2020.0210.FR0004 20-051 Wyndstone Bldg 1 Equip SubKNIGHT FIRE PROTECTION, INC. 9702 LATHROP INDUSTRIAL DR. SW OLYMPIA, WA 98512-9188 (360) 786-8606 FAX 786-8722 LICENSE NO. KNIGHFP044LK Fire Sprinkler System Equipment Submittal Wyndstone Apartments Bldg 1 15025 Tahoma Blvd. SE Yelm, WA KFP Job #12-113 KFP Job #12-113 APRIL 2019 REV.A GFS-302 PAGE 1 of 4 SERIES GL-RES RESIDENTIAL PENDENT AND RECESSED PENDENT K-FACTOR: 3.0, 4.1, 4.9, 5.6 4077 Airpark Dr. Standish, MI 48658 • 989-846-4583 • www.globesprinkler.com Technical Support • 989-414-2600 • techservice@globesprinkler.com NOTE: Users should refer to Globe’s web site (www.globesprinkler.com) to assure that the most recent technical literature is being utilized. GENERAL DESCRIPTION The series GL-RES pendent sprinklers are decorative fast response glass bulb sprinklers specifically tested and List- ed for use in residential applications such as homes, apart- ments, hotels, and dormitories to provide control of these residential type fires and to improve the chance for occu- pants to escape. They utilize a 3mm frangible glass bulb as its heat sensing operating element. The recessed version of each of these Residential Sprinklers is intended for use in areas with finished ceilings. It employs a two-piece Re- cessed Escutcheon. The Recessed Escutcheon provides a total adjustment of 1/2 inch (12.7mm) from the flush ceiling position or ±1/4 inch (6.4mm) of recessed adjustment. The adjustment provided by the Recessed Escutcheon reduces the accuracy to which the pipe drops to the sprinklers must be cut. This sprinkler may be installed within dwelling occupancies as allowed by NFPA 13, 13D, 13R and any other related documents as appropriate. The GL3010 is typically utilized when maximum coverag- es are not needed, thereby reducing flow demands. The GL5610 is typically the sprinkler of choice when utilizing Residential Sprinklers within an NFPA 13 Occupancy. The larger K-factor can be advantageous when needed to con- form to the NFPA 13 hydraulic Special Design Approach for Residential Sprinklers. OPERATION Upon exposure to heat such as from a fire, the fluid in the bulb expands, compressing the air bubble within the bulb. When the air bubble can no longer compress, the fluid ex- pansion causes breakage of the glass bulb, resulting in re- lease of the water seat assembly, and discharge of water from the sprinkler. TECHNICAL DATA Approvals • See TABLE A Maximum Working Pressure • 175 psi (12 bar) Temperature Rating • See TABLE A K-Factor • GL3010 K3.0 gpm/psi½ (43.2 lpm/bar½) • GL4110 K4.1 gpm/psi½ (59.0 lpm/bar½) • GL4910 K4.9 gpm/psi½ (70.6 lpm/bar½) • GL5610 K5.6 gpm/psi½ (80.6 lpm/bar½) Thread Size • 1/2” NPT (15 mm) Length • 2-1/2” (6.3 cm) Materials of Construction • Frame - bronze • Deflector - brass • Screw - brass • Lodgement Wire (GL5610 only) - stainless steel • Bulb seat - copper • Spring - nickel alloy • Seal - teflon • Bulb - glass with alcohol based solution, 3mm • Escutcheon Assembly - carbon steel FINISHES AND ACCESSORIES Finishes • Factory Bronze • Chrome • White Polyester • Black Polyester - special order Escutcheons • Brass • Chrome • White Polyester • Black Polyester Wrenches • Standard • Recess • 1/2” NPT SERIES GL-RES GL3010, GL4110, GL4910, GL5610 SERIES GL-RES RESIDENTIAL PENDENT AND RECESSED PENDENT K-FACTOR: 3.0, 4.1, 4.9, 5.6 SERIES GL-RES RESIDENTIAL PENDENT AND RECESSED PENDENT K-FACTOR: 3.0, 4.1, 4.9, 5.6GFS-302 GFS-302 APRIL 2019 REV.A GFS-302 PAGE 2 of 4 DESIGN CRITERIA The Globe Residential Pendent Sprinkler Series GL-RES is cULus Listed for installation in accordance with this data sheet as well as the applicable installation Standard being utilized. Globe Residential Sprinkler Installation Guide When conditions exist that are outside the scope of the pro- vided criteria, refer to the Globe Residential Sprinkler Instal- lation Guide (Document GFS-380) for recommendations that may be acceptable to the authority having jurisdiction. Hydraulic Design (NFPA 13D and 13R) For systems designed to NFPA 13D or NFPA 13R, the min- imum required sprinkler flow rate is given in Table A for the coverage areas shown. The sprinkler flow rate is the min- imum required discharge from each of the total number of “design sprinklers” as specified in NFPA 13D or NFPA 13R. Hydraulic Design (NFPA 13) The minimum required discharge from each design area sprinkler shall be the greater of the following: (1) In accordance with minimum flow rates indicated in TABLE A. (2) In rooms or compartments greater than 800 ft2 (74.3 m2), calculated based on delivering a minimum of 0.1 gpm/ft2 (4.1 mm/min) over the coverage area of each sprinkler, calculated in accordance with the S x L Rules for density area sprinklers. (3) In rooms or compartments 800 ft2 (74.3 m2) or less (Defined as “Small Rooms”) calculated based on de- livering a minimum of 0.1 gpm/ft2 (4.1 mm/min) over the room or compartment using the area of the room divided by the number of sprinklers in the room. (7psi minimum) SIN K FACTOR GPM/PSI½ (lpm/bar½) TEMPERATURE MAX.AREA OF COVERAGE FEET (m) MINIMUM PRESSURE PSI (bar) MINIMUM FLOW GPM (L/min.) DEFLECTOR TO CEILING/ MOUNTING SURFACE DISTANCE INCHES (mm) MINIMUM DISTANCE BETWEEN SPRINKLERS FEET (m)155°F (68°C)175°F (79°C)200°F (93°C) GL3010 3.0 (43.2) cULus EU(1)cULus cULus 12 (3.6) x 12 (3.6)7.1 (.49)8.0 (30.3) Smooth Ceilings Recessed 1-1/8 (29) to 1-5/8 (41) Smooth Ceilings Exposed Max. 4 (101.6) Beamed Ceilings Adjacent per NFPA 13, 13D, or 13R as appropriate Beamed Ceilings In Beam 14” Max. Beam Depth 1-1/8 (29) to 1-5/8 (41) 8 (2.4) cULus EU(1)cULus cULus 14 (4.3) x 14 (4.3)11.1 (.765)10.0 (37.8) GL4110 4.1 (59) cULus EU(1)cULus EU(1)NA 12 (3.6) x 12 (3.6)7.2 (.5)11.0 (42) cULus EU(1)NA NA 14 (4.3) x 14 (4.3)8.6 (.59)12.0 (45) cULus EU(1)cULus NA 16 (4.9) x 16 (4.9)11.7 (.81)14.0 (53) GL4910 4.9 (70.6) cULus EU(1)cULus EU(1)NA 12 (3.6) x 12 (3.6)7.0 (.48)13.0 (49) cULus EU(1)cULus EU(1)NA 14 (4.3) x 14 (4.3)8.2 (.57)14.0 (53) cULus EU(1)cULus EU(1)NA 16 (4.9) x 16 (4.9)8.2 (.57)14.0 (53) cULus EU(1)cULus EU(1)NA 18 (5.5) x 18 (5.5)12.0 (.83)17.0 (64) cULus EU(1)cULus EU(1)NA 20 (6.1) x 20 (6.1)16.7 (1.15)20.0 (76) GL5610 5.6 (80.6) cULus NA NA 12 (3.6) x 12 (3.6)7.2 (.5)15.0 (57) cULus NA NA 16 (4.9) x 16 (4.9)11.5 (.79)19.0 (72) cULus NA NA 18 (5.5) x 18 (5.5)14.1 (.97)21.0 (79) cULus NA NA 20 (6.1) x 20 (6.1)18.4 (1.27)24.0 (91) TABLE A: NFPA 13, 13R, AND 13D HYDRAULIC AND INSTALLATION DESIGN CRITERIA (1)LISTED BY UNDERWRITERS LABORATORIES, INC. FOR USE IN THE U.S., CANADA, AND EUROPEAN UNION. NOTE: Deflector-to-Ceiling Distance Criteria reflects 2019 Edition of NFPA 13D and 13R. APRIL 2019 REV.A GFS-302 PAGE 3 of 4 4077 Airpark Dr. Standish, MI 48658 • 989-846-4583 • www.globesprinkler.com Technical Support • 989-414-2600 • techservice@globesprinkler.com NOTICE Do not install any bulb-type sprinkler if the bulb is cracked or there is loss of liquid from the bulb. Sprinklers should be tightened enough to obtain a leak-tight joint when water pressure is applied and/or hydrostatic test is performed. Sprinklers should not be overtightened as this can result in distortion and subsequent leak-age. It is recommended not to exceed 14 ft.-lb. (19.0 Nm) torque for 1/2 inch NPT sprinkler threads. Step1. Sprinklers must be properly oriented. Step2. With pipe thread sealant applied to the pipe threads, hand tighten the sprinkler into the sprin- kler fitting. Note: Do not grasp the sprinkler by the deflector. Step3. Wrench-tighten the sprinkler using only the appropriate wrench. Wrenches are only to be applied to the sprinkler wrench flats or wrench hex as applicable. Note: Do not apply wrench to frame arms. INSTALLATION CARE AND MAINTENANCE Prior to installation, it is important to read and follow the “Sprinkler Caution” sheet (GFS-840) included within each box of sprinklers. This sheet is available on Globe’s web site (www.globesprinkler.com). Always obtain permission from the proper authorities to shut down the affected fire protection system and notify all personnel who may be affected by this action before closing a fire protection system main control valve for maintenance work on the system that it controls. Sprinklers should only be cleaned by means of gently dust- ing with a feather duster; otherwise, non-operation in the event of a fire or inadvertent operation may result. Store sprinklers in a cool, dry place. Exposure to extreme heat will damage the thermal sensing element, possibly re- sulting in premature activation. Avoid direct sunlight. Replace any sprinkler that shows any corrosion, damage, or loss of liquid from the glass bulb. Do not attempt to paint or alter the sprinkler’s coating in any manner after leaving the manufacturing plant. Do not attach wiring, ropes, decorations or fixtures to a sprinkler. Absence of an escutcheon, used to cover a ceiling hole, may delay sprinkler operation in a fire situation. It is the owner’s responsibility for inspection, testing and maintenance of the fire sprinkler system with all components and devices in accordance with the National Fire Protection Association Pamphlet 25 as well as any other requirements as set forth by the local Authority Having Jurisdiction (AHJ). FIGURE 1: STANDARD WRENCH P/N 325390 FIGURE 2: RECESSED WRENCH P/N 325391 FIGURE 3: 1/2” ADJUSTMENT RECESSED PENDENT APRIL 2019 REV.A GFS-302 PAGE 4 of 4 GLOBE® PRODUCT WARRANTY Globe agrees to repair or replace any of its manufactured products found to be defective in material or workmanship for a period of one year from date of shipment. For specific details of our warranty please refer to Price List Terms and Conditions of Sale (Our Price List). ORDERING INFORMATION SPECIFY: • WRENCH • Quantity • Part Number 1/2” NPT Standard . . . . . . . . . . . 325390 1/2” NPT Recess . . . . . . . . . . . . 325391 • Quantity • Part Number Cap . . . . . . . . . . . . . . . . . . . 327109-Cap • PROTECTIVE CAPS • SPRINKLER • ESCUTCHEON • Quantity • Finish • Part Number (See TABLE C) • Quantity • SIN • Temperature Rating • Finish • Part Number (See TABLE B) TABLE B: PART NUMBER SELECTION PART NUMBER SIN + TEMPERATURE + FINISH XXXX XXX XX SIN TEMPERATURE FINISH GL3010 3010 155 155°F (68°C)01 BRONZE GL4110 4110 175 175°F (79°C)02 CHROME GL4910 4910 200 200°F (93°C)03 WHITE POLYESTER GL5610 5610 04 BLACK POLYESTER Note: All combinations may not be available. Refer to TABLE A for available listed combinations 1/2" (13mm) ADJUSTABLE RECESSED ESCUTCHEON FINISH FRICTION FIT 1/2” NPT THREADED 1/2” NPT Chrome 332071 329301 White Polyester 332073-W 329303-W Brass 332072 NA Black Polyester 332073-B NA TABLE C: ESCUTCHEONS NOV 2016 GFS-100a (Formerly A-20) SPRINKLER TEMPERATURE RATING/CLASSIFICATION and COLOR CODING • See reverse side for Approvals and Specifi cations. • Temperature Ratings - 135°F (57°C), 155°F (68°C), 175°F (79°C), 200°F (93°C), 286°F (141°C) • Water Working Pressure Rating - 175 psi (12 Bars) • Factory tested hydrostatically to 500 psi (34 Bars) • Maximum low temperature glass bulb rating is -67°F (-55°C) • Frame - bronze • Defl ector - brass • Screw - brass • Lodgement Wire - stainless steel • Bulb seat - copper • Spring - nickel alloy • Seal - tefl on • Bulb - glass with alcohol based solution, 3mm size CLASSIFICATION AVAILABLE SPRINKLER TEMPERATURES BULB COLOR N.F.P.A. MAXIMUM CEILING TEMPERATURE ORDINARY INTERMEDIATE HIGH 135°F/155°F 175°F/200°F 286°F 57°C/68°C 79°C/93°C 141°C ORANGE/RED YELLOW/GREEN BLUE 100°F 150°F 225°F 38°C 66°C 107°C QUICK RESPONSE AUTOMATIC SPRINKLERS GL SERIES UPRIGHT PENDENT VERTICAL SIDEWALL HORIZONTAL SIDEWALL CONVENTIONAL (OLD STYLE) UPRIGHT CONVENTIONAL PENDENT VERTICAL SIDEWALL QUICK RESPONSE DESCRIPTION AND OPERATION The Globe Quick Response GL Series Sprinklers are a low profi le yet durable design which utilizes a 3mm frangible glass ampule as the thermosensitive element. This provides sprinkler operation approximately six times faster than ordinary sprinklers. While the Quick Response Sprinkler provides an aesthetically pleasing appearance, it can be installed wherever standard spray sprinklers are specifi ed when allowed by the applicable stan- dards. It offers the additional feature of greatly increased safe- ty to life and is available in various styles, orifi ces, temperature ratings and fi nishes to meet many varying design requirements. Quick Response Sprinklers should be used advisedly and under the direction of approving authorities having jurisdiction. The heart of Globe's GL Series sprinkler proven actuat- ing assembly is a hermetically sealed frangible glass ampule that contains a precisely measured amount of fl uid. When heat is ab- sorbed, the liquid within the bulb expands increasing the internal pressure. At the prescribed temperature the internal pressure within the ampule exceeds the strength of the glass causing the glass to shatter. This results in water discharge which is distrib- uted in an approved pattern depending upon the defl ector style used. QUICK RESPONSE SPRINKLER TEMPERATURE RATING/CLASSIFICATION and COLOR CODING TECHNICAL DATA QUICK RESPONSE HORIZONTAL SIDEWALL LPC/CE HORIZONTAL SIDEWALL NOV 2016 GFS-100a (Formerly A-20)PRINTED U.S.A. NOMINAL “K” FACTOR THREAD SIZE LENGTH 1 FINISHES 2.8 (40 metric) 1/2”NPT (15mm) 2 1/4” (5.7cm) Factory Bronze Chrome White Polyester3 Black Polyester2,3 4.2 (60 metric) 1/2”NPT (15mm) 2 1/4” (5.7cm) 5.6 (80 metric) 1/2”NPT (15mm) 2 1/4” (5.7cm) 8.0 (115 metric) 1/2”NPT (15mm) 2 1/4” (5.7cm) 8.0 (115 metric) 3/4”NPT (20mm) 2 7/16” (6.2cm) NOTE: METRIC CONVERSIONS ARE APPROXIMATE. 1HORIZONTAL SIDEWALL IS 2 9/16”. 2FINISHES AVAILABLE ON SPECIAL ORDER. 3AVAILABLE AS cULus LISTED COROSION RESISTANT WHEN SPECIFIED ON ORDER. SPECIFICATIONS 1SPRINKLERS SHALL BE LIMITED AS PER THE REQUIREMENTS OF NFPA13 AND ANY OTHER RELATED DOCUMENTS. §HORIZONTAL SIDEWALL cULus LISTED FOR DEFLECTOR 4” TO 12” BELOW THE CEILING, FM APPROVED 4” TO 6” BELOW THE CEILING. ¤INSTALL IN ACCORDANCE TO BS5306 AND ANY OTHER RELATED DOCUMENTS. †PENDENT VERTICAL SIDEWALL cULus LISTED FOR 6’ MIN. SPACING. †UPRIGHT VERTICAL SIDEWALL cULus LISTED FOR 9’ MIN. SPACING. OH: ORDINARY HAZARD LH: LIGHT HAZARD *1/2” NPT ORDERING INFORMATION 4077 AIRPARK DRIVE, STANDISH, MICHIGAN 48658 FAX 989-846-9231 www.globesprinkler.com 989-846-4583 1-800-248-0278 GLOBE® PRODUCT WARRANTY Globe agrees to repair or replace any of its own manufactured products found to be defective in material or workmanship for a period of one year from date of shipment. For specifi c details of our warranty please refer to Price List Terms and Conditions of Sale (Our Price List). • Quantity • Model Number • Style • Orifi ce • Thread Size • Temperature • Finishes desired • Quantity - Wrenches - P/N 325390 (1/2”); P/N 312366 (L.O.) SPECIFY APPROVALS QUICK RESPONSE AUTOMATIC SPRINKLERS GL SERIES UPRIGHT PENDENT VERTICAL SIDEWALL HORIZONTAL SIDEWALL CONVENTIONAL (OLD STYLE) STYLE SIN MODEL K FACTOR HAZARD1 TEMPERATURE cULus FM LPC CE NYC - DOB MEA 101-92-E135°F (57°C) 155°F (68°C) 175°F (79°C) 200°F (93°C) 286°F (141°C) UPRIGHT GL2815 GL4215 GL5615 GL8115 GL8118 2.8 4.2 5.6 8.0* 8.0 LH LH LH/OH LH/OH LH/OH X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X --- --- X --- X --- --- X --- X --- --- X --- X X X X X X PENDENT GL2801 GL4201 GL5601 GL8101 GL8106 2.8 4.2 5.6 8.0* 8.0 LH LH LH/OH LH/OH LH/OH X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X --- --- X X X --- --- X --- X --- --- X --- X X X X X X VERTICAL SIDEWALL† GL5632 GL8133 5.6 8.0 LH LH X X X X X X X X X X X X X --- --- --- --- --- --- --- HORIZONTAL SIDEWALL GL2826§ GL4226§ GL5626§ GL5627¤ GL8127§ 2.8 4.2 5.6 5.6 8.0 LH LH LH/OH LH/OH LH/OH X X X X X X X X X X X X X X X X X X X X X X X X X X X X --- X --- --- X --- --- --- --- --- X --- --- --- --- X --- X X X --- --- CONVENTIONAL (OLD STYLE) GL5624 GL8125 5.6 8.0 LH/OH LH/OH X X X X X X X X X X --- --- --- --- X X X X --- --- BLAZEMASTER CPVC Fire Sprinkler Pipe & Fittings Submittal Sheet Page 1 of 2 APRIL 2016 TFP1915 Worldwide Contacts www.tyco-fire.com General Description TYCO CPVC Pipe and Fittings pro- duced by Tyco Fire Protection Prod- ucts (TFPP) are designed exclusively for use in wet pipe automatic fire sprinkler systems. The TYCO CPVC Pipe and Fittings are produced from BLAZEMASTER CPVC compound that is a specially developed thermo- plastic compound composed of post chlorinated polyvinyl chloride (CPVC) resin and state of the art additives. TYCO CPVC Pipe and Fittings are easier to install than traditional steel pipe systems, and at the same time, provide superior heat resistance and strength as compared to traditional CPVC and PVC piping materials used in the plumbing trade. Various adapt- ers are available to connect CPVC pipe to metallic piping. All female pipe thread adapters have brass inserts for durability. Grooved adapters connect directly to grooved end valves and metallic pipe, with flexible grooved end couplings. NOTICE The CPVC Pipe and Fittings produced with BLAZEMASTER CPVC compound described herein must be installed and maintained in compliance with this document and with the applicable standards of the National Fire Protec- tion Association (NFPA), in addition to the standards of any authorities having jurisdiction. Failure to do so may impair the performance of these devices. The owner is responsible for main- taining their fire protection system and devices in proper operating con- dition. Contact the installing contrac- tor or product manufacturer with any questions. Technical Data Sizes 3/4 Inch thru 3 Inch Maximum Working Pressure175 psi Approvals UL and C-UL Listed FM Approved LPCB Approved NSF Certified MEA Approved City of Los Angeles (Refer to Installation Handbook IH-1900 dated June 2008 for exact listing/approval information.) Manufacture Source U.S.A. MaterialPipe: ASTM F442, SDR 13.5 Fittings: ASTM F438 (Sch. 40) ASTM F439 (Sch. 80) ASTM F1970 ColorOrange Installation TYCO CPVC Pipe and Fittings are to be to be installed in accordance with Installation Handbook IH-1900 dated April 2016. GLOBAL HEADQUARTERS | 1400 Pennbrook Parkway, Lansdale, PA 19446 | Telephone +1-215-362-0700 TFP1915 Page 2 of 2 Copyright © 2016 Tyco Fire Products, LP. All rights reserved. BLAZEMASTER is a trademark of The Lubrizol Corporation. Care and Maintenance TYCO CPVC Pipe and Fittings are to be maintained and serviced in accordance with this section. Before closing a fire protection system control valve for inspection or main- tenance work on the fire protection system that it controls, permission to shut down the affected fire protection system must first be obtained from the proper authorities and all person- nel who may be affected by this action must be notified. After placing a fire protection system in service, notify the proper authorities and advise those responsible for moni- toring proprietary and/or central station alarms. The owner is responsible for the inspec- tion, testing, and maintenance of their fire protection system and de-vices in compliance with this document, as well as with the applicable standards of the National Fire Protection Associa- tion (e.g., NFPA 25), in addition to the standards of any authority having juris- diction. Contact the installing contrac- tor or product manufacturer with any questions. Automatic sprinkler systems should be inspected, tested, and maintained by a qualified Inspection Service in accor- dance with local requirements and/or national codes. Limited Warranty For warranty terms and conditions, visit www.tyco-fire.com Pipe Clamps Fig. 28 ® "Stand -Off" Hanger & Restrainer f®r CPUC Plastic Pipe & IPS Steel Pipe ** Size Range: — 3/4' (20mm) through 2' (50mm) Material: — Steel, Pre -Galvanized Function: — Designed to be used as a hanger and restrainer for CPVC piping where the 'stand-off' design will ease installation by eliminating the need for wood blocking. Features: • Flared edge design protects CPVC pipe from any rough or abrasive surfaces. • Unique twist and lock design holds pipe firmly in place and allows retrofit type of installation. • The 'Stand -Off' design eliminates the need for wood block extension. • Can be installed on horizontal or vertical piping regardless of mounting surface orientation. • Attaches easily to wood structure with two hex head self -threading screws furnished with product. • Installs easily using rechargeable electrical driver with 5/16' (7.9mm) extension socket eliminating impact tool damage to pipe. • Attaches easily to steel, minimum 18 gauge (1.024mm) with (2) 1/4' x 1' tek type self drilling tapping screws. • UL Listed as a hanger and a restrainer for fire sprinkler piping. Approvals: — Underwriters Laboratory Listed in the USA (UL) and Canada (cUL) to support automatic fire sprinkler systems. May be installed into wood using fasteners supplied with product, or into minimum 18 gauge steel using (2) 1/4' x 1' tek type screws. Meets and exceeds the requirements of NFPA 13, 13R and 13D. Fig. 28 satisfies the UL vertical restraint requirement where needed. UL Listed as a hanger and vertical restraint when installed on 3/8' (9.5mm) composite wood material. Use two Fig. 27B Speed Nuts when used as a hanger and restraint. Use one Fig. 27B Speed Nut on the upper installed screw when used as a hanger only. Order by: — Figure number and pipe size. Pat. # 7,455,268, Pat. # 7,832,248 ** With reduced spacing, consult factory. Fig. 27B (1) Required High Side of Hanger Application Hanger Application Fig. 27B Fli (2) Required Li Hanger and Restraint Application B -Line by 0 All dimensions in charts and on drawings are in inches. Dimensions shown in parentheses are in millimeters unless otherwise specified. 40 Fire Protection Solutions Pipe Size A B C Max Hanger Approx. Spacing Wt./100 Part No. in. (mm) in. (mm) in. (mm) in. (mm) R. (m) lbs. (kg) 28-3/4 3/4' (20) 31/32' (77.0) 2' (50.8) 31/2' (88.9) 51/2 (1.67) 18 (8.1) 28-1 V (25) 35/16" (84.1) 23/16' (55.6) 31/2' (88.9) 6 (1.83) 21 (9.5) 28-11/4 11/4' (32) 35/8' (92.1) 23/8' (60.3) 31/2' (88.9) 61/2 (1.98) 23 (10.4) 28-11/2 11/2' (40) 4' (101.6) 21/2' (63.5) 31/2' (88.9) 7 (2.13) 31 (14.0) 28-2 2' (50) 41/2' (114.3) 211/16' (68.3) 35/8' (92.1) 8 (2.44) 34 (15.4) B -Line by 0 All dimensions in charts and on drawings are in inches. Dimensions shown in parentheses are in millimeters unless otherwise specified. 40 Fire Protection Solutions Pipe ClampsAll dimensions in charts and on drawings are in inches. Dimensions shown in parentheses are in millimeters unless otherwise specified. Pipe Clamps 34 Fig. 24 - Hanger for CPVC Plastic Pipe & IPS Steel Pipe** Double Fastener Strap Side Mounted (Cooper B-Line B3183) Size Range:3/4" (20mm)thru 2" (50mm)CPVC pipe Material:Pre-Galvanized Steel Function:Intended to perform as a hanger to support CPVC piping used in automatic fire sprinkler systems. Can be installed on the top or on the bottom of a beam. Approvals:Underwriters Laboratories Listed in the USA (UL)and Canada (cUL)to support fire sprinkler piping. May be installed in wood using fasteners supplied with product, or into minimum 20 gauge (0.912mm)steel using (2) 1/4" x 1" tek type screws. Meets and exceeds the requirements of NFPA 13, 13R and 13D. Features:Fig. 24 incorporates features which protect the pipe and ease installation. The flared edge design protects the CPVC pipe from any rough surface. Easily attaches to the building structure using the two UL Listed hex head self threading screws* furnished with the product. It is recommended that rechargeable electric drills fitted with a hex socket attachment be used as installation tools. No impact tools (such as a hammer) are allowed. Damage has been known to result from installations using impact type tools. No pre-drilling of a pilot hole in wood is required. Finish:Pre-Galvanized Order By:Figure number and pipe size * Hardened hex head self threading screw is furnished with the product and is the minimum fastener size acceptable. ** With reduced spacing, consult factory. C A B B CPVC Max. Hanger Fastener Hex Approx. Pipe Size ABCSpacing Head Size Wt./100 Part No.in. (mm) in. (mm) in. (mm) in. (mm) Ft. (m) in. (mm) Lbs. (kg) 24-3/4 3/4"(20)25/16"(58.7)15/32"(27.8)13/16"(30.2)51/2 (1.67)5/16"(7.9)9 (4.1) 24-1 1"(25)25/8"(66.7)15/16"(33.3)13/16"(30.2)6 (1.83)5/16"(7.9)9 (4.1) 24-11/4 11/4"(32)3"(76.2)11/2"(38.1)13/16"(30.2)61/2 (1.98)5/16"(7.9)11 (5.0) 24-11/2 11/2"(40)31/4"(82.5)15/8"(42.3)13/16"(30.2)7 (2.13)5/16"(7.9)12 (5.4) 24-2 2"(50)311/16"(93.7)127/32"(43.6)13/16"(30.2)8 (2.44)5/16"(7.9)15 (6.8) Fig. 25 - Surge Restrainer Size Range:— One size fits 3/4"(20mm)thru 2"(40mm)pipe. Material:— Pre-Galvanized Steel Function:— Designed to be used in conjunction with Fig. 200 band hangers to restrict the upward movement of piping as it occurs during sprinkler head activation or earthquake type activity. The surge restrainer is easily and efficiently installed by snapping into a locking position on the band hanger. This product is intended to satisfy the requirements as indicated in the National Fire Protection Association NFPA 13, 2010 edition, 9.2.3.4.4.1 and 9.2.3.4.4.4 Can be used to restrain either steel pipe or CPVC plastic Pipe. Approvals:— Underwriters Laboratories Listed only when used with band hanger Fig. 200, in the USA (UL)and Canada (cUL). Finish:Pre-Galvanized Order By:Figure number and band hanger, size from 3/4"(20mm)thru 2"(40mm). Patent #5,344,108 OFFICE/MANUFACTURING FACILITY • 1375 SAMPSON AVE. • CORONA, CA 92879 • PH: 951.737.5599 • FAX: 951.737.0330 CUSTOMER SERVICE • 800.786.5266 www.tolco.com 43 www.tolco.com Revision 1/11/2011 Fig. 28M - Offset Hanger and Restrainer for CPVC Plastic Pipe and IPS Pipe Size Range — 3/4" thru 1-1/4" Material — Carbon Steel, Pre-Galvanized Function — Designed to be used as a hanger and restrainer for CPVC piping or steel piping where the “stand-off” design will ease installation by eliminating the need for wood blocking. Features — • Flared edge design protects CPVC pipe from any rough or abrasive surfaces • Unique snap-on design holds pipe firmly in place and allows retrofit type of installation • The “Stand-Off” design eliminates the need for wood block extension • Can be installed on horizontal or vertical piping regardless of mounting surface orientation • Attaches easily to wood structure with two hex head self-threading screws furnished with product • Installs easily using rechargeable electrical driver with 5/16” extension socket eliminating impact tool damage to pipe • Attaches easily to steel, minimum 18 gauge with (2) 1/4” x 1” tek type self drilling tapping screws • cULus Listed as a hanger and a restrainer for fire sprinkler piping Installation Note — When installed in wood structural member and threads from the #10 x 1" screws are exposed, use FIG. 27B speed nut to secure Approvals — Underwriters’ Laboratory Listed in the USA (UL) and Canada (cUL) to support automatic fire sprinkler systems. May be installed into wood using fas- teners screws. Meets and exceeds the requirements of NFPA 13, 13R and 13D. Fig. 28M satisfies the UL vertical restraint requirements where needed. Order By — Figure number and pipe size A C B RESTRAINT Patent #7,744,042 RESTRAINT Dimensions • Weights Max. Spacing Pipe required per Approx Size A B C NFPA 13 for Wt./100 CPVC plastic pipe 3/4 2 3/16 3-5/16 5’-6” 9 1 2-1/8 3/16 3-1/2 6’-0” 12 1-1/4 2-5/16 3/16 3-1/2 6’-6” 13 HANGER APPLICATIONDETAIL A TOLCO FIG. 27B(1) REQUIREDHIGH SIDEOF HANGER APPLICATIONHANGER AND RESTRAINT A TOLCO FIG. 27B(2) REQUIRED The Series 705 Butterfly Valve features a weatherproof actuator housing Approved for indoor or outdoor use, a ductile iron body and disc with EPDM seats. Designed for fire protection services only. Victaulic FireLock Series 705 Butterfly Valve is cULus Listed, LPCB Listed, FM and VdS Approved for 300 psi/2068 kPa service. Contact Victaulic for details of agency approvals. APPROVALS AND LISTINGS Approval/Listing Service Pressures Series 705 Butterfly Valve cULus FM VdS LPCB 2"/50mm up to 300psi/2068kPa n/a up to 300psi/2068kPa up to 300psi/2068kPa 2 1/2"/65mm up to 300psi/2068kPa up to 300psi/2068kPa n/a up to 300psi/2068kPa 76.1mm up to 300psi/2068kPa up to 300psi/2068kPa up to 300psi/2068kPa up to 300psi/2068kPa 3"/80mm up to 300psi/2068kPa up to 300psi/2068kPa up to 300psi/2068kPa up to 300psi/2068kPa 4"/100mm up to 300psi/2068kPa up to 300psi/2068kPa up to 300psi/2068kPa up to 300psi/2068kPa 5"/125mm up to 300psi/2068kPa up to 300psi/2068kPa n/a up to 300psi/2068kPa 139.7mm up to 300psi/2068kPa up to 300psi/2068kPa up to 300psi/2068kPa up to 300psi/2068kPa 6"/150mm up to 300psi/2068kPa up to 300psi/2068kPa up to 300psi/2068kPa up to 300psi/2068kPa 165.1mm up to 300psi/2068kPa up to 300psi/2068kPa n/a up to 300psi/2068kPa 8"/200mm up to 300psi/2068kPa up to 300psi/2068kPa up to 300psi/2068kPa up to 300psi/2068kPa 10"/250mm up to 300psi/2068kPa up to 300psi/2068kPa n/a up to 300psi/2068kPa 12"/300mm up to 300psi/2068kPa up to 300psi/2068kPa n/a up to 300psi/2068kPa 10.81_1 FireLock ® Butterfly Valve SERIES 705 WITH WEATHERPROOF ACTUATOR 10.81IPS CARBON STEEL PIPE – FIRE PROTECTION VALVES JOB/OWNER CONTRACTOR ENGINEER System No. __________________________Submitted By ________________________Spec Sect ____________ Para __________ Location ____________________________Date ________________________________Approved ___________________________ Date ________________________________ www.victaulic.com VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. © 2013 VICTAULIC COMPANY. ALL RIGHTS RESERVED. REV_E MATERIAL SPECIFICATIONS Body: Ductile iron conforming to ASTM A-536, grade 65-45-12 End Face, 2 – 6"/50 – 150 mm: Ductile iron conforming to ASTM A-536, grade 65-45-12 Seal Retainer, 8 – 12"/200 – 300 mm: Ductile iron conforming to ASTM A-536, grade 65-45-12 Coating: Black alkyd enamel Disc: Ductile iron conforming to ASTM A-536, grade 65-45-12, with electroless nickel coating con- forming to ASTM B-733 Seat: • Grade “E” EPDM Stems: 416 stainless steel conforming to ASTM A-582 Stem Seal Cartridge: C36000 brass Bearings: Stainless Steel with TFE lining Stem Seals: EPDM Stem Retaining Ring: Carbon steel Actuator: • 2 - 8"/50 - 200mm: Brass or bronze traveling nut on a steel lead screw, in a ductile iron housing • 10 - 12"/250 - 300mm: Steel worm and cast iron quadrant gear, in a cast iron housing 10.81_2 FireLock ® Butterfly Valve SERIES 705 WITH WEATHERPROOF ACTUATOR 10.81IPS CARBON STEEL PIPE – FIRE PROTECTION VALVES www.victaulic.com VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. © 2013 VICTAULIC COMPANY. ALL RIGHTS RESERVED. REV_E DIMENSIONS – Size Dimensions – Inches/millimeters Size Outside Diameter End to End A B C D E F G DIA H J 2"2.375 4.25 2.28 6.41 ——4.00 4.22 4.50 2.12 60.3 mm 60.3 108.0 57.9 162.8 101.6 107.2 114.3 53.8 2½"2.875 3.77 2.28 7.54 ——4.00 4.22 4.50 1.77 73 mm 73.0 95.8 57.9 191.5 101.6 107.2 114.3 45.0 3.000 3.77 2.28 7.54 ——4.00 4.22 4.50 1.77 76.1 mm 76.1 95.8 57.9 191.5 101.6 107.2 114.3 45.0 3"3.500 3.77 2.53 7.79 ——4.50 4.22 4.50 1.77 88.9 mm 88.9 95.8 64.3 197.9 114.3 107.2 114.3 45.0 4.250 4.63 2.88 8.81 ——5.50 4.22 4.50 2.20 108 mm 108.0 117.6 73.2 223.8 139.7 107.2 114.3 55.9 4"4.500 4.63 2.88 8.81 ——5.50 4.22 4.50 2.20 114.3 mm 114.3 117.6 73.2 223.8 139.7 107.2 114.3 55.9 5.250 5.88 3.35 10.88 ——6.56 6.19 6.30 2.58 133 mm 133.0 149.4 85.1 276.4 166.6 157.2 160.0 65.5 5.500 5.88 3.35 10.88 ——6.56 6.19 6.30 2.58 139.7 mm 139.7 149.4 85.1 276.4 166.6 157.2 160.0 65.6 5"5.563 5.88 3.35 10.88 ——6.56 6.19 6.30 2.58 141.3 mm 141.3 149.4 85.1 276.4 166.6 157.2 160.0 65.5 6.250 5.88 3.84 11.38 0.41 10.4 7.52 6.19 6.30 2.58 159 mm 159.0 149.4 97.5 289.1 —191.0 157.2 160.0 65.5 6.500 5.88 3.84 11.38 —0.41 10.4 7.52 6.19 6.30 2.58 165.1 mm 165.1 149.4 97.5 289.1 191.0 157.2 160.0 65.5 6"6.625 5.88 3.84 11.38 0.41 10.4 7.52 6.19 6.30 1.90 168.3 168.3 149.4 97.5 289.1 —191.0 157.2 160.0 48.3 8"8.625 5.33 5.07 13.53 0.80 1.47 10.00 6.19 8.10 2.33 219.1 mm 219.1 135.4 128.8 343.6 20.3 37.3 254.0 157.2 205.7 59.2 10"10.750 6.40 6.37 15.64 1.41 1.81 12.25 8.10 9.00 —273 mm 273.0 162.6 161.8 397.3 35.8 46.0 311.2 205.7 228.6 12"12.750 6.50 7.36 16.64 2.30 2.80 14.25 8.10 9.00 —323.9 mm 323.9 165.1 186.9 422.7 58.4 71.1 362.0 205.7 228.6 F G E A D ØH B C J F G E A D ØH B C J Note: Optional ½"/15mm tap available. Contact Victaulic for details. 10.81_3 FireLock ® Butterfly Valve SERIES 705 WITH WEATHERPROOF ACTUATOR 10.81IPS CARBON STEEL PIPE – FIRE PROTECTION VALVES www.victaulic.com VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. © 2013 VICTAULIC COMPANY. ALL RIGHTS RESERVED. REV_E PERFORMANCE The chart expresses the frictional resistance of Victaulic Series 705 Butterfly Valve in equivalent feet/ meters of straight pipe. Size Size Nominal Size Inches mm Actual Outside Diameter Inches mm Equiv. Feet/m of Pipe Nominal Size Inches mm Actual Outside Diameter Inches mm Equiv. Feet/m of Pipe 2 2.375 6 6 6.625 14 50 60.3 1.8 150 168.3 4.2 2 ½2.875 6 159 mm 159 mm 14 65 73.0 1.8 4.3 76.1 mm 3.000 6 165.1 mm 6.500 14 76.1 1.8 165.1 4.2 3 3.500 7 8 8.625 16 80 88.9 2.1 200 219.1 4.9 4 4.500 8 10 10.750 18 100 114.3 2.4 250 273.0 5.5 108 mm 108 mm 8 12 12.750 19 2.4 300 323.9 5.8 5 5.563 12 125 141.3 3.7 133 mm 133 mm 12 3.7 139.7 mm 5.500 12 139.7 3.7 10.81_4 FireLock ® Butterfly Valve SERIES 705 WITH WEATHERPROOF ACTUATOR 10.81IPS CARBON STEEL PIPE – FIRE PROTECTION VALVES www.victaulic.com VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. © 2013 VICTAULIC COMPANY. ALL RIGHTS RESERVED. REV_E PERFORMANCE CV values for flow of water at +60°F/+16°C with a fully open valve are shown in the table below. For additional details, contact Victaulic. Formulas for CV Values: Size CV Size CV Size CV Nominal Size Inches mm Actual Outside Diameter Inches mm (Full Open) Nominal Size Inches mm Actual Outside Diameter Inches mm (Full Open) Nominal Size Inches mm Actual Outside Diameter Inches mm (Full Open) 2 2.375 170 5 5.563 1200 8 8.625 340060.3 125 141.3 200 219.1 2 ½2.875 260 133 mm 133 mm 1200 10 10.750 58006573.0 250 273.0 76.1 mm 3.000 260 139.7 mm 5.500 1200 12 12.750 900076.1 139.7 300 323.9 3 3.500 440 6 6.625 18008088.9 150 168.3 4 4.500 820 159 mm 159 mm 1800100114.3 108 mm 108 mm 820 165.1 mm 6.500 1800165.1 Formulas for KV Values: Size KV Size KV Size KV Nominal Size Inches mm Actual Outside Diameter Inches mm (Full Open) Nominal Size Inches mm Actual Outside Diameter Inches mm (Full Open) Nominal Size Inches mm Actual Outside Diameter Inches mm (Full Open) 2 2.375 147 5 5.563 1040 8 8.625 294060.3 125 141.3 200 219.1 2 ½2.875 225 133 mm 133 mm 1040 10 10.750 50206573.0 250 273.0 76.1 mm 3.000 225 139.7 mm 5.500 1040 12 12.750 779076.1 139.7 300 323.9 3 3.500 380 6 6.625 15608088.9 150 168.3 4 4.500 710 159 mm 159 mm 1560100114.3 108 mm 108 mm 710 165.1 mm 6.500 1560165.1 10.81_5 FireLock ® Butterfly Valve SERIES 705 WITH WEATHERPROOF ACTUATOR 10.81IPS CARBON STEEL PIPE – FIRE PROTECTION VALVES www.victaulic.com VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. © 2013 VICTAULIC COMPANY. ALL RIGHTS RESERVED. REV_E SWITCH AND WIRING 1. The supervisory switch contains two single pole, double throw, pre-wired switches. 2. Switches are rated: 10 amps @ 125 or 250 VAC/60 Hz 0.50 amps @ 125 VDC 0.25 amps @ 250 VDC 3. Switches supervise the valve in the “OPEN” position. 4. One switch has two #18 insulated wires per terminal, which permit complete supervision of leads (refer to diagrams and notes below). The second switch has one #18 insulated wire per termi- nal. This double circuit provides flexibility to operate two electrical devices at separate locations, such as an indicating light and an audible alarm, in the area that the valve is installed. 5. A #14 insulated ground lead (green) is provided. Switch #1 = S1 For connection to the supervisory circuit of a UL Listed alarm control panel Switch #2 = S2 Auxiliary switch that may be connected to auxiliary devices, per the authority having jurisdiction S1 {Normally Closed: (2) Blue Common: (2) Yellow S2 {Normally Closed: Blue with Orange Stripe Normally Open: Brown with Orange Stripe Common: Yellow with Orange Stripe CONDUIT ½" NPT CONDUIT CONNECTORS UL LISTEDJUNCTION BOX WIRE NUTS FIRE ALARM CONTROL PANEL SUPERVISORY CIRCUIT N.C.NO.COM. TO END-OF-LINE RESISTOR, OR NEXT INDICATOR BELL OR HORNVOLTAGE SOURCE Switch 1: 2 leads per terminal Switch 2: 1 lead per terminal SWITCH CONTACT RATING: 10A AT 125 AND 250VAC, 0.5A AT 125 VDC, 0.25 AT 250 VDC S1 S2 NOTE: The above diagram shows a connection between the common terminal (yellow – S1 and yellow-with-orange stripe – S2) and the normally closed terminal (blue – S1 and blue-with-orange stripe – S2). In this example, the indicator light and alarm will stay on until the valve is fully open. When the valve is fully open, the indicator light and alarm will go out. Cap off any unused wires (e.g. brown with orange stripe). Only S1 (two leads per terminal) may be connected to the fire alarm control panel. The connection of the alarm switch wiring shall be in accordance with NFPA 72 and the auxiliary switch per NFPA 70 (NEC). 10.81_6 FireLock ® Butterfly Valve SERIES 705 WITH WEATHERPROOF ACTUATOR 10.81IPS CARBON STEEL PIPE – FIRE PROTECTION VALVES www.victaulic.com VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. © 2013 VICTAULIC COMPANY. ALL RIGHTS RESERVED. REV_E WARRANTY Refer to the Warranty section of the current Price List or contact Victaulic for details. This product shall be manufactured by Victaulic or to Victaulic specifications. All products to be installed in accordance with current Victaulic installation/assembly instructions. Victaulic reserves the right to change product specifications, designs and standard equipment without notice and without incurring obligations. NOTE Reference should always be made to the installation sheet included with the valve. Verify you have the latest revision by visiting our website at www.victaulic.com. Further reference can be found in the I-100 Victaulic Field Installation Handbook. INSTALLATION 10.81 FireLock ® Butterfly Valve SERIES 705 WITH WEATHERPROOF ACTUATOR 10.81IPS CARBON STEEL PIPE – FIRE PROTECTION VALVES For complete contact information, visit www.victaulic.com 10.81 5662 REV E UPDATED 04/2013 VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. © 2013 VICTAULIC COMPANY. ALL RIGHTS RESERVED. PRINTED IN USA PAGE 1 OF 4 VSR VANE TYPE WATERFLOW ALARM SWITCH WITH RETARD MFG. #5401146 - REV M 11/15 UL, CUL and CSFM Listed, FM Approved, LPCB Approved, For CE Marked (EN12259-5) / VdS Approved model use VSR-EU Service Pressure: 450 PSI (31 BAR) - UL Flow Sensitivity Range for Signal: 4-10 GPM (15-38 LPM) - UL Maximum Surge: 18 FPS (5.5 m/s) Contact Ratings: Two sets of SPDT (Form C) 10.0 Amps at 125/250VAC 2.0 Amps at 30VDC Resistive 10 mAmps min. at 24VDC Conduit Entrances: Two knockouts provided for 1/2" conduit. Individual switch compartments suitable for dissimilar voltages. Environmental Specifications: • NEMA 4/IP54 Rated Enclosure suitable for indoor or outdoor use with factory installed gasket and die-cast housing when used with appropriate conduit fitting. • Temperature Range: 40°F - 120°F, (4.5°C - 49°C) - UL • Non-corrosive sleeve factory installed in saddle. Service Use: Automatic Sprinkler NFPA-13 One or two family dwelling NFPA-13D Residential occupancy up to four stories NFPA-13R National Fire Alarm Code NFPA-72 • Installation must be performed by qualified personnel and in accordance with all national and local codes and ordinances. • Shock hazard. Disconnect power source before servicing. Serious injury or death could result. • Risk of explosion. Not for use in hazardous locations. Serious injury or death could result. Ordering Information Nominal Pipe Size Model Part Number 2"DN50 VSR-2 1144402 2 1/2"DN65 VSR-2 1/2 1144425 3"DN80 VSR-3 1144403 3 1/2"-VSR-3 1/2 1144435 4"DN100 VSR-4 1144404 5"-VSR-5 1144405 6"DN150 VSR-6 1144406 8"DN200 VSR-8 1144408 Specifications subject to change without notice. Optional: Cover Tamper Switch Kit, stock no. 0090148 Replaceable Components: Retard/Switch Assembly, stock no. 1029030 Waterflow switches that are monitoring wet pipe sprinkler systems shall not be used as the sole initiating device to discharge AFFF, deluge, or chemical suppression systems. Waterflow switches used for this application may result in unintended discharges caused by surges, trapped air, or short retard times. Potter Electric Signal Company, LLC • St. Louis, MO • Phone: 866-956-1211/Canada 888-882-1833 • www.pottersignal.com General Information The Model VSR is a vane type waterflow switch for use on wet sprinkler systems. It is UL Listed for use on a steel pipe; schedules 5 through 40, sizes 2" - 6" and is UL Listed and FM Approved for use on steel pipe; schedules 10 through 40, sizes 2" thru 8" (50 mm thru 200 mm). LPC approved sizes are 2" thru 8" (50 mm thru 200 mm). See Ordering Information chart. The VSR may also be used as a sectional waterflow detector on large systems. The VSR contains two single pole, double throw, snap action switches and an adjustable, instantly recycling pneumatic retard. The switches are actuated when a flow of 10 GPM (38 LPM) or more occurs downstream of the device. The flow condition must exist for a period of time necessary to overcome the selected retard period. Enclosure The VSR switches and retard device are enclosed in a general purpose, die-cast housing. The cover is held in place with two tamper resistant screws which require a special key for removal. A field installable cover tamper switch is available as an option which may be used to indicate unauthorized removal of the cover. See bulletin number 5401103 for installation instructions of this switch. Important: This document contains important information on the installation and operation of the VSR waterflow switches. Please read all instructions carefully before beginning installation. A copy of this document is required by NFPA 72 to be maintained on site. PRINTED IN USA MFG. #5401146 - REV M 11/15 PAGE 2 OF 4 VSR VANE TYPE WATERFLOW ALARM SWITCH WITH RETARD Installation (see Fig. 1) These devices may be mounted on horizontal or vertical pipe. On horizontal pipe they shall be installed on the top side of the pipe where they will be accessible. The device should not be installed within 6" (15 cm) of a fitting which changes the direction of the waterflow or within 24" (60 cm) of a valve or drain. NOTE: Do not leave cover off for an extended period of time. Drain the system and drill a hole in the pipe using a hole saw in a slow speed drill (see Fig. 1). Clean the inside pipe of all growth or other material for a distance equal to the pipe diameter on either side of the hole. Roll the vane so that it may be inserted into the hole; do not bend or crease it. Insert the vane so that the arrow on the saddle points in the direction of the waterflow. Take care not to damage the non-corrosive bushing in the saddle. The bushing should fit inside the hole in the pipe. Install the saddle strap and tighten nuts alternately to required torque (see the chart in Fig. 1). The vane must not rub the inside of the pipe or bind in any way. ADAPTER USE (2) 5180162 ADAPTERS AS SHOWN ABOVE DN50 ONLY ADAPTER 50mm 20mm ±2mm MAX. DWG# 1146-1F Fig. 1 NOTE: For copper or plastic pipe use Model VSR-CF. Retard Adjustment The delay can be adjusted by rotating the retard adjustment knob from 0 to the max setting (60-90 seconds). The time delay should be set at the minimum required to prevent false alarms (Flowing water activates device in one direction only.) DO NOT LEAVE COVER OFF FOR AN EXTENDED PERIOD OF TIME TIGHTEN NUTS ALTERNATELY MOUNT ON PIPE SO ARROW ON SADDLE POINTS IN DIRECTION OF WATERFLOW ROLL PADDLE IN OPPOSITE DIRECTION OF WATERFLOWDIRECTION OF WATERFLOW Hole must be drilled perpendicular to the pipe and vertically centered. Refer to the Compatible Pipe/Installation Requirements chart for size. Correct Incorrect Compatible Pipe/ Installation Requirements Model Nominal Pipe Size Nominal Pipe O.D. Pipe Wall Thickness Hole Size U-Bolt Nuts TorqueLightwallSchedule 10 (UL)Schedule 40 (UL)BS-1387 (LPC)DN (VDS) inch mm inch mm inch mm inch mm inch mm inch mm inch mm inch mm ft-lb n-m VSR-2 2 DN50 2.375 60.3 .065 1.651 0.109 2.77 0.154 3.91 0.142 3.6 0.091 2.3 1.25 + .125/- .062 33.0 ± 2.0 20 27 VSR-2 1/2 2.5 -2.875 73.0 .084 2.134 0.120 3.05 0.203 5.16 ---- VSR-2 1/2 -DN65 3.000 76.1 ------0.142 3.6 0.102 2.6 VSR-3 3 DN80 3.500 88.9 .083 2.108 0.120 3.05 0.216 5.49 0.157 4.0 0.114 2.9 2.00 ± .125 50.8 ± 2.0 VSR-3 1/2 3.5 -4.000 101.6 --0.120 3.05 0.226 5.74 ---- VSR-4 4 DN100 4.500 114.3 .084 2.134 0.120 3.05 0.237 6.02 0.177 4.5 0.126 3.2 VSR-5 5 -5.563 141.3 --0.134 3.40 0.258 6.55 ---- VSR-6 6 DN150 6.625 168.3 .115 2.921 0.134 3.40 0.280 7.11 0.197 5.0 0.157 4.0 VSR-8 8 DN200 8.625 219.1 --0.148 3.76 0.322 8.18 0.248 6.3 0.177 4.5 Do not trim the paddle. Failure to follow these instructions may prevent the device from operating and will void the warranty. Do not obstruct or otherwise prevent the trip stem of the flow switch from moving when water flows as this could damage the flow switch and prevent an alarm. If an alarm is not desired, a qualified technician should disable the alarm system. PRINTED IN USA PAGE 3 OF 4 VSR VANE TYPE WATERFLOW ALARM SWITCH WITH RETARD MFG. #5401146 - REV M 11/15 To remove knockouts: Place screwdriver at inside edge of knockouts, not in the center. DWG 1146-4 Fig. 2 Do not drill into the base as this creates metal shavings which can create electrical hazards and damage the device. Drilling voids the warranty. Fig. 4 Switch Terminal Connections Clamping Plate Terminal Fig. 3 Break out thin section of cover when wiring both switches from one conduit entrance. Testing The frequency of inspection and testing for the Model VSR and its associated protective monitoring system shall be in accordance with applicable NFPA Codes and Standards and/or the authority having jurisdiction (manufacturer recommends quarterly or more frequently). If provided, the inspector’s test valve shall always be used for test purposes. If there are no provisions for testing the operation of the flow detection device on the system, application of the VSR is not recommended or advisable. A minimum flow of 10 GPM (38 LPM) is required to activate this device. Advise the person responsible for testing of the fire protection system that this system must be tested in accordance with the testing instructions. Fig. 6 Mounting Dimensions DWG. 1146-14 3.50 in (89.0 mm) 2.34 in (59.4 mm) PIPE DIA. + 5.25 in (+ 133.4 mm) 5.56 in (141.2 mm)2.00 in (50.8 mm) U-BOLT NUT U-BOLT WASHER PIPE SADDLE PIPE PLASTIC PADDLE U-BOLT NOMINAL PIPE DIA. +1.75 in (+44.5 MM) FOR DN 50 – DN 65 2–2.5 in NOMINAL PIPE DIA. +2.125 in (+54.0 MM) FOR DN 80 – DN 200 3–8 in DWG 1146-15 GREEN GROUND SCREWS Fig. 7 An uninsulated section of a single conductor should not be looped around the terminal and serve as two separate connections. The wire must be severed, thereby providing supervision of the connection in the event that the wire become dislodged from under the terminal. Failure to sever the wire may render the device inoperable risking severe property damage and loss of life. Do not strip wire beyond 3/8" of length or expose an uninsulated conductor beyond the edge of the terminal block. When using stranded wire, capture all strands under the clamping plate. Notes: 1. The Model VSR has two switches, one can be used to operate a central station, proprietary or remote signaling unit, while the other contact is used to operate a local audible or visual annunciator. 2. For supervised circuits, see “Switch Terminal Connections” drawing and warning note (Fig. 4). Fig. 5 Typical Electrical Connections LOAD TO BELLNEUTRAL FROM BELL CONNECTOR EOL (End Of Line Resistor) BELLNEUTRAL FROM BREAKER BREAKER LINE FROM BREAKER NOTE: When connecting to a UL Listed control panel, use the panel’s resistor value for circuit supervision. PRINTED IN USA MFG. #5401146 - REV M 11/15 PAGE 4 OF 4 VSR VANE TYPE WATERFLOW ALARM SWITCH WITH RETARD Removal of Waterflow Switch • To prevent accidental water damage, all control valves should be shut tight and the system completely drained before waterflow detectors are removed or replaced. • Turn off electrical power to the detector, then disconnect wiring. • Loosen nuts and remove U-bolts. • Gently lift the saddle far enough to get your fingers under it. With your fingers, roll the vane so it will fit through the hole while continuing to lift the waterflow detector saddle. • Lift detector clear of pipe. Fig. 8 Retard/Switch Assembly Replacement (See Fig. 8) The Retard/Switch Assembly is field-replaceable without draining the system or removing the waterflow switch from the pipe 1. Make sure the fire alarm zone or circuit connected to the waterflow switch is bypassed or otherwise taken out of service. 2. Disconnect the power source for local bell (if applicable). 3. Identify and remove all wires from the waterflow switch. 4. Remove the (2) mounting screws holding retard/switch assembly to the base. Do not remove the (2) retard housing screws. 5. Remove the retard assembly by lifting it straight up over the tripstem. 6. Install the new retard assembly. Make sure the locating pins on the retard/switch assembly fit into the locating pin bosses on the base. 7. Re-install the (2) original mounting screws. 8. Reconnect all wires. Perform a flow test and place the system back in service. Maintenance Inspect detectors monthly. If leaks are found, replace the detector. The VSR waterflow switch should provide years of trouble-free service. The retard and switch assembly are easily field replaceable. In the unlikely event that either component does not perform properly, please order replacement retard switch assembly stock #1029030 (see Fig. 8). There is no maintenance required, only periodic testing and inspection. DWG# 1146-10 BREAK OUT THIN SECTION OF COVER WHEN WIRING BOTH SWITCHES FROM ONE CONDUIT ENTRANCE. DO NOT REMOVE (2) RETARD HOUSING SCREWS REMOVE (2) ORIGINAL MOUNTING SCREWS HOLDING RETARD/SWITCH ASSEMBLY TO BASE RETARD/SWITCH ASSEMBLY (2) ORIGINAL MOUNTING SCREWS (2) LOCATING PINS (2) LOCATING PIN BOSSES IN BASE BASE data sheet The information contained herein is produced in good faith and is believed to be reliable but is for guidance only. ARGCO and its agents cannot assume liability or responsibility for results obtained in the use of its product by persons whose methods are outside or beyond our control. It is the user's responsibility to determine the suitability of any of the products, methods of use, or preparation prior to use, mentioned in our literature. It is the user's responsibility to observe and adapt such precautions as may be advisable for the protection of personnel and property in the handling and use of any of our products. FOR MORE INFORMATION CALL ARGCO AT 1-800-854-1015 OR LOG ONTO WWW.ARGCO.COM Fire Sprinkler Pressure Gauges 0-300 psi water 0-300 psi air 0-300 psi air/water Application:Fluid medium which does not clog connection port or corrode copper alloy. Specifically designed for the fire sprinkler industry. Size:4” (100 mm) Accuracy ± 3/2/3% of span - 1½" (ASME B40.1 Grade B) Working Range Steady: 3/4 of full scale value Fluctuating: 2/3 of full scale value Short time: full scale value Operating Temperature Ambient: -40°F to 140°F (-40°C to 60°C) Media: max. 140°F (+60°C) Temperature Error Additional error when temperature changes from reference temperature of 68°F (20°C) +0.4% for every 18° F (10°C) rising or falling. Percentage of span. Standard Features Connection Material: copper alloy Lower mount (LM) - not available for 1½" size 1/4" NPT limited to wrench flat area Bourdon Tube:Material: copper alloy C-type Movement:Copper alloy, silicone dampened Dia:White plastic with stop pin - black &red lettering Pointer: Black aluminum Case: Black polycarbonate Approvals UL listed (UL-393) FM approved Standard Scale PSI Window Acrylic, ultrasonically welded to case Standard Series • Type 110.10sp Order Options water air/water air CERTIFICATE OF COMPLIANCE ACCURACY STATEMENT WIKA Instrument Corporation certifies that the products specked herein have been manufactured to the ASME 1340.100 accuracy grade listed. CUSTOMER: ALLIED RUBBER & GASKET CO. 5400 SOUTH 66 STREET FORT SMITH, AR 72903 CUSTOMER P.O. NO.: 26482 ORDER NO.: 865505 ORDER DATE: 9/25/08 CUSTOMER PIN: 6510160 WIKA PIN: 4276176 - Pressure and Temperature Measurement WIKA Instrument Corporation 1000 Wiegand Boulevard Lawrenceville, Georgia 30043 Tei. 770-513-8200 Fax 770-338118 www.wtka.com info@wika.com DESCRIPTION: . 111 _I OSP 4 300P81 114 L AlR/WATER ARGCO GAUGE RANGE(S): 300PSI QUANTITY: 6000 ACCURACY GRADE: +1- 31213% OF SPAN AUTHORIZED SIGNATURE: 4:61°�C"6D DATE: 1/812009 �eC ��5T� E .. RTIFICATE of £OI11lPUANCE AHSIIASR Z O090DI-20Q 00 P O R P % Registered ANSIIASQ Q9001-2000 r err Certlffed IWIKA11 CERTIFICATE OF COMPLIANCE Pressure and Temperature ACCURACY STATEMENT Measurement WIKA instrument Corporation 1 COD Wiegand Boulevard WIKA Instrument Corporation certifies that the products Lawrenceville, Georgia 30043 specified herein have been manufactured to the ASME Tel. 770-513-8200 840.100 accuracy grade listed. Fax 770-338-5118www.wika.cam in€o@aika.com CUSTOMER: ALLIED RUBBER & GASKET CO. 5400 SOUTH 66 STREET FORT SMITH, AR 72903 CUSTOMER P.O. NO.: 26482 ORDER NO.: 865505 ORDER DATE: 9125108 CUSTOMER PIN: 6510161 WIKA PIN: 4276192 DESCRIPTION: 111.10SP 4 30OPSI 114 L WATER ARGCO GAUGE RANGE(S): 30OPSI QUANTITY: 3000 ACCURACY GRADE: +1- 31213% OF SPAN AUTHORIZED SIGNATURE:`�'�` DATE: 1/6/2009 /4�- CERTIFICAT ��1 of COMPLIANCE �y ANSVASQ Q500f-20000 p�' 0RP�� Registered ANSTIASQ Q9001-2000 BELLS PBA-AC & MBA-DC 5400776 - REV Z • 11/17 PAGE 1 OF 2 Potter Electric Signal Company, LLC • St. Louis, MO • Phone: 800-325-3936 • www.pottersignal.com Description These vibrating type bells are designed for use as fire or general signaling devices. They have low power consumption and high decibel ratings. The unit mounts on a standard 4” (101mm) square electrical box for indoor use or on a model BBK-1 or HC-BB weatherproof backbox for outdoor applications. Weatherproof backbox model BBK- 1 or HC-BB, Stock No. 1500001. Notes 1. Minimum dB ratings are calculated from integrated sound pressure measurements made at Underwriters Laboratories as specified in UL Standard 464. UL temperature range is -30° to 150°F (-34° to 66°C) 2. Typical dB ratings are calculated from measurements made with a conventional sound level meter and are indicative of output levels in an actual installation. 3. ULC only applies to MBA DC bells. Technical Specifications Dimensions 6” (150mm), 8” (200mm) and 10” (250mm) Enclosure Cover: Steel Finish: Red Powder Coat Base: non-corrosive composite material All parts have corrosion resistant finishes Model BBK-1 or HC-BB weatherproof backbox (optional) Voltages Available 24VAC 120VAC 12VDC (10.2 to 15.6) Polarized 24VDC (20.4 to 31.2) Polarized Environmental Limitations Indoor or outdoor use (See Note 1) -40° to 150°F (-40° to 66°C) (Outdoor use requires weatherproof backbox.) Termination AC Bells - 4 No. 18 AWG stranded wires DC Bells - Terminal strip Service Use NFPA 13, 72, local AHJ *Specifications subject to change without notice. Features • Listed for indoor and outdoor use • Outdoor use requires BBK-1 or HC-BB weatherproof back box • Indoor use mounts directly to standard 4” box • Low current draw • High dB output • AC and DC models • DC models are motor driven, polarized, and have built in transient protection for supervised alarm circuits • Available in 6”, 8” and 10” sizes In outdoor or wet installations, bell must be mounted with weatherproof backbox, BBK-1 or HC-BB. Standard electrical boxes will not provide a weatherproof enclosure. If the bell and/or assembly is exposed to moisture, it may fail or create an electrical hazard. • Installation must be performed by qualified personnel and in accordance with all national and local codes and ordinances. • Shock hazard. Disconnect power source before servicing. Serious injury or death could result. • Risk of explosion. Not for use in hazardous locations. Serious injury or death could result. R * ULC on MBA-DC Only Size inches (mm) Voltage Model Number Stock Number Current (Max.) Typical dB at 10 ft. (3m) (2) Minimum dB at 10 ft. (3m) (1) 6 (150)12VDC MBA-6-12 1750070 .12A 85 76 8 (200)12VDC MBA-8-12 1750080 .12A 90 77 10 (250)12VDC MBA-10-12 1750060 .12A 92 78 6 (150)24VDC MBA-6-24 1750100 .06A 87 77 8 (200)24VDC MBA-8-24 1750110 .06A 91 79 10 (250)24VDC MBA-10-24 1750090 .06A 94 80 6 (150)24VAC PBA246 1806024*.17A 91 78 8 (200)24VAC PBA248 1808024*.17A 94 77 10 (250)24VAC PBA2410 1810024*.17A 94 78 6 (150)120VAC PBA1206 1806120*.05A 92 83 8 (200)120VAC PBA1208 1808120*.05A 99 84 10 (250)120VAC PBA12010 1810120*.05A 99 86 All DC bells are polarized and have built-in transient protection. * Does not have ULC listing. * 5400776 - REV Z • 11/17 PAGE 2 OF 2 Potter Electric Signal Company, LLC • St. Louis, MO • Phone: 800-325-3936 • www.pottersignal.com BELLS PBA-AC & MBA-DC Wiring Rear View Installation Bell Dimension Inches (mm) Fig 1 Fig 3 2 11/16” (68 mm)DWG# 776-1 10” (250 mm)8” (200 mm)6” (150 mm) 5 3/4” (146 mm) 1 5/8” (41 mm) DWG# 776-2 3 3/8” (86 mm) 4 1/4” (108 mm) 3 3/8” (86 mm) 5” (127 mm) Weatherproof Backbox Dimensions Inches (mm) Fig 2 The bell shall be installed in accordance with NFPA 13, 72, or local AHJ. The top of the device shall be no less than 90” AFF and not less than 6” below the ceiling. 1. Remove the gong. 2. Connect wiring (see Fig. 3). 3. Mount bell mechanism to backbox (bell mechanism must be mounted with the striker pointing down). 4. Reinstall the gong (be sure that the gong positioning pin, in the mechanism housing, is in the hole in the gong). 5. Test all bells for proper operation and observe that they can be heard where required (bells must be heard in all areas as designated by the authority having jurisdiction). MODEL BBK-1 OR HC-BBFailure to install striker down will prevent bell from ringing. NOTES: 1. OBSERVE POLARITY TO RING D.C. BELLS.2. RED WIRES POSITIVE (+).3. BLACK WIRES NEGATIVE (-).4. EOL RESISTOR IS SUPPLIED BY FIRE ALARM CONTROL PANEL. NOTES: 1. WHEN USING A.C. BELLS, TERMINATE EACH EXTRA WIRE SEPERATELY AFTER LAST BELL.2. END-OF-LINE RESISTOR IS NOT REQUIRED ON AC BELLS . NOTES: 1. OBSERVE POLARITY TO RING D.C. BELLS.2. RED WIRES POSITIVE (+).3. BLACK WIRES NEGATIVE (-).4. EOL RESISTOR IS SUPPLIED BY FIRE ALARM CONTROL PANEL. NOTES: 1. WHEN USING A.C. BELLS, TERMINATE EACH EXTRA WIRE SEPERATELY AFTER LAST BELL.2. END-OF-LINE RESISTOR IS NOT REQUIRED ON AC BELLS .