IMPUTE DEVICES OR ACTIONS
SMOKE DETECTOROUTPUT DEVICES OR ACTIONSALARM LED ACTIVATESFACP FARAP DISPLAYSUPERVISORY LED ACTIVATESTROUBLE LED ACTIVATESPIEZO ACTIVATESALARM WITH POINT ID TRANSMITTEDAES COMMUNICATORALARM INITIATING DEVICES
PULLSTATION
WATERFLOW SWITCH
SPRINKER SUPERVISORY SWITCHES
HVAC SUPERVISORY CONDITIONS
SUPERVISORY INITIATING DEVICES
DRILL BUTTON
FACP DISPLAY / KEYPAD
FUNCTION 2 KEY
FUNCTION 1 KEY
FUNCTION 3 KEY
FUNCTION 4 KEY
SYSTEM COMPONIT
TROUBLE CONDITIONS
NOTIFICATTION CUIRCIT
DEVICE OR MODULE
AC / BATTERY SUP. WITH POINT ID TRANSMITTEDTROUBLE WITH POINT ID TRANSMITTEDGENERAL ALARM NOTIFICATIONNOTIFICATION CIRCUITSAUXILIARY CONTROLSHVAC SHUT DOWNFIRE DAMPERS CLOSEEXTERIOR STROBE ONLYWATERFLOW BELLELEVATOR SHUNT HEAT DETECTOR
FIRE ALARM CONTROL UNIT-
SYMBOL LEGEND
FACP
M
FAPS
F
FIRE ALARM POWER SUPPLY -
MANUAL PULL STATION -
SMOKE DETECTOR - SYSTEM SENSOR - 2WB
SMOKE DETECTOR
MONITOR MODULE -
CEILING MOUNT HORN STROBE - SYSTEM
SENSOR - SS PC2RL
CEILING MOUNT STROBE - SYSTEM SENSOR -
SS SCRL
INDICATES CANDELA RATING OF STROBE LIGHTXXcd
WP
FIRE ALARM DOCUMENT BOXFAD
AES RADIO - POWER PROVIDED BY FACP
I
EOL DENOTES END OF CIRCUIT FOR THAT NAC LOOP
INDICATES WEATHER RESISTANT DESIGN
FIRE ALARM ANNUNCIATOR -0FAA
CEILING MOUNTED
AUDIO/VISUAL
SEE NOTE 2
CEILING MOUNTED
HEAT/SMOKE
SEE NOTE 1
SEE NOTE 6
6'-8"
(80")
CEILING/DECK
SEE NOTE 5
CEILING MOUNTED
AUDIO/VISUAL
SEE NOTE 3
MAX 30'-0"
(360")
CEILING MOUNTED
HEAT/SMOKE
SEE NOTE 1
MAX 6'-0"
(72") &
MIN 5'-6"
(66")
TYP.
5'-0"
(60")
TYP.MAX 4'-0"
(48")
MIN 3'-6"
(42")
NOTES:
1.LOCATE CEILING MOUNTED HEAT/SMOKE DETECTORS ON THE BOTTOM OF THE DECK/SUSPENDED CEILING
(NOT ON BOTTOM OF STRUCTURAL MEMBERS), AND AS INDICATED IN NFPA 72.
2.LOCATE CEILING MOUNTED NOTIFICATION DEVICES ON BOTTOM OF BEAMS OR JOISTS; WITH CLEAR LINE
OF SITE IN ALL DIRECTIONS; NO GREATER THAN THIRTY (30) FEET ABOVE THE FINISHED FLOOR; AND AS
INDICATED IN NFPA 72.
3.LOCATE CEILING MOUNTED NOTIFICATION DEVICES FLUSH WITH THE SUSPENDED CEILING; ALIGNED WITH
LIGHTING, SPRINKLERS, AND OTHER ARCHITECTURAL FIXTURES; WITH CLEAR LINE OF SITE IN ALL
DIRECTIONS; NO GREATER THAN THIRTY (30) FEET A.F.F. ; AND AS INDICATED IN NFPA 72.
4.LOCATE WALL MOUNTED NOTIFICATION DEVICES AT 80" A.F.F TO BOTTOM OF BACK BOX.
5.COORDINATE EXACT MOUNTING HEIGHT OF CONTROL PANELS, ANNUNCIATORS, AND POWER SUPPLIES
WITH THE GENERAL CONTRACTOR, ELECTRICAL CONTRACTOR AND AHJ PRIOR TO INSTALLATION.
6.MEASURED TO THE OPERABLE PART OF THE PULL STATION.
TYPICAL DEVICE MOUNTING HEIGHT
N.T.S.
SEE NOTE 5
FAA
WALL MOUNTED
AUDIO/VISUAL
SEE NOTE 4
PULL STATION
FACU FAPS
SUSPENDED CEILING
FINISHED FLOOR
DESIGN NARRATIVE
THE PURPOSE OF THIS DESIGN IS TO UPGRADE CURRENT CORRIDOR PORTION OF THE EXISTING FIRE ALARM SYSTEM TO CODE COMPLIANT LAYOUT
AND DEVICES FOR DELAYED OR RESTRICTED ACCESS CORRIDORS.
SMOKE DETECTION IS PROVIDED THROUGHOUT, USING CORRIDOR SPACING, SO AS NO PORTION OF THE PROTECTED AREA IS GREATER TAN .07x THE
LISTED SPACING.
WE ACHIEVE SPRINKLER NOTIFICATION WITH SYSTEM SENSOR NOTIFICATION DEVICES MOUNTED AT THE CEILING THROUGHOUT CORRIDORS. THE
HORN STROBES ARE PLACED TO PROVIDE 15 DECIBELS ABOVE AMBIENT SOUND PRESSURE LEVELS. AMBIENT SOUND PRESSURE LEVELS ARE
SPECIFIED IN TABLE A.18.3.2 FROM NFPA 72 2013 HANDBOOK. ANTICIPATED AUDIBILITY IS FIGURED BY THE "6DB RULE OF THUMB" METHOD
REFERENCED IN NFPA 72 2013 HANDBOOK.
MONITORING IS EXISTING AND OUT OF OUR SCOPE OF WORK.
THE EXISTING ADDRESSABLE FIRE ALARM PANEL IS POWERED FROM A 20 AMP DEDICATED CIRCUIT. THE BATTERIES ARE SIZED TO PROVIDE 24 HOUR
STANDBY WITH 5 MINUTES OF ALARM. COMPLETE CALCULATIONS ARE INCLUDED WITH CUT SHEETS.
B2
A,B
WIRE LEGEND SYMBOLS
DESCRIPTION
A INDICATES 1x OF THE SPECIFIED WIRE. THE LETTER CORRESPONDS TO THE WIRE TYPE, IN THE WIRE LEGEND.
INDICATES 1x EACH OF THE SPECIFIED WIRE. THE LETTER CORRESPONDS TO THE WIRE TYPE, IN THE WIRE LEGEND.
INDICATES 2 OF THE SPECIFIED WIRE. THE LETTER CORRESPONDS TO THE TYPE, THE EXPONENT IS THE NUMBER OF THAT WIRE.
WIRE LEGEND SYMBOLS
DESCRIPTION
AES
0ISOLATION MODULE -
0T
R
H
0RELAY MODULE -
0HEAT DETECTOR -
SPRINKLER TAMPER CONNECTION
MONITORING SERVICE PROVIDED BY:
EXISTING AND OUT OF OUR SCOPE OF WORK
BUILDING DATA
ADDRESS:
PARCEL #:
AREA:
TYPE OF CONST:
OCCUPANCY:
16525 100TH WAY SE
YELM, WA.
64303600300
4,4367 FT2
SCHOOL - TYPE - E
RUNNER SERVICE PROVIDED BY
FIRETEK DESIGN AND INSTALLATION
500 CHERRY STREET SE
OLYMPIA, WA 98501
EMERGENCY SERVICE NUMBER 1-360-870-4329ELEVATOR RECALL MAINELEVATOR RECALL ALTERNATEELEVATOR RECALL MACHINE ROOMELEVATOR MAIN LOBBY SMOKE DETECTOR
ELEVATOR ALTERNATE LOBBY SMOKE DETECTORS
ELEVATOR MACHINE ROOM SMOKE DETECTOR
ELEVATOR SUPERVISORY CONDITIONS ELEVATOR SHUNT ACTIVATEDWIRE LEGEND
A
USE TYPEWIRE
B
DOOR HOLDERC 14 GAUGE 2 CONDUCTOR - FPLP
DESCRIPTION
CIRCUIT TO DOOR HOLDERS
WIRE LEGEND
DETECTION 18 GAUGE 4 CONDUCTOR - FPLPA
USE TYPEWIRE
NACB
C
DESCRIPTION
CIRCUIT TO SMOKES
14 GAUGE 4 CONDUCTOR - FPLP
0WALL MOUNT LOW FREQUENCY HORN -LF
SHEET INDEX
SHEET NUMBER DISCRIPTION
FA01 PROJECT DETAILS
FA02 NORTH CORRIDOR
FA03 SOUTH CORRIDOR
CIRCUIT TO HORNS & STROBES
WALL MOUNT MAGNETIC DOOR HOLDER -
DHS-24120C 8
FA01
Sheet NumberProject Name:Date:Drawn By:Email:Job #:File Name:DWG Name:Plot Date:Version:Rev:Date:Description:FA_PLANAutoCAD LT 2021KLMKARA@FIRETEKOLYMPIA.COM8/3/2020FORT STEVENSELEMENTARY SCHOOL16525 100TH WAY SE,YELM, WA. 98597F20-09_FORT STEVENS ESF20-09
15cd75cdDCCA²,B²,CA²,B²,CA²,B²,CA²,B²A²,B²A²,B²A²A,B,CA,BA,BA,BFA02FA03N.I.C.N.I.C.N.I.C.N.I.C.N.I.C.N.I.C.N.I.C.N.I.C.N.I.C.N.I.C.FA02FORT STEVENS ELEMENTARY SCHOOL -- DEVICE AND WIRE LAYOUTFA02Sheet NumberProject Name:Date:
Drawn By:
Email:
Job #:
File Name:
DWG Name:
Plot Date:
Version:
Rev:Date:Description:04'8'16'SCALE: 1/8"=1'-0"(IN FEET)FA_PLAN
AutoCAD LT 2021
8/3/2020
KLM
KARA@FIRETEKOLYMPIA.COM
FORT STEVENS
ELEMENTARY SCHOOL
16525 100TH WAY SE,
YELM, WA. 98597
F20-09_FORT STEVENS ES
F20-09KEY PLAN
EXEOL 15cd15cd15cd75cd15cd15cdCCA,B,CNEW WIRE FROMFACP TO DOORHOLDERSTIE IN TO EXISTING BOXA,B,CA²,B²,CCCCCA²,B²A²,B²B²DDA,B,CA²,B²,CA²,B²,CA,B,CA,BA,BA,BA,BA,BAFA02FA03FA02FA03N.I.C.N.I.C.N.I.C.N.I.C.N.I.C.N.I.C.N.I.C.N.I.C.N.I.C.N.I.C.N.I.C.N.I.C.N.I.C.N.I.C.N.I.C.N.I.C.N.I.C.N.I.C.FA03FORT STEVENS ELEMENTARY SCHOOL -- DEVICE AND WIRE LAYOUTFA03Sheet NumberProject Name:Date:
Drawn By:
Email:
Job #:
File Name:
DWG Name:
Plot Date:
Version:
Rev:Date:Description:04'8'16'SCALE: 1/8"=1'-0"(IN FEET)FA_PLAN
AutoCAD LT 2021
KLM
KARA@FIRETEKOLYMPIA.COMKEY PLAN8/3/2020
FORT STEVENS
ELEMENTARY SCHOOL
16525 100TH WAY SE,
YELM, WA. 98597
F20-09_FORT STEVENS ES
F20-09