2020.0217.FR0008 FA20048 PLAN - BLDG 2SHEET REV.DESCRIPTION
FA001 GENERAL SHEET, LEGEND & NOTES
FA101 DEVICE LOCATION VIEWS - FIRST LEVEL
FA102 DEVICE LOCATION VIEWS - SECOND LEVEL
FA103 DEVICE LOCATION VIEWS - THIRD LEVEL
FA501 SCHEDULES & RISER DIAGRAMS
FA601 PRODUCT TYPICALS
FA801 POWER CALCULATIONS
FA901 PRODUCT SHEETS
FA902 PRODUCT SHEETS
FIRE ALARM
CONSTRUCTION DOCUMENT SET
SHEET INDEX
SMITHFIRE SYSTEMS INC.FIRE1106 54TH AVE ETACOMA, WA 98424(253) 926-1880SMITHFS861RSCONSTRUCTION SET
DESIGNER:
ISSUE DATE:
SYSTEM:
FIRE ALARM
SHEET:
GENERAL SHEETLEGEND & NOTES
FA001DATEISSUE LOG:INT DESCRIPTION15025 TAHHOMA BLVD SEWYNDSTONE APARTMENTSBLDG #2YELM, WA 98597PARCEL #21724420300SHEET NAMING CONVENTION
SHEET DESCRIPTION
FA0XX GENERAL SHEET, LEGEND & NOTES
FA1XX DEVICE LOCATION VIEWS - FIRST FLOOR
FA2XX ELEVATION VIEWS
FA3XX SECTION VIEWS
FA4XX LARGE SCALE VIEWS
FA5XX SCHEDULES & RISER DIAGRAMS
FA6XX PRODUCT TYPICALS
FA7XX DEVICE DETAILS
FA8XX POWER CALCULATIONS
FA9XX PRODUCT SHEETS
IDENTIFIERS
TYPE DESCRIPTION
DEVICE IDENTIFIER - EXISTING, ADD, REPLACE, MOVE, DEMO
POINT OF PROTECTION IDENTIFIER / TYPE REFERENCE
REVISION IDENTIFIER
CABLE ID - SEE CABLE LEGEND
SHEET ID - SHEET DETAIL "A", "B", "C" / SHEET #XXXX
X:XX:XXX
XX
XX
XX
XXXXXX
CABLE LEGEND
ID AWG COND SHEILD CLASS ID AWG SHEILD CLASS
A 16 2 N FPLR AA
B 16 4 N FPLR BB
C 16 2 N FPLP CC
D 16 4 N FPLP DD
E 14 2 N FPLR EE
F 14 4 N FPLR FF
G 14 2 N FPLP GG
H 14 4 N FPLP HH
I 12 2 N FPLR II
J 12 4 N FPLR JJ
K 12 2 N FPLP KK
L 12 4 N FPLP LL
M 16 2 N TFFN MM
N 16 4 N TFFN NN
O 16 2 N THWN OO
P 16 4 N THWN PP
Q QQ
U UU
R RR
S SS
T TT
U UU
V VV
X XX
Y YY
Z ZZ
SHEET INDEX
SHEET INDEX
THE SCOPE OF THIS PROJECT IS TO INSTALL A NEW FIRE ALARM CONTROL PANEL, NOTIFICATION, AND INITIATING DEVICES FOR THE PURPOSE
OF NEW CONSTRUCTION.
SYSTEM CODES
INTERNATIONAL BUILDING CODE (IBC 2015 EDITION)
INTERNATIONAL FIRE CODE (IFC 2015 EDITION)
NATIONAL FIRE PROTECTION ASSOCATION (NFPA 70 2011 EDITION)
NATIONAL FIRE PROTECTION ASSOCIATION (NFPA 72 2013 EDITION)
NATIONAL FIRE PROTECTION (NFPA 101 2011 EDITION)
ADA INTERNATIONAL CODE ANSIE 117.1
UNDERWRITERS LABORATORIES, INCORPORATED
YELM MUNICIPAL CODES
USE & OCCUPANCY CLASSIFICATION
ASSEMBLY (A)A-1 A-2 A-3 A-4 A-5
BUSINESS (B)
EDUCATIONAL (E)
FACTORY & INDUSTRIAL (F)F-1 F-2
HIGH HAZZARD (H)H-1 H-2 H-3 H-4 H-5
INSTITUTIONAL (I)I-1 I-2 I-3 I-4
MERCANTILE (M)
RESIDENTIAL (R)R-1 R-2 R-3 R-4
STORAGE (S)S-1 S-2 S-3 S-4
UTILITY & MISCELLANEOUS (U)
BUILDING CONSTRUCTION TYPES
TYPE I
TYPE II
TYPE III
TYPE IV
TYPE V
TYPE I-A TYPE I-B
TYPE II-A TYPE II-B
TYPE III-A TYPE III-B
TYPE V-A TYPE V-B
AUTOMATIC SPRINKLER PROTECTION
NO PARTIAL FULL
GENERAL NOTES
1. INSTALLATION SHALL BE ACCOMPLISHED IN STRICT COMPLIANCE WITH NFPA, LOCAL, AND STATE AHJ'S, NEC, AND CONTRACT DRAWINGS.
2. AS-BUILT DRAWINGS ARE REQUIRED AT THE TIME OF AHJ ACCEPTANCE. SMITH FIRE SYSTEMS REQUIRES ELECTRICAL RED LINES WITH IN TWO WEEKS PRIOR TO
3. AGREEMENT AND CONFIRMATION OF ALL MILESTONE EVENTS WILL BE MADE WITH SMITH FIRE SYSTEMS PROJECT MANAGER. ALL SMITH FIRE SYSTEMS FIELD
SERVICES MUST BE SCHEDULED WITH SMITH FIRE SYSTEMS PROJECT MANAGER WITH A MINIMUM OF TEN BUSINESS DAY'S ADVANCE NOTICE.
4. A SET OF INSTALLATION AS-BUILT DRAWINGS SHOWING ACTUAL CONDUIT AND CONDUCTOR ROUTES SHALL BE KEPT BY PROJECT FOREMAN FOR USE
BY SMITH FIRE SYSTEMS ALARM TECHNICIAN.
5. FIRE ALARM CONTROL PANEL SHALL NOT BE ENERGIZED WITHOUT THE PRESENCE OF A SMITH FIRE SYSTEMS ALARM TECHNICIAN.
PRIOR TO AHJ TEST'S.
6. THE FIRE ALARM SYSTEM SHALL BE MONITORED BY A UNDERWRITERS LISTED MONITORING STATION BEFORE AHJ'S TEST.
7. WIRE ROUTING IS DIAGRAMMATIC IN NATURE ONLY AND NOT INTENDED FOR ACTUAL CONDUIT ROUTING.
8. ALL CONDUIT SIZING AND ROUTING BY ELECTRICAL CONTRACTOR PER NEC AND AHJ.
9. NO LINE VOLTAGE IN SAME CONDUIT AS POWER LIMITED FIRE ALARM CABLE.
10. VERIFY ALL LOCATIONS OF DEVICES WITH ELECTRICAL AND ARCHITECTURAL PLANS. SCALE AND PLACE ALL DEVICES PER ELECTRICAL
AND ARCHITECTURAL PLANS.
11. FIELD VERIFY WATERFLOW SWITCHES, TAMPER SWITCHES, PRESSURE SWITCHES, SMOKE DAMPERS, AND DUCT DETECTOR LOCATIONS.
12. FIELD VERIFY ALL WIRING LOCATIONS AND REQUIREMENTS FOR HVAC AND FAN CONTROL.
13. SMOKE DETECTORS SHALL NOT BE LOCATED WITH IN 36" OF ANY AIR DIFFUSER.
14. WALL MOUNTED AUDIBLE/VISUAL APPLIANCES SHALL BE MOUNTED IN SUCH THAT THE ENTIRE LENS IS NOT LESS THAN 80" AND NOT GREATER THE
96" ABOVE FINISHED FLOOR.
15. THE OPERABLE PART OF EACH MANUAL FIRE ALARM BOX SHALL BE NOT LESS THAN 3'-6" AND NOT MORE THAN 4'-6" ABOVE THE FINISHED FLOOR.
16. NO DETECTOR SHALL BE INSTALLED UNTIL AFTER FINAL CONSTRUCTION CLEAN-UP. DETECTORS THAT HAVE BEEN INSTALLED PRIOR TO CLEAN-UP MUST BE
CLEANED OR REPLACED AND WILL BE INVOICED ON A TIME AND MATERIAL BASES.
17. A DEDICATED BRANCH CIRCUIT OF ONE OF THE FOLLOWING SHALL SUPPLY PRIMARY POWER.
A) COMMERCIAL LIGHT AND POWER.
B) AN ENGINE-DRIVEN GENERATOR OR EQUIVALENT WHERE A PERSON SPECIFICALLY TRAINED IN ITS OPERATIONS IS ON DUTY AT ALL TIMES.
C) AN ENGINE-DRIVEN GENERATOR OR EQUIVALENT ARRANGED FOR COGENERATION WITH COMMERCIAL LIGHT AND POWER WHERE A PERSON SPECIFICALLY
TRAINED IN ITS OPERATION IS ON DUTY AT ALL TIMES.
18. ALL CIRCUITS WILL BE PROPERLY TAGGED AND TESTED FOR OPENS, SHORTS, GROUNDS, AND PROPER "END-TO-LINE" RESISTANCE. EACH CIRCUITS METER
READING MUST BE DOCUMENTED AND PRESENTED TO SMITH FIRE SYSTEMS ALARM TECHNICIAN UPON ARRIVAL ONSITE FOR STARTUP AND CHECKOUT.
19. NO TAPPING OF SIGNALING OR INITIATING ZONE CIRCUITS ARE ALLOWED. T-TAPPING OF STYLE 4 ADDRESSABLE CIRCUITS IS ALLOWED PROVIDING A SPLICE
IS PROFESSIONALLY INSTALLED, POLARITY IS OBSERVED, AND SHIELDS ARE CONTINUOUS AND FREE OF GROUNDS. SHIELDS MUST BE TERMINATED AT
THE FIRE ALARM CONTROL PANEL ONLY. CABLE SHIELDS SHALL BE SPLICED TOGETHER AT EVERY JUNCTION BETWEEN THE FIRE ALARM CONTROL PANEL AND
THE LAST DEVICE ON EACH CABLE RUN. SHIELDS AND OTHER FIRE ALARM CONDUCTORS (EXCEPT POWER GROUNDS) SHALL BE INSULATED AND
COMPLETELY FREE FROM CONDUIT OR EARTH GROUNDS. SHIELDS WILL BE TIED TO GROUND ONLY AT THE FIR ALARM CONTROL PANEL.
DRAWING ACCEPTANCE
THIS DRAWING IS TO BE USED FOR THE PURPOSE OF PLACING AND LOCATING SMITH FIRE SYSTEMS FIRE ALARM DEVICES AND IS NOT BE USED FOR ANY OTHER
PURPOSES.
RECORD DRAWINGS
ALL WORK PERFORMED IN THE FIELD SHALL BE ACCURATELY RECORDED ON THESE DRAWINGS AND RETURNED TO SMITH FIRE SYSTEMS CORPORATE OFFICE.
MONITORING COMPANY
ALARM CENTER
4500 3RD AVE, LACEY, WA 98503
ACCOUNT# TBD
QTY SYMBOL DEVICE DESCRIPTION
1 FIRE ALARM CONTROL PANEL
FM-200 CLEAN AGENT PANEL
PRE-ACTION CONTROL PANEL
VOICE EVACUATION CONTROL PANEL
1 FIRE SIGNAL EXPANDER
REMOTE ANNUNCIATOR
SUBSCRIBER TERMINAL UNIT
1 AES RADIO
FIRE ALARM - PANELS
QTY SYMBOL DEVICE DESCRIPTION
WALL STROBE
WALL STROBE WEATHERPROOF
CEILING STROBE
CEILING STROBE WEATHERPROOF
WALL HORN-STROBE
1 WALL HORN-STROBE WEATHERPROOF
CEILING HORN-STROBE
CEILING HORN-STROBE WEATHERPROOF
WALL HORN
CEILING HORN
WALL HORN-STROBE LOW FREQUENCY
62 WALL MINI HORN LOW FREQUENCY
CEILING SPEAKER
WALL SPEAKER/STROBE
CEILING SPEAKER/STROBE
WALL CHIME
CEILING CHIME
WALL BUZZER
CEILING BUZZER
BELL
FIRE ALARM - NOTIFICATION DEVICES
QTY SYMBOL DEVICE DESCRIPTION
1 SMOKE DETECTOR
SMOKE DETECTOR ABOVE CEILING
SMOKE DETECTOR BELOW CEILING
DUCT SMOKE DETECTOR
DUCT SMOKE DETECTOR REMOTE TEST SWITCH
SMOKE BEAM TRANSMITTER
SMOKE BEAM RECEIVER
135° FIXED TEMP HEAT DETECTOR
135° RATE OF RISE HEAT DETECTOR
194° FIXED TEMP HEAT DETECTOR
194° RATE OF RISE HEAT DETECTOR
190° FIXED TEMP HEAT DETECTOR
194° LINE TYPE HEAT DETECTOR
FIRE ALARM - DETECTORS
QTY SYMBOL DEVICE DESCRIPTION
13 MANUAL PULL STATION
MINI MONITOR MODULE
MONITOR MODULE
2 TWO POINT POINT MONITOR MODULE
FOUR POINT MONITOR MODULE
RELAY MODULE
CONTROL RELAY MODULE
INPUT MODULE
FOUR POINT INPUT/OUTPUT RELAY MODULE
ISOLATION MODULE
NOTIFICATION MODULE
SYNC MODULE
DOOR HOLDER
FIRE ALARM - MODULE / RELAY
QTY SYMBOL DEVICE DESCRIPTION
SPRINKLER RISER
WATER GONG BELL
E WATERFLOW SWITCH
PRESSURE SWITCH
E TAMPER SWITCH
FIRE ALARM - SPRINKLER
QTY SYMBOL DEVICE DESCRIPTION
ELEVATOR STATUS RECALL
FIRE FIGHTERS PHONE
FIRE FIGHTERS PHONE JACK
FIRE FIGHTERS HANDSET
FIRE ALARM - FIREMAN'S PHONE
QTY SYMBOL DEVICE DESCRIPTION
KITCHEN HOOD
JUNCTION BOX
5 BATTERY
FIRE ALARM - MISCELLANEOUS
QTY SYMBOL DEVICE DESCRIPTION
NURSE CALL
CCTV CAMERA
CCTV CAMERA WEATHERPROOF
DOOR BELL
DOOR BUZZER
DOOR CHIME
SECURITY ELECTRONIC DOOR OPENER
SECURITY ELECTRONIC DOOR STRIKE
INTERCOM UNIT
MASTER INTERCOM & DIRECTORY
MOTION DETECTOR
SECURITY DOOR ALARM MAG LOCK
SECURITY CARD READER
SECURITY CARD READER WEATHERPROOF
SECURITY CONTROL UNIT
SECURITY DOOR PANEL
SECURITY DOOR CONTACTS
SECURITY EXIT PUSH BUTTON
SECURITY KEY PAD
ACCESS / SECURITY / CAMERA - DEVICES
X
PROJECT #:
INSTALLATION COMPANY
SMITH FIRE SYSTEMS
1106 54TH AVE E, TACOMA, WA 98424
JEF MARQUEZ
7/9/20
FA20048
TAHOMA BLVD SE
DURANT ST SEWORK AREA
A2-6A2-7A2-8
A2-11A2-10
A2-9
A1-11A1-9
A1-8
A1-12
A1-10
A1-1
A1-2A1-3
A1-4
A1-5
K
K
K
K
K
K
UP TO2ND FLRSLC
C
C
C
A2-14
A2-13
A2-12 K
A2-3
A2-4
A5-5
A2-15
K
A2-2
EOL
A1-6
A1-7
EOL
TOFSE/NAC-A1
K
RISER
PIV WATERFLOW
CONTROL VALVE
K
K
K
C
C
C
FIELD VERIFY:
INSTALL WEATHERPROOF HORN/STROBEON BUILDING FACING FOREMOST OF STREET.
TOFSE/NAC-A2
A2-175cd SMITHFIRE SYSTEMS INC.FIRE1106 54TH AVE ETACOMA, WA 98424(253) 926-1880SMITHFS861RSKEY PLAN
KEY PLAN
N.T.S.
N
DEVICE LOCATION VIEWS - FIRST LEVELASCALE: 1/8" = 1'-0"
FA101
CONSTRUCTION SET
DESIGNER:
ISSUE DATE:DATEISSUE LOG:INT DESCRIPTION
PROJECT #:
SYSTEM:
FIRE ALARM
SHEET:
DEVICELOCATION VIEWS
JEF MARQUEZNICET LEVEL IVFIRE ALARM SYSTEMSCERT #119820EXP 7/1/22 15025 TAHHOMA BLVD SEWYNDSTONE APARTMENTSBLDG #2YELM, WA 98597PARCEL #21724420300JEF MARQUEZ
7/9/20
FA20048
DN
UP
UP
UP
A4-4A4-5A4-6
A4-9A4-8
A4-7
A3-9A3-7
A3-6
EOLA3-8
A3-1
A3-2A3-3
A3-4
A3-5 DN TOFSE/NAC-A4
K
K
K
K
K
K
K
UP TO3RD FLRSLC
C
C
RESTROOM
RESTROOM
RSTM
RSTM
KITCHEN
LIVING RM
LIVING RM
RSTM
RSTM
CLST
CLST
RESTROOM
RESTROOM
RESTROOM
RESTROOM
RESTROOM
RESTROOM
RESTROOM
RESTROOMLIVING RM
LIVING RM
LIVING RM
LIVING RM
RSTM
RSTM
RSTM
RSTM
RSTM
RSTM
KITCHEN
KITCHEN
KITCHEN
KITCHEN
KITCHEN
LIVING RMRESTROOM RESTROOM
KITCHEN
KITCHEN
RSTM
RSTM
RSTM
RSTM
LIVING RM
RESTROOM RESTROOM
A4-12
A4-11A4-10 K
A4-1A4-2
A4-3
EOL
DN TOFSE/NAC-A3
K
A3-10
K
K
DN TO1ST FLRSLC
C
C
TAHOMA BLVD SE
DURANT ST SEWORK AREA SMITHFIRE SYSTEMS INC.FIRE1106 54TH AVE ETACOMA, WA 98424(253) 926-1880SMITHFS861RSKEY PLAN
KEY PLAN
N.T.S.
DEVICE LOCATION VIEWS - SECOND LEVELBSCALE: 1/8" = 1'-0"
FA102N
CONSTRUCTION SET
DESIGNER:
ISSUE DATE:DATEISSUE LOG:INT DESCRIPTION
PROJECT #:
DEVICELOCATION VIEWS
SYSTEM:
SHEET:
FIRE ALARM
JEF MARQUEZNICET LEVEL IVFIRE ALARM SYSTEMSCERT #119820EXP 7/1/22 15025 TAHHOMA BLVD SEWYNDSTONE APARTMENTSBLDG #2YELM, WA 98597PARCEL #21724420300JEF MARQUEZ
7/9/20
FA20048
DN
1-11-2
1-3
1-4
1-5
1-8
1-9
1-10
1-11
1-12
DN TOFACP/NAC-1
K
K
K
C
C
LIVING RM LIVING RM
LIVING RM LIVING RM RESTROOMRESTROOM
RESTROOMRESTROOM
RSTM
RSTM
RSTM
RSTM
KITCHEN
KITCHEN
KITCHEN
KITCHEN
BONUS
BONUS
BONUS
BONUS
1-7
1-6
1-13
1-14
DN TO2ND FLRSLC
C
EOL
TAHOMA BLVD SE
DURANT ST SEWORK AREA SMITHFIRE SYSTEMS INC.FIRE1106 54TH AVE ETACOMA, WA 98424(253) 926-1880SMITHFS861RSKEY PLAN
KEY PLAN
N.T.S.
DEVICE LOCATION VIEWS - THIRD LEVELCSCALE: 1/8" = 1'-0"
FA103N
CONSTRUCTION SET
DESIGNER:
ISSUE DATE:DATEISSUE LOG:INT DESCRIPTION
PROJECT #:
DEVICELOCATION VIEWS
SYSTEM:
SHEET:
FIRE ALARM
JEF MARQUEZNICET LEVEL IVFIRE ALARM SYSTEMSCERT #119820EXP 7/1/22 15025 TAHHOMA BLVD SEWYNDSTONE APARTMENTSBLDG #2YELM, WA 98597PARCEL #21724420300JEF MARQUEZ
7/9/20
FA20048
.108mA
1-1
.108mA
1-2
.108mA
1-3
.108mA
1-4
.108mA
1-5
.108mA
1-6
FACP / NAC-2: FSE TRIGGER
WATERFLOW
CONTROL VALVE
PIV
C
K
K
K
K
K
K
K
.108mA
A1-1
.108mA .108mA .108mA .108mA .108mA .108mA .108mA
A1-2 A1-3 A1-4 A1-4 A1-5 A1-6 A1-7
.108mA .108mA .108mA .108mA
A1-8 A1-9 A1-10 A1-11
.108mA
A1-12
A2-175cd
.121mA .108mA .108mA .108mA .108mA .108mA .108mA .108mA
A2-2 A2-3 A2-4 A2-4 A2-5 A2-6 A2-7
.108mA
A2-8
.108mA .108mA .108mA .108mA .108mA
A2-9 A2-10 A2-11 A2-12 A2-13
.108mA
A2-14
.108mA
A2-15
EOL
EOL
.108mA
A3-1
.108mA .108mA .108mA .108mA .108mA .108mA .108mA
A3-2 A3-3 A3-4 A3-4 A3-5 A3-6 A3-7
.108mA .108mA .108mA
A3-8 A3-9 A3-10
.108mA
A4-1
.108mA .108mA .108mA .108mA .108mA .108mA .108mA
A4-2 A4-3 A4-4 A4-4 A4-5 A4-6 A4-7
.108mA .108mA .108mA .108mA
A4-8 A4-9 A4-10 A4-11
.108mA
A4-12
EOL
EOL
.108mA
1-7
.108mA
1-8
.108mA
1-9
.108mA
1-10
.108mA
1-11
.108mA
1-12
.108mA
1-13
.108mA
1-14
EOL
FACP / NAC-3: EMPTY
FACP / NAC-4: EMPTY SMITHFIRE SYSTEMS INC.FIRE1106 54TH AVE ETACOMA, WA 98424(253) 926-1880SMITHFS861RSSCHEDULES & RISER DIAGRAMSA
FA501
SCHEDULES - SEQUENCE OF OPERATIONS MATRIXASYSTEM TROUBLEDISPLAY OF AN ALARM EVENT AT THE FACP
DISPLAY OF A SUPERVISORY EVENT AT THE FACP
DISPLAY OF A TROUBLE EVENT AT THE FACP
DISPLAY OF AN ALARM EVENT REMOTE ANNUNCIATOR
DISPLAY OF A SUPERVISORY EVENT REMOTE ANNUNCIATOR
DISPLAY OF A TROUBLE EVENT REMOTE ANNUNCIATOR
TRANSMIT AN ALARM SIGNAL TO THE CENTRAL STATION
TRANSMIT A SUPERVISORY SIGNAL TO THE CENTRAL STATION
TRANSMIT A TROUBLE SIGNAL TO THE CENTRAL STATION
ACTIVATE ALL AUDIBLE & VISIBLE DEVICES
INITIATE ELEVATOR RECALL TO UPPER LEVEL
INITIATE ELEVATOR RECALL TO LOWER LEVEL
ILLUMINATE FIREMANS HAT POST INDICATORTAMPER SWITCHHIGH-LOW AIRDRY WATERFLOWWET WATFLOWUPPER LEVEL ELEVATOR LOBBY SMOKELOWER LEVEL ELEVATOR LOBBY SMOKEELEVATOR MACHINE RM SMOKEDUCT SMOKE DETECTORSMOKE DETECTORMANUAL PULL STATIONCONSTRUCTION SET
DESIGNER:
ISSUE DATE:DATEISSUE LOG:INT DESCRIPTION
PROJECT #:
SYSTEM:
FIRE ALARM
SHEET:
SCHEDULES &RISER DIAGRAMS15025 TAHHOMA BLVD SEWYNDSTONE APARTMENTSBLDG #2YELM, WA 98597PARCEL #21724420300JEF MARQUEZ
7/9/20
FA20048
SMITHFIRE SYSTEMS INC.FIRE1106 54TH AVE ETACOMA, WA 98424(253) 926-1880SMITHFS861RSFA601
CONSTRUCTION SET
DESIGNER:
ISSUE DATE:
SYSTEM:
FIRE ALARM
SHEET:
PRODUCTTYPICALSDATEISSUE LOG:INT DESCRIPTION
PROJECT #:
FIRE ALARM - PHONE CONNECTION
FIRE ALARM - DCVA TAMPER SWITCHES
TO WALL TRANSITION AND OPEN WIRING
FIRE ALARM - POWER DISCONNECT
FIRE ALARM - DROP CEILING & J BOX
FIRE ALARM - OS&Y TAMPER GATE VALVE
RJ CORD
RJ 31X BLOCK
TO PHONES
FIRE ALARM CONTROL PANEL SECURITY CONTROL PANEL
RJ CORD
PRIMARY PORT
SECONDARY PORT
PRIMARY PORT
GRN
BLK
RED
YLW
DMARCLINE
LINE
CONDUIT
FIRE ALARM - CEILING
JUNCTION BOX
SQUARE
JUNCTION BOX
OTCTAGON
OR
NO STAPLESWIRE TIEORWIRE HANGER FIRE ALARMCONDUCTOR
WEATHERPROOF J-BOXWITH ELECTRICALLY SUPERVISEDCOVER TAMPER
1/2" WEATHERPROOF BOX SUPPORTARLINGTON OR EQUIVALENT
1/2" X 36" RIGID CONDUIT
WEATHERPROOF1/2" FLEX CONDUIT
OS&Y TAMPERSWITCH
SCHEDULE 80 PVCOR RIGID CONDUIT18" & 24"
SCHEDULE 40 PVC OR RIGID CONDUIT4S J-BOXGROUND LINE
FIRE ALARM CONTROL PANEL
DISTRIBUTION PANEL
CONDUIT
DEDICATED LOCKEDCIRCUIT BREAKER
DRAINOUTLET
WATERFLOWSWITCH
SPRINKLERRISER
WALL
FDC
4S BOXW/ COVER
1/2" FLEXCONDUIT
OS&YCONTROLVALVE
CHECK VALVE
TAMPERSWITCH
1/2" FLEXCONDUIT
CEILING
FLOOR
IF TOTAL HEIGHT IS LESS THAN90", MOUNT 6" FROM CEILING
NOT LESS THAN 90" AFF
NFPA 72 2013, 18.4.8.1WALL MOUNTED APPLIANCES SHALL HAVE THEIR TOPSABOVE THE FINISHED FLOORS AT HEIGHTS OF NOT LESSTHAN 90" AND BELOW THE FINISHED CEILINGS ATDISTANCES OF NOT LESS THAN 6".
CEILING
FLOOR
IF TOTAL HEIGHT IS LESS THAN90", MOUNT 6" FROM CEILING
NOT LESS THAN 80" AFF
NFPA 72 2013, 18.5.5.1WALL MOUNTED APPLIANCES SHALL BE MOUNTEDSUCH THAT THE ENTIRE LENS IS NOT LESS THAN 80"AND NOT GREATER THAN 96" ABOVE THE FINISHEDFLOOR.
BUT NOT GREATER THAN 96" AFF
CEILING
FLOOR
NOT LESS THAN 42" AFF
NFPA 72 2013, 17.14.5THE OPERABLE PART OF A MANUALLY ACTUATEDALARM INITIATING DEVICE SHALL BE NOT LESS THE42" AND NOT MORE THAN 48" FROM THE FINISHED FLOOR.
FIRE
NOT MORE THAN 48" AFF
CEILING
FLOOR
NFPA 72 2013, 17.6.3.1.3.1DETECTORS SHALL BE LOCATED ON THE CEILING NOTLESS THAN 4" FROM THE SIDEWALL OR ON THESIDEWALLS BETWEEN 4" AND 12" FROM THE CEILING.
NO LESS THAN 4"
NO LESS THAN 4"NO MORE THAN 12"
CEILING
FLOOR
NFPA 72 2013, A.17.7.4.1DETECTORS SHALL NOT BE LOCATED INDIRECT AIRFLOW OR CLOSER THAN 36" FROM AN AIRSUPPLY DIFFUSER OR RETURN AIR OPENING.
NO LESSTHAN 36"
FIRE ALARM - STROBE MOUNTING FIRE ALARM - PULL STATION MOUNTING FIRE ALARM - SMOKE & HEAT MOUNTING
FIRE ALARM - HORN MOUNTINGA
B C D
E F G
H I J 15025 TAHHOMA BLVD SEWYNDSTONE APARTMENTSBLDG #2YELM, WA 98597PARCEL #21724420300JEF MARQUEZ
7/9/20
FA20048
SMITHFIRE SYSTEMS INC.FIRE1106 54TH AVE ETACOMA, WA 98424(253) 926-1880SMITHFS861RSPOWER CALCULATIONSA
FA801
CONSTRUCTION SET
DESIGNER:
ISSUE DATE:DATEISSUE LOG:INT DESCRIPTION
PROJECT #:
POWERCALCULATIONS
SYSTEM:
FIRE ALARM
SHEET:15025 TAHHOMA BLVD SEWYNDSTONE APARTMENTSBLDG #2YELM, WA 98597PARCEL #21724420300JEF MARQUEZ
7/9/20
FA20048
SMITH FIRE SYSTEMS INC.
FIRE
1106 54TH AVE E
TACOMA, WA 98424
(253) 926-1880
SMITHFS861RSPRODUCT DATA SHEETSAFA901CONSTRUCTION SETDESIGNER:ISSUE DATE:SYSTEM:FIRE ALARMSHEET:PRODUCTDATA SHEETSDATE
ISSUE LOG:
INT DESCRIPTIONPROJECT #:15025 TAHHOMA BLVD SE
WYNDSTONE APARTMENTS
BLDG #2
YELM, WA 98597
PARCEL #21724420300JEF MARQUEZ7/9/20FA20048
SMITH FIRE SYSTEMS INC.
FIRE
1106 54TH AVE E
TACOMA, WA 98424
(253) 926-1880
SMITHFS861RSPRODUCT DATA SHEETSBFA902CONSTRUCTION SETDESIGNER:ISSUE DATE:SYSTEM:FIRE ALARMSHEET:PRODUCTDATA SHEETSDATE
ISSUE LOG:
INT DESCRIPTIONPROJECT #:15025 TAHHOMA BLVD SE
WYNDSTONE APARTMENTS
BLDG #2
YELM, WA 98597
PARCEL #21724420300JEF MARQUEZ7/9/20FA20048