
24 in square by 4.75 ft deep with 6 in thick punch pad
OK
Pole Design 9 of 9