Loading...
2020.0215.FR0006 Material Submittals_ Prairie ESAPR 2017 GFS-520a (Formerly A-58) EXTENDED QUICK RESPONSE AUTOMATIC SPRINKLERS GL SERIES DRY TYPE HORIZONTAL SIDEWALL DESCRIPTION AND OPERATION RECESSED SPRINKLER TEMPERATURE RATING/CLASSIFICATION and COLOR CODING • Water Working Pressure Rating - 175 psi (12 Bars) • Factory tested hydrostatically to 500 psi (34 Bars) • Maximum low temperature glass bulb rating is -67°F (-55°C) • Frame - bronze • Defl ector - brass • Screw - brass • Bulb Seat - brass • Spring - nickel alloy • Seal - tefl on • Retainer - brass • Pin - stainless steel • Torsion Spring - stainless steel • Orifi ce Insert - brass • Bulb - glass with alcohol based solution, 3mm size • 3/4”NPT or 1”NPT • Outer Tube - galvanized steel pipe • Inner Tube - stainless steel TECHNICAL DATA • See reverse side for Approvals and Specifi cations. • Temperature Ratings - 135°F (57°C), 155°F (68°C), 175°F (79°C) 200°F (93°C), 286°F (141°C) SLEEVE & SKIRT SURFACE MOUNT CLASSIFICATION AVAILABLE SPRINKLER TEMPERATURES BULB COLOR N.F.P.A. MAXIMUM CEILING TEMPERATURE ORDINARY INTERMEDIATE HIGH 135°F/155°F 175°F/200°F 286°F 57°C/68°C 79°C/93°C 141°C ORANGE/RED YELLOW/GREEN BLUE 100°F 150°F 225°F 38°C 66°C 107°C The Globe Quick Response GL Series Dry Type Horizontal Sidewall Sprinkler is designed for use in special applications such as freezing environments and conditions where sediment or foreign materials might accumulate in ordinary horizontal pipe nipples. The Globe Quick Response GL Series Dry Type Horizontal Sidewall Sprinkler utilizes a 3mm frangible glass ampule as the thermosensitive element. This provides sprinkler operation approximately six times faster than ordinary sprinklers. At the ampule's rated temperature, the sprinkler opens releasing the bulb seat, causing the inner tube assembly to move, allowing the spring assembly to pivot alongside the inner tube. At this time, water fl ows through the sprinkler and is distributed by the defl ector, in an approved discharge pattern. It can be installed wherever standard spray sprinklers are specifi ed but offers the additional feature of greatly increased safety to life. Quick Response Sprinklers should be used advisedly and under the direction of approv- ing authorities having jurisdiction. The heart of Globe's GL Series sprinkler proven actuating assembly is a hermetically sealed frangible glass ampule that contains a precisely measured amount of fl uid. When heat is absorbed, the liquid within the bulb expands increasing the internal pressure. At the prescribed temperature the internal pressure within the ampule exceeds the strength of the glass causing the glass to shatter. This results in water discharge which is distributed in an approved pattern. APR 2017 GFS-520a (Formerly A-58) NOTE: METRIC CONVERSIONS ARE APPROXIMATE. 1FINISHES AVAILABLE ON SPECIAL ORDER. 2cULus LISTED CORROSION RESISTANT WHEN SPECIFIED ON ORDER. SPECIFICATIONS APPROVALS PRINTED U.S.A. 4077 AIRPARK DRIVE, STANDISH, MICHIGAN 48658 FAX 989-846-9231 www.globesprinkler.com 989-846-4583 1-800-248-0278 GLOBE® PRODUCT WARRANTY Globe agrees to repair or replace any of its own manufactured products found to be defective in material or workmanship for a period of one year from date of shipment. For specifi c details of our warranty please refer to Price List Terms and Conditions of Sale (Our Price List). QUICK RESPONSE AUTOMATIC SPRINKLERS GL SERIES DRY TYPE HORIZONTAL SIDEWALL 1SPRINKLERS SHALL BE LIMITED AS PER THE REQUIREMENTS OF NFPA13 AND ANY OTHER RELATED DOCUMENTS. *HORIZONTAL SIDEWALL STYLE - FM APPROVED 155°F (68°C), 200°F (93°C), AND 286°F (141°C) *RECESSED HORIZONTAL SIDEWALL STYLE - FM APPROVED 155°F (68°C) AND 200°F (93°C) LH: LIGHT HAZARD; OH: ORDINARY HAZARD SIN MODEL NOMINAL “K” FACTOR THREAD SIZE LENGTH FINISHES GL5641 5.6 (80 metric) 1”NPT cULus Variable to 48” FM Variable to 36” Factory Bronze Chrome White Polyester2 Black Polyester1,2 GL5642 5.6 (80 metric) 3/4”NPT GL8141 8.0 (115 metric) 1”NPT STYLE SIN MODEL HAZARD1 135°F (57°C) 155°F (68°C) 175°F (79°C) 200°F (93°C) 286°F (141°C)*FM cULus DEFLECTOR TO CEILING DISTANCE Inches (mm) MIN. DISTANCE BETWEEN SPRINKLERS Feet (Meters) Horizontal Sidewall Recessed Horizontal Sidewall GL5641 LH X X X X X X X 4 (102) to 12 (305) 6 (1.8)GL5642 LH X X X X X --- X GL8141 LH/OH X X X X X --- X "A" 1" MIN. 3/4"NPT 3/4" MIN. 1"NPT 2 1/2" DIA. MIN. HOLE IN WALL TEE FITTING ANSI B16.3 CLASS 155 OR ANSI 16.4 CLASS 125 FACE OF MOUNTING SURFACE CEILING 4" TO 12" 3 1/2" DIA. 3 3/4" MIN. 4 3/4" MAX. FACE OF TEE FITTING TWO PIECE ESCUTCHEON "A" 2 1/2" MIN. 3/4"NPT 2 1/4" MIN. 1"NPT 4" TO 12"CEILING FACE OF MOUNTING SURFACE 3" DIA. 1 1/2" DIA. MIN. HOLE IN WALL TEE FITTING ANSI B16.3 CLASS 155 OR ANSI 16.4 CLASS 125 1/4" FACE OF TEE FITTING TEE FITTING ANSI B16.3 CLASS 155 OR ANSI 16.4 CLASS 125 FACE OF MOUNTING SURFACE "A" 3 1/4" MIN. 3/4"NPT 2 3/4" MIN. 1"NPT 1 1/4" MIN. 2" MAX. 2" DIA. MIN. HOLE IN WALL 2 15/16" DIA.4" TO 12" CEILING FACE OF TEE FITTING CUP RETAINER "A" 1 3/4" MIN. 3/4"NPT 1 1/2" MIN. 1"NPT 1 3/4" DIA. MIN. HOLE IN WALL 3 7/32" DIA. 2 1/2" MIN. 4" MAX. TWO PIECE ESCUTCHEON FACE OF MOUNTING SURFACE FACE OF TEE FITTING TEE FITTING ANSI B16.3 CLASS 155 OR ANSI 16.4 CLASS 125 CEILING4" TO 12" ESCUTCHEON CROSS SECTIONS EXTENDED SLEEVE & SKIRT RECESSED SURFACE MOUNT IMPORTANT INSTALLATION DATA Globe GL Series Dry Pendent Sprinklers should be installed in accordance with the requirements set forth in NFPA 13. These sprinklers are to be installed using a pipe wrench applied to the outer tube. When this is not possible, the proper sprinkler head wrench may be used with extreme care for lengths up to approximately 18”. Excessive force may distort the frame thus destroying the unit. When installed in a wet system extending into a freezing area see chart on Dry Caution Sheet for minimum exposed barrel length to prevent ice plugs. Please refer to our Dry Caution Sheet for further important installation data. ORDERING INFORMATION • Quantity • Model Number • Style • Orifi ce • Temperature • Finishes desired • Quantity - Wrenches - P/N 333010 • Quantity Recessed Wrenches - P/N 337014 • Quantity - Protective Caps - P/N 327109-cap (Friction Fit Recessed) • Escutcheons Desired • “A” Dimension - Distance from face of fi tting to the fi nished ceiling line regardless of escutcheon used. SPECIFY