2020.0225.FR0012 2035 FIRE SUPPRESSION DRAWINGS 08-04-20DESCRIPTIONLEGEND / PARTS LISTPART #QUAN.SYMBOLMANUFACTURERNOTESGENERAL NOTES:1.ALL DOORS IN THE CLEAN AGENT HAZARD AREA SHALL HAVE DOOR CLOSURES, DOOR SWEEPS AND DOOR SEALS. ( BYOTHERS )2.THE DISCHARGE TIME OF THE SYSTEM SHALL NOT EXCEED 10 SECONDS. THE PROTECTED VOLUME IS TO BE FLOODEDAT A 4.5% CONCENTRATION FOR CLASS "A" FIRES AND 4.5% FOR CLASS "C" FIRES UNLESS OTHERWISE NOTED ON THESYSTEM DRAWINGS AND HYDRAULIC CALCULATIONS. THE HAZARD AREA SHALL MAINTAIN DESIGN CONCENTRATIONFOR A MINIMUM OF 10 MIN.3.THE CLEAN AGENT CONTROL PANEL SHALL HAVE BATTERY BACK-UP TO PROVIDE 24 HOURS OF STANDBY OPERATIONWITH 5 MINUTES OF ALARM UNLESS NOTED OTHERWISE ON THE DRAWINGS AND THE BATTERY CALCULATIONS.4.INTERLOCK WIRING AND CONDUIT TO SHUTDOWN THE HVAC SYSTEM AND/OR DAMPERS ( IF REQUIRED ) WILL BEWIRED BY OTHERS. SUPPRESSION SYSTEMS INC. WILL PROVIDE RELAY CONTACTS LOCATED IN THE CLEAN AGENTCONTROL PANEL.5.INTERLOCK WIRING AND CONDUIT TO CONNECT TO THE REMOTE FIRE ALARM SYSTEM ( IF REQUIRED ) SHALL BEPROVIDED BY OTHERS. SUPPRESSION SYSTEMS INC. WILL PROVIDE RELAY CONTACTS LOCATED IN THE CLEAN AGENTCONTROL PANEL.6.INTERLOCK WIRING AND CONDUIT TO SHUTDOWN EQUIPMENT ( IF REQUIRED ) SHALL BE PROVIDED BY OTHERS.SUPPRESSION SYSTEMS INC. WILL PROVIDE RELAY CONTACTS LOCATED IN THE CLEAN AGENT CONTROL PANEL.7.THE CLEAN AGENT HAZARD AREA SHALL BE SEALED TO PREVENT LEAKAGE OF THE AGENT. ( BY OTHERS )SUPPRESSION SYSTEMS INC. WILL PROVIDE GUIDANCE AND/OR SUPERVISION.8.THE 120VAC CIRCUIT FOR THE CLEAN AGENT CONTROL PANEL SHALL BE A DEDICATED CIRCUIT WITH A LOCK-OUTDEVICE ON THE BREAKER SWITCH TO COMPLY WITH NFPA 72 CURRENT ADDITION.9.ALL TERMINATION'S IN THE CLEAN AGENT CONTROL PANEL SHALL BE PERFORMED BY SUPPRESSION SYSTEMS INC.10.RETENTION TIME FOR THE PROTECTED SPACE SHALL BE VERIFIED BY A ROOM INTEGRITY TEST PERFORMED IN ACCORDANCE WITH NFPA 2001 2015 EDITION.CLEAN AGENT PIPING SYSTEM NOTES :1.REFER TO SYSTEM DRAWINGS AND CALCULATIONS FOR THE LOCATION AND LAYOUT OF THE CLEAN AGENTDISTRIBUTION PIPING SYSTEM. EXAMINE THE CONFIGURATION OF THE PIPING SYSTEM TO ENSURE THE PIPING ANDDISCHARGE NOZZLES DO NOT INTERFERE WITH ANY ON SITE PHYSICAL OBSTRUCTIONS WITHIN THE CLEAN AGENTHAZARD AREA BEFORE THE PIPING INSTALLATION BEGINS. SHOULD ANY CONFLICTS OCCUR NOTIFY SUPPRESSIONSYSTEMS INC. TO MAKE THE REQUIRED ADJUSTMENTS TO THE SYSTEM DRAWINGS AND HYDRAULIC CALCULATIONSPRIOR TO BEGINNING PIPING INSTALLATION. ANY DEVIATIONS IN THE ROUTING OF THE PIPE NETWORK SHALL BEVERIFIED AND APPROVED BY SUPPRESSION SYSTEMS INC.2.CLEAN AGENT SUPPRESSION SYSTEM SHALL BE INSTALLED AND TESTED IN ACCORDANCE WITH NFPA 2001 CURRENTADDITION, AS WELL AS ALL APPLICABLE LOCAL CODES. DO NOT HYDROSTATIC TEST. PNEUMATIC PRESSURE TESTWITH AIR OR N2 TO 40 PSI FOR 10 MINUTES. AT THE END OF 10 MINUTES SHALL NOT DROP BELOW 20% OF THETEST PRESSURE.3.PIPING MATERIAL MUST CONFORM TO THE REQUIREMENTS OUTLINED IN NFPA 2001, CURRENT EDITION. SCHEDULE 40OR SCHEDULE 80 PIPE (BLACK OR GALVANIZED) MUST CONFORM TO ASTM A53 OR A106. ORDINARY CAST IRON PIPE,STEEL PIPE CONFORMING TO ASTM-120, OR NONMETALLIC PIPE SHALL NOT BE PERMITTED TO BE USED.4.PIPE FITTINGS MUST CONFORM TO THE REQUIREMENTS OUTLINED IN NFPA 2001, CURRENT EDITION. MALLEABLE IRONFITTINGS (BLACK OR GALVANIZED) SHALL BE 300 LB. CLASS THAT CONFORM TO ASTM SPECIFICATION A-197. 150 LB.CLASS FITTINGS AND ORDINARY CAST IRON FITTINGS ARE NOT PERMITTED. ONLY LISTED GROOVED, THREADED,WELDED OR FLANGED FITTINGS MAY BE USED, PROVIDED THEY CONFORM TO THE ABOVE REQUIREMENTS. HOLE CUTFITTINGS MAY NOT BE USED.5.ALL PIPE JOINING METHODS SHALL BE IN ACCORDANCE WITH NFPA 2001 CURRENT ADDITION. TEFLON TAPE ISRECOMMENDED AND SHALL BE USED WITH ALL THREADED PIPING CONNECTIONS. THREADED PIPE AND FITTINGSSHALL BE TAPERED IN CONFORMANCE WITH ANSI SPECIFICATION B-20.1. ALL GROOVED PIPING CONNECTIONS SHALLBE BE LUBRICATED PER MANUFACTURERS SPECIFICATIONS.6.ALL PIPING MUST BE RIGIDLY SUPPORTED BY A COMBINATION OF PIPE HANGERS AND RIGID SUPPORT BRACKETS. PIPEHANGERS ARE USED TO SUPPORT THE " DEAD LOAD " OF THE PIPING SYSTEM AND SHALL BE SPACED AT INTERVALSNOT EXCEEDING 15 FEET. RIGID SUPPORTS ARE REQUIRED TO SUPPORT THE " LIVE LOAD " OF THE PIPING SYSTEMDURING DISCHARGE. RIGID BRACING IS REQUIRED AT EACH DIRECTIONAL CHANGE - 90° ELBOW, TEE AND NOZZLE.ALL 180° NOZZLES REQUIRE BACK-BRACING IN THE OPPOSITE DIRECTION OF THE DISCHARGE PATTERN. EARTHQUAKEBRACING SHALL BE USED WHERE REQUIRED BY LOCAL CODE. REFER TO ANSI B31.1 FOR BRACING REQUIREMENTS.7.REDUCTIONS IN PIPE SIZE SHALL BE DIRECTLY AFTER A TEE WITH THE TEE BEING THE SAME PIPE SIZE AS THE INLETLINE TO THE TEE. REDUCTIONS IN PIPE SIZE MAY ALSO BE MADE USING A CONCENTRIC BELL REDUCER AFTER AUNION, PROVIDED THE NEXT CHANGE IN DIRECTION (TEE) IS LOCATED A MINIMUM OF 10 PIPE DIAMETERSDOWNSTREAM OF THE CONCENTRIC BELL REDUCER. CONCENTRIC BELL REDUCERS OR CONCENTRIC REDUCINGCOUPLINGS SHALL BE USED TO MAKE ALL REDUCTIONS IN PIPE SIZE. REDUCING BUSHINGS, WELD-O-LETS AND HOLECUT FITTINGS SHALL NOT BE PERMITTED.8.THE SYSTEM SHALL BE INSTALLED IN A PROFESSIONAL MANNER WITH " GOOD COMMERCIAL PRACTICE ". ALL PIPINGAND FITTINGS MUST BE REAMED, BLOWN CLEAN AND SWABBED WITH A CLEANING SOLVENT TO REMOVE DIRT, RUSTAND OIL.9.PIPE REDUCTIONS MADE DIRECTLY AFTER A CHANGE IN DIRECTION, WITH THE FITTING BEING THE SAME PIPE SIZE ASTHE INLET , SHALL BE MADE USING A COMMON CONCENTRIC BELL REDUCER. REDUCING BUSHINGS ARE NOTACCEPTABLE ( UNLESS OTHERWISE NOTED ). A MINIMUM OF 10 PIPE DIAMETERS MUST BE MAINTAINED FROM THECENTER OF THE FITTING TO THE CENTER OF THE NEXT CHANGE IN DIRECTION.10.WHEN BRACING THE PIPING CARE SHOULD BE TAKEN TO INSURE THE NOZZLE LOCATIONS ARE WITHIN ONE FOOT OFTHE LOCATIONS SHOWN ON THE SYSTEM PLANS. CORRECT NOZZLES SHALL BE INSTALLED EXACTLY IN ACCORDANCEWITH THE SYSTEM PLANS. NOZZLES SHALL BE INSTALLED PERPENDICULAR TO THE CEILING FOR PROPERDISTRIBUTION PATTERNS. 180° NOZZLES SHALL BE ALIGNED WITH THE ORIFICE HOLES ORIENTED PARALLEL TO THEADJACENT WALLS SO NO DIRECT WALL IMPINGEMENT OF THE AGENT OCCURS.11.FINAL INSTALLATION ACCEPTANCE SHALL BE IN ACCORDANCE WITH NFPA 2001 CURRENT ADDITION.ELECTRICAL SYSTEM NOTES :1.THE DETECTION AND CONTROLS PORTION OF THE SYSTEM SHALL BE INSTALLED IN ACCORDANCE WITHNFPA 70, 72 AND STATE AND LOCAL CODES WHERE APPLICABLE.2.ALL WIRING FOR THE CLEAN AGENT SUPPRESSION SYSTEM SHALL BE INSTALLED IN MINIMUM OF 1/2"ELECTRICAL METALLIC TUBING (EMT) OR CONDUIT.3.INITIATING AND RELEASING CIRCUITS SHALL BE INSTALLED IN RACEWAYS. ( NFPA 2001 )4.AC AND DC CURRENT SHALL BE RUN IN SEPARATE CONDUIT AND BOXES.5.PAINT ALL J-BOXES AND COVERS RED TO IDENTIFY FIRE ALARM SYSTEM.6.IDENTIFY EACH COVER WITH POWER LIMITED FIRE ALARM CKT.7.MAINTAIN 1" SEPARATION BETWEEN ALL POWER LIMITED AND NON POWER LIMITED CIRCUITS.8.CONTROL SYSTEM SHALL BE INSTALLED AND TESTED IN ACCORDANCE WITH NFPA 72 , AS WELL AS ALLAPPLICABLE LOCAL CODES.9.SMOKE DETECTORS SHALL BE LOCATED NO CLOSER THAN 3 FEET TO AN AIR SUPPLY OUTLET. ALL SMOKEDETECTORS SHALL BE INSTALLED IN AN ACCESSIBLE LOCATION TO ALLOW FUTURE TESTING AND SERVICE.10.AIR HANDLING DAMPERS SHALL SHUT DOWN WHEN CLEAN AGENT SYSTEM IS IN THE PRE-DISCHARGECONDITION.11.SOUND PRESSURE LEVELS FOR AUDIO APPLIANCES SHALL BE IN COMPLIANCE INTERNATIONAL BUILDINGCODE CURRENT EDITION.EXCLUSIONS :**WORK LISTED BELOW SHALL BE PROVIDED BY OTHERS OR UNDER OTHER SECTIONS OF THE PROJECT.**1.120 VAC POWER SUPPLY TO THE CLEAN AGENT CONTROL PANEL.2.INTERLOCK WIRING AND CONDUIT FOR SHUTDOWN OF HVAC , DAMPERS AND/OR ELECTRIC POWERSUPPLIES , RELAYS , SHUNT TRIP BREAKERS OR OTHER DEVICES.3.CONNECTION TO LOCAL OR REMOTE FIRE ALARM SYSTEMS OR LISTED CENTRAL ALARM STATION.4.ALL MATERIALS AND LABOR TO ENSURE THE " AIR-TIGHTNESS " OF THE PROTECTED SPACE(S) ANDRESPONSIBILITY FOR THE INTEGRITY OF THE CLEAN AGENT PROTECTED SPACE TO SATISFY THEREQUIREMENTS FOR THE TEN ( 10 ) MINUTE RETENTION TIME. SUPPRESSION SYSTEMS INC. MAY PROVIDEASSISTANCE , BY MEANS OF INSPECTION OF THE SPACE AND MAKING RECOMMENDATIONS ON REMEDIALACTIONS THAT MAY BE REQUIRED TO ENSURE ROOM INTEGRITY.5.RESERVE SUPPLY OF AGENT.6.CLEAN AGENT CYLINDER SHALL BE LOCATED WITHIN THE SPACE, IF THE CYLINDER IS REQUESTED TO BELOCATED OUTSIDE OF THE SPACE THE ADDITIONAL EQUIPMENT, CALCULATIONS AND ENGINEERING ARENOT INCLUDED IN BASE CONTRACT UNLESS SPECIFICALLY CALLED OUT IN THESE DOCUMENT.7.FIRE SPRINKLER WORK OF ANY KIND.PROJECT STANDARDS :APPLICABLE CODES :NFPA 2001 2015NFPA 70 2014NFPA 72 2013INTERNATIONAL FIRE CODE 2015INTERNATIONAL BUILDING CODE 2015SCOPE OF WORK :PROVIDE ADDRESSABLE DETECTION AND CONTROLS,HIGH SENSITIVITY SMOKE DETECTION, CLEAN AGENT FIRESUPPRESSION AND PRE-ACTION CONTROLS FOR SERVER ROOM 188. PRE-ACTION SPRINKLER RISER ISLOCATED IN MECHANICAL ROOM 197.OWNER / SITE DATA :YELM MIDDLE SCHOOL402 WEST YELM AVENUEYELM, WASHINGTON 98597AUTHORITY HAVING JURISDICTION :CITY OF YELM PUBLIC WORKS901 RHOTON ROADYELM, WASHINGTON 98597DRAWING INDEXFP-1.1NOTES, LEGEND, PARTS LIST, AND DRAWING INDEXFP-1.2GENERAL ELEVATION AND MAPSFP-2.1FLOOR PLANS AND ELEVATION "A"FP-2.2SEQUENCE OF OPERATIONS AND ISOMETRICSFP-3.1MULTI LINE WIRING DIAGRAMFP-3.2ELECTRICAL DETAILS AND SINGLE LINEFP-4.1MECHANICAL DETAILSA1SS2-1-0-4GREEN ABORT STATIONSTIABORTAI1170-417008-001ADDRESSABLE MONITOR MODULE (N/O)KIDDE4S BOX OR 2 GANG327 LBS47-190000-001NOVEC 1230 CLEAN AGENTKIDDECLEAN AGENT CYLINDERCP176-600000-001ARIES ADDRESSABLE CONTROL PANELKIDDERED ENCLOSURE6' AFFILR206-220023-001IN-LINE RELEASING CIRCUITKIDDEAT CYLINDERCHM1CONTROL HEAD MONITORKIDDEINCL. W/ SOL. ASSY.2UB1215015.0 AH BATTERYUPGCONTROL PANELM1GEM MAINTMAINTENANCE BYPASS, 4 POLEGEMCOM2 GANG DEEPSIGN 11SSI SIGN #1CLEAN AGENT DOOR SIGNSSI / CWSIZE 9" X 12"SIGN 31SSI SIGN #3CLEAN AGENT DISCHARGE STROBE SIGNSSI / CWSIZE 5" X 8"SIGN 21SSI SIGN #2ACLEAN AGENT HORN/STROBE SIGNSSI / CWSIZE 5" X 8"P1DS-PSPHOTOELECTRIC SMOKE DETECTORKIDDEBASE (DS-SB)1DS-SB4" DETECTOR BASE W/ 6" TRIM RINGKIDDE3-0 BOX1SS2-0-0-0RED MANUAL RELEASESTIMANUAL RELEASEMULTIcd cd14890123HORN/STROBE - MULTI CANDELA BLUE LENSPOTTER4S BOX OR 2 GANGDEEPMULTIcd cd14890103STROBE - MULTI CANDELA BLUE LENSPOTTER4S BOX OR 2 GANGDEEPSOL185-486500-020ELECTRIC, STACKABLE (EP) 24V DC CONTROL HEADKIDDE4S BOX OR 2 GANG0.24A1 pcVP-P-2103/4" CPVC PIPE, 15' LENGTH (BOX 14 EACH)VESDA1 pcVP-EC3/4" END CAP (BOX 25 EACH)VESDA5 pcVP-COUP3/4" COUPLING (BOX 15 EACH)VESDAHSSD1VLF-250VESDA LASER FOCUS DETECTORVESDAUP TO 2,500 SQ. FT.4SAMP-POINTSTANDARD DRILLED SAMPLING POINTXTRALIS2 pcVP-ELB-453/4" ELBOW, 45° (BOX 25 EACH)XTRALIS1WK-281866-000MOUNTING STRAP FOR A 350 lb. CYLINDERKIDDECLEAN AGENT CYLINDER1WK-283905-000VALVE OUTLET ADAPTER FOR A 350 lb. CYL.KIDDECLEAN AGENT CYLINDER145-550351-001350 lb. CYLINDER W/ 327.0 lbs. AGENT (2" VALVE)KIDDEINC. LLI (PN 283894)500 PSI6"1SSM24-66" BELLSYSTEM SENSOR4S BOX OR 2 GANGDEEPL1BY OTHERSPRE-ACTION LOW AIR SWITCHBY OTHERST1BY OTHERSPRE-ACTION TAMPER SWITCHBY OTHERSFL1BY OTHERSPRE-ACTION FLOW SWITCHBY OTHERSSOL1BY OTHERSPRE-ACTION SOLENOIDBY OTHERS245-194726-190360° CLEAN AGENT NOZZLEKIDDENOZZLE AREA 0.8053SIGN 21SSI SIGN #2EPRE-ACTION DISCHARGE WATERFLOW BELLSSI / CWSIZE 5" X 8"EPO1SS2-2-0-3YELLOW EPO SWITCHSTIEPOSHEET NUMBER:SHEET TITLE:COMPLIANCEDATEREVDESCRIPTIONDATENICETCERTIFIEDNATHAN SCHERNECKNICET #111032 - LEVEL 4, FIRE ALARMPROJECT INFORMATION:1234DESIGNED BY:DRAWN BY:CHECKED BY:JOB NUMBER:SUBMITTALSNICET STAMPSMANUFACTURER LOGO'SFIRE PROTECTION ENGINEERS STAMPSCALE:NOT TOSCALEUNLESSNOTEDOTHERWISESUPPESSION SYSTEMS INC.SPECIAL HAZARDS FIRE PROTECTION3077 20TH STREET EAST, SUITE BFIFE, WA 98424-1798(253) 926-3300 FAX (253)926-3306RTMYELM MIDDLE SCHOOL
402 WEST YELM AVENUE
YELM, WASHINGTON 98597NMRJACZST2035FIRE SUPPRESSION SYSTEMNOTES, LEGEND, PARTS LIST, AND DRAWING INDEXFP-1.1 of 7100% SUBMITTAL07/15/20KiddeFire Systems
AREA MAPNNVICINITY MAPSCALE: NTSSCALE: NTSKIDDESUPPRESSION SYSTEM ABORTVARIESVARIESCLEANAGENTCYLINDERCLEANAGENTNOZZLEHIGHSENSITIVITYSMOKEDETECTOR(HSSD) POWERSUPPLY1'-0" MAXFROM CEILINGBATTERY BOXHIGHSENSITIVITYSMOKEDETECTOR(HSSD)62"MAX.36.5" MAXFROMAFFCONTROL PANEL72"MAXCEILINGMOUNTVISUAL ORAUDIBLE/VISUALDEVICEFROMAFFSMOKE OR HEAT DETECTORSMOKE OR HEATDETECTORS12" MAXFROMCEILING3' MINFROMDIFFUSER3' MINFROMDIFFUSER4" MINFROMCEILING4" MINFROMWALLDO NOTINSTALLHEREA/C SUPPLY OR RETURN DIFFUSERFINISHED FLOORCEILING6" MINFROM CEILING90" MINAFFVISUAL DEVICETOP OFSTROBE LENSBOTTOM OFSTROBE LENSLOW CEILINGS:DEVICE SHALL BELOCATED WITHIN 6"OF THE CEILING96" MAXAFF48" MAXPUSH/HOLDKIDDEPUSHPULLKIDDESUPPRESSION SYSTEM ABORTPUSH/HOLDDOORFROMAFF5' MAXFROMDOOR48" MAX5' MAXFROMDOORMANUAL RELEASE STATION TYP.ABORT STATION TYP.MAINTENANCE BYPASS TYP.AUDIBLEDEVICEFIRESYSTEMRELEASEFIRESYSTEMRELEASESYSTEMARMEDSYSTEMINACTIVESYSTEMARMEDSYSTEMINACTIVE6" MINFROM CEILING90" MINAFFPRE-ACTION BELL84" TYP.80" MINAFFKIDDEPUSHPULLFIRESYSTEMRELEASEFIRESYSTEMRELEASEGENERAL DEVICE ELEVATIONNOTES:·ALL ELEVATIONS ARE SHOWN FROM A VIEW OF BEING INSIDE THE ROOM LOOKING AT THE DOOR.·ADDRESSABLE INPUT MODULES SHALL BE MOUNTED BEHIND INPUT DEVICES.·ADDRESSABLE SIGNAL MODULES SHALL BE MOUNTED AT THE SAME ELEVATION AS INDICATING DEVICE.·ALL DEVICES SHALL BE MOUNTED IN ACCORDANCE WITH ALL APPLICABLE CODES.·CONFER WITH THE LOCAL AHJ AND ENGINEER OF RECORD IF MOUNTING HEIGHTS CAN NOT BE ATTAINED ORCONFLICT WITH THE LOCAL CODES.·ALL VISUAL DEVICES SHALL BE SYNCHRONIZED AND UNOBSTRUCTED.·SOLENOID TO BE MOUNTED IN J/BOX AT CYLINDER VALVE OUTLET ELEVATION.·MAINTENANCE BYPASS SHALL BE INSIDE PROTECTED HAZARD.··IF CYLINDER IS INSIDE PROTECTED HAZARD LOCATE AT CYLINDER.··IF CYLINDER IS OUTSIDE PROTECTED HAZARD LOCATE AT RELEASE PANEL NEAR MANUAL RELEASE ANDABORT STATION IN PROTECTED HAZARD.··IF PANEL IS OUTSIDE PROTECTED HAZARD, LOCATE NEAR MANUAL RELEASE AND ABORT STATION INPROTECTED HAZARD.NOTES CONTINUED:·DISCHARGE STROBES TO BE MOUNTED ON THE OUTSIDE OF THE ROOM @ A MAX. OF 96" A.F.F. TO THE CENTER OFTHE DEVICE.·HORN/STROBES TO BE MOUNTED @ A MAX. OF 80" A.F.F. TO THE CENTER OF THE DEVICE PER ADA REQUIREMENTS.·MANUAL RELEASE AND ABORT SWITCHES TO BE MOUNTED @ 48" A.F.F. TO THE TOP OF THE DEVICE.·CLEAN AGENT DOOR SIGN IS TO BE MOUNTED ON THE OUTSIDE OF ALL DOORS TO CLEAN AGENT ZONES.·CLEAN AGENT HORN/STROBE SIGN TO BE MOUNTED BELOW ALL SUPPRESSION HORN/STROBES IN A CLEANAGENT ZONE.·CLEAN AGENT DISCHARGE STROBE SIGNS TO BE MOUNTED BELOW ALL CLEAN AGENT STROBES.SYSTEMARMEDSYSTEMINACTIVESTANDARD REFERENCE NOTES FOR AUDIO/VISUAL DEVICES:·MOUNTING HEIGHTS FOR AUDIBLE APPLIANCES ARE DETERMINED BY THE FOLLOWING CODES:··NFPA 72 2013 EDITION (18.4.8.1)·MOUNTING HEIGHTS FOR AUDIBLE/VISUAL APPLIANCES ARE DETERMINED BY THE FOLLOWING CODES:··NFPA 72 2013 EDITION (18.5.5.1)STANDARD REFERENCE NOTES FOR DETECTION:·MOUNTING HEIGHTS FOR MANUAL PULL STATIONS ARE DETERMINED BY THE FOLLOWING CODES:··NFPA 72 2013 EDITION (17.14.5 AND 17.14.8.5)·MOUNTING HEIGHTS FOR WALL MOUNTED SMOKE AND HEAT DETECTORS ARE DETERMINED BY THE FOLLOWINGCODES:··NFPA 72 2013 EDITION (17.7.3.2.1 SMOKE AND 17.6.3.1.3.1 FOR HEAT )8"8"8"8"SITE LOCATIONAREA OF WORKSERVER ROOM 188EXTERIOR DOOREXTERIOR DOOREXTERIOR DOOREXTERIOR DOOREXTERIOR DOOREXTERIOR DOORGYMAREA OF WORKMECH ROOM 197PRE-ACTION RISERSHEET NUMBER:SHEET TITLE:COMPLIANCEDATEREVDESCRIPTIONDATENICETCERTIFIEDNATHAN SCHERNECKNICET #111032 - LEVEL 4, FIRE ALARMPROJECT INFORMATION:1234DESIGNED BY:DRAWN BY:CHECKED BY:JOB NUMBER:SUBMITTALSNICET STAMPSMANUFACTURER LOGO'SFIRE PROTECTION ENGINEERS STAMPSCALE:NOT TOSCALEUNLESSNOTEDOTHERWISESUPPESSION SYSTEMS INC.SPECIAL HAZARDS FIRE PROTECTION3077 20TH STREET EAST, SUITE BFIFE, WA 98424-1798(253) 926-3300 FAX (253)926-3306RTMYELM MIDDLE SCHOOL
402 WEST YELM AVENUE
YELM, WASHINGTON 98597NMRJACZST2035FIRE SUPPRESSION SYSTEMGENERAL ELEVATIONAND MAPS FP-1.2 of 7100% SUBMITTAL07/15/20KiddeFire Systems
NFIRE SUPPRESSION FLOOR PLANSCALE: 1/4"=1'-0"NFIRE SUPPRESSION HSSD PIPING PLANSCALE: 1/4"=1'-0"0GRAPHIC SCALE12481216ELEVATION "A"SCALE: 1/4"=1'-0"NFIRE SUPPRESSION NOVEC PIPING PLANSCALE: 1/4"=1'-0"CPA30cdP1-02130cdMAI1-001ILRSOLCHMAI1-006SERVER188RR187FMMM-012HSSD ACTIONHSSD FIRE 1HSSD3'-0" MAXFROM PEAKFL LTSOLAI1-019AI1-017AI1-0186"LOCATED ATPRE-ACTIONRISER INMECHANICALROOM 197FMMM-011FMMM-010HSSD FAULTAI1-002AI1-003A - FP-2.1A - FP-2.1 COMBO 1REL 2ILREPOAI1-004SERVER188RR187HSSDDOWN TO 5'-0" AFFTESTING POINT6'-2"9'-0"5'-5 1/2"12'-0"1'-0"
6'-6"
A - FP-2.1A - FP-2.1 HSSD PIPINGSHALL FOLLOWSLOPE OFCEILINGINSTALLED ONBOTTOM OFBEAMSERVER18822'-9"17'-4 1/2"21'-8"TESTING POINT6'-0"HSSD PIPINGP3'-0"PHOTODETECTORNOVEC PIPINGNOVECNOZZLETO HSSDDETECTOR6'-0" AFFMAX16'-0"MAX1'-0"SERVER188RR18721'-4 1/2"21'-7 1/2"
8'-0"8'-11 1/2"8'-2"1'-0"1'-0"12'-2 1/2"NOVEC PIPESHALL FOLLOWSLOPE OFCEILINGINSTALLED ONBOTTOM OFBEAMA - FP-2.1A - FP-2.1
SHEET NUMBER:SHEET TITLE:COMPLIANCEDATEREVDESCRIPTIONDATENICETCERTIFIEDNATHAN SCHERNECKNICET #111032 - LEVEL 4, FIRE ALARMPROJECT INFORMATION:1234DESIGNED BY:DRAWN BY:CHECKED BY:JOB NUMBER:SUBMITTALSNICET STAMPSMANUFACTURER LOGO'SFIRE PROTECTION ENGINEERS STAMPSCALE:NOT TOSCALEUNLESSNOTEDOTHERWISESUPPESSION SYSTEMS INC.SPECIAL HAZARDS FIRE PROTECTION3077 20TH STREET EAST, SUITE BFIFE, WA 98424-1798(253) 926-3300 FAX (253)926-3306RTMYELM MIDDLE SCHOOL
402 WEST YELM AVENUE
YELM, WASHINGTON 98597NMRJACZST2035FIRE SUPPRESSION SYSTEMFLOOR PLANS ANDELEVATION "A"FP-2.1 of 7100% SUBMITTAL07/15/20KiddeFire Systems
VOLUME CALCULATION NOTES:1.FORMULA FOR ABOVE CALCULATIONS:1.1.AREA x DEPTH = VOLUME1.2.VOLUME x AGENT FACTOR = MINIMUM AMOUNT OF CLEAN AGENT REQUIRED1.3.MINIMUM AMOUNT OF AGENT REQUIRED X ELEVATION CORRECTION = ADJUSTED MINIMUM AGENT REQUIRED2.FOR ADDITIONAL INFORMATION SEE THE CLEAN AGENT FLOW CALCULATIONS INCLUDED IN THE SUBMITTAL PACKAGE.3.AGENT DESIGN CONCENTRATION IS FROM NFPA 2001 AND MANUFACTURE RECOMMENDATIONS.ISOMETRIC PIPING NOTES:4.PIPE LENGTH'S DO NOT REPRESENT CUT LENGTH'S.5.ALL LENGTH'S SHALL BE FIELD VERIFIED.6.ALL PIPING 1/2" TO 1 1/2" SHALL BE THREADED. MINIMUM AND MAXIMUM PRESSURE RATINGS SHALL MEET FSSA PIPE DESIGN GUIDE FOR USEWITH SPECIAL HAZARD FIRE SUPPRESSION SYSTEMS.7.ALL PIPING 2" TO 6" SHALL BE GROOVED. MINIMUM AND MAXIMUM PRESSURE RATINGS SHALL MEET FSSA PIPE DESIGN GUIDE FOR USE WITHSPECIAL HAZARD FIRE SUPPRESSION SYSTEMS.8.ANY DEVIATIONS IN PIPE LENGTH OR SIZE SHALL BE APPROVED BY SUPPRESSION SYSTEMS INC. PRIOR TO BEGINNING INSTALLATION.CLEAN AGENT AREA VOLUME CALCULATIONSROOM DESCRIPTIONAREA(SQUARE FEET)DEPTH(FEET)VOLUME(CUBIC FEET)AGENTCONCENTRATION( % )AGENT FACTORMINIMUM AGENTREQUIRES(POUNDS)ELEVATIONCORRECTIONFACTORADJUSTEDMINIMUM AGENTREQUIRED(POUNDS)AGENTSUPPLIEDCYLINDERSUPPLIEDSERVER ROOM 188390.88VARIES8018.004.500.0407326.70--326.70327.00350 LB.CLEAN AGENT ISOMETRICSCALE: 1/4"=1'-0"HSSD NOTES:5) ALARM THRESHOLD SETTINGS:ACTION THRESHOLD SETTING = 0.2782ACTION TARGET HOLE SENSITIVITY = 1.5FIRE 1 THRESHOLD SETTING = 0.5798FIRE 1 TARGET HOLE SENSITIVITY = 3.125AIR SAMPLING ISOMETRICSCALE: NTSHSSD DETECTOR VLF-250TEST POINT, SOLID ENDCAP NOT GLUED9'-6"1'-0"90°45°90°9'-0"6'-6"2'-8"1'-0"12'-5"5'-5 1/2"DOWN TO 6'-0" AFFSHEET NOTE:ALL SAMPLING HOLESTO BE DRILLED AT 1/8"UNLESS OTHERWISESTATEDALL PIPE TO BE 3/4" ØUNLESS OTHERWISESTATED1/8"Ø SAMPLING POINT (TYP. 4)SEQUENCE OF OPERATIONSMATRIX FOR CLEAN AGENT FIRESUPPRESSION SYSTEM WITHPRE-ACTION DETECTION ANDCONTROLS AND (HSSD) AIRSAMPLING DETECTIONSYSTEM OUTPUTSACTIVATE PIEZO BUZZER AND TROUBLE LED ATRELEASE PANELACTIVATE PIEZO BUZZER AND ALARM LED ATRELEASE PANELACTIVATE PIEZO BUZZER AND SUPERVISORY LED ATRELEASE PANELINTERIOR HORNS PULSE AT 60 BPM UNTIL RELEASEPANEL IS SILENCEDINTERIOR HORNS PULSE AT 120 BPM UNTILRELEASE PANEL IS SILENCEDINTERIOR HORNS STAY CONSTANT UNTIL RELEASEPANEL IS SILENCEDINTERIOR STROBES ACTIVATEDEXTERIOR DISCHARGE STROBES PULSE AT 60 BPMACTIVATE 30 SECOND TIME DELAY SUPPRESSIONSYSTEM ZONERELEASE CLEAN AGENT IN ACTIVATEDSUPPRESSION SYSTEM ZONELOCK-OUT RELEASE CIRCUITS SUPPRESSIONSYSTEM ZONESHUT DOWN HVAC AND CLOSE DAMPERS AS
REQUIRED SUPPRESSION SYSTEM ZONE
HOLD CLEAN AGENT RELEASE UNTIL THE ABORT IS
RELEASED SUPPRESSION SYSTEM ZONE
ACTIVATE PRE-ACTION SOLENOID SPRINKLER ZONE
AS REQUIRED
ACTIVATE PRE-ACTION BELL SPRINKLER ZONE AS
REQUIRED
SEND ALARM SIGNAL TO BUILDING FIRE ALARM
CONTROL PANEL
SEND TROUBLE SIGNAL TO BUILDING FIRE ALARM
CONTROL PANEL
SEND SUPERVISORY SIGNAL TO BUILDING FIRE
ALARM CONTROL PANEL
SEND PRE-ACTION WATER FLOW SIGNAL TO
BUILDING FIRE ALARM CONTROL PANEL
TERMINATE POWER TO PROTECTED EQUIPMENTSYSTEM INPUTSFIRST DETECTOR AND/OR FIRE 1 IN ALARMXXXXXSECOND DETECTOR AND/OR FIRE 1 IN ALARMXXXXXXEXPIRATION OF 30 SECOND TIME DELAYXXXXACTIVATION OF MANUAL RELEASEXXXXXXACTIVATION OF ABORTXXACTIVATION OF MAINTENANCE BYPASSXXXEPO SWITCHXXXSYSTEM TROUBLEXXBATTERY FAULTXXGROUND FAULTXXOPEN CIRCUIT FAULTXXLOSS OF PRIMARY POWERXXMISSING DEVICEXXCYLINDER CONTROL HEAD MONITOR DEVICEXXPRE-ACTION WATER FLOWXXPRE-ACTION LOW AIR AS REQUIREDXPRE-ACTION TAMPER AS REQUIREDXHSSD FAULTXHSSD NOTES:1) SYSTEM SHALL BE AREA SAMPLING BELOW THE CEILING ONLY.2) SYSTEM LIMITS:A) MAXIMUM TRANSPORT TIME 60 SECONDS.B) 250 SQ. FT. AREA OF COVERAGE PER SAMPLING POINT.3) SYSTEM CALCULATIONS:AREA (12'-5" X 8'-0")+(21'-5" X 13'-8") = 393 SQ. FT.393 SQ. FT. / 250 SQ. FT. = 2 SAMPLING POINTS REQUIRED4 SAMPLING POINTS PROVIDED4) SYSTEM RESULTS:CALCULATED TRANSPORT TIME = 33 SECCALCULATED SYSTEM FLOW RATE = 14.9 L/MINMINIMUM AGGREGATE SENSITIVITY = 0.5485% OB / FTMAXIMUM AGGREGATE SENSITIVITY = 0.6110% OB / FTBACK TO BACK 90° SWING JOINT TO FOLLOW THE SLOPE OF THE CEILINGCLEAN AGENT ISOMETRIC DETAIL 1SCALE: NTSSHEET NUMBER:SHEET TITLE:COMPLIANCEDATEREVDESCRIPTIONDATENICETCERTIFIEDNATHAN SCHERNECKNICET #111032 - LEVEL 4, FIRE ALARMPROJECT INFORMATION:1234DESIGNED BY:DRAWN BY:CHECKED BY:JOB NUMBER:SUBMITTALSNICET STAMPSMANUFACTURER LOGO'SFIRE PROTECTION ENGINEERS STAMPSCALE:NOT TOSCALEUNLESSNOTEDOTHERWISESUPPESSION SYSTEMS INC.SPECIAL HAZARDS FIRE PROTECTION3077 20TH STREET EAST, SUITE BFIFE, WA 98424-1798(253) 926-3300 FAX (253)926-3306RTMYELM MIDDLE SCHOOL
402 WEST YELM AVENUE
YELM, WASHINGTON 98597NMRJACZST2035FIRE SUPPRESSION SYSTEMSEQUENCE OF OPERATIONSAND ISOMETRICSFP-2.2 of 7100% SUBMITTAL07/15/20KiddeFire SystemsSEE DETAIL 1 ON THIS PAGE1 1/2" X 11'-4"2" X 1 1/2" REDUCER1 1/2" X 0'-5"1 1/2" X 0'-3"1 1/2" 90° ELBOWS USED AS ASWING JOINT TO RUN CLEANAGENT PIPING ALONG THESLOPE OF CEILING (TYP. 2)1 1/2" X 11'-7"1 1/4" X 3'-0"1 1/4" X 1'-0" (TYP. 2)1 1/2" TEE1 1/2" X 1 1/4" REDUCER (TYP. 2)1 1/4" X 1'-0"1 1/4" 90° (TYP. 2)E1-N145-194726-190350 LB CYLINDERW/ 327 LBS CLEAN AGENTE1-N245-194726-1901 1/4" NOZZLE1 1/4" NOZZLE
POWER SUPPLY:**5 AMP MAXIMUM ALL EXTERNAL DEVICES**NOTE: EXTERNAL DEVICES INCLUDE ALL NOTIFICATION APPLIANCES,RELEASING SOLENOIDS, SLC INITIATING AND CONTROL DEVICESAND ALL DEVICES POWERED FROM THE PANEL POWER SUPPLY.TB #13 - AC/DC POWER SUPPLY UNIT5.4 A @ 27VDC 120 OR 240 VAC 50/60 Hz LINE VOLTAGENON-POWER LIMITEDTB #3 - BATTERY CONNECTIONSUPERVISED24 VDC NOMINALMAX. BATTERY SIZE 70 AHNON-POWER LIMITED - DEDICATED CIRCUITRELAYS (POWER OR NON-POWER LIMITED BUT NOT BOTH):TB #4, TB #8, TB #9 - PROGRAMMABLE RELAY SPDT FORM CCONTACTRATED FOR 1.0 AMPS @ 30 VDC (RESTRICTIVE)RATED FOR 0.5 AMPS @ 30 VDC (INDUCTIVE)RATED FOR 0.5 AMPS @ 120 VDC (INDUCTIVE)TB #10 - TROUBLE RELAY SPDT FORM C CONTACTRATED FOR 1.0 AMPS @ 30 VDC (RESTRICTIVE)RATED FOR 0.5 AMPS @ 30 VDC (INDUCTIVE)RATED FOR 0.5 AMPS @ 120 VDC (INDUCTIVE)AUXILIARY POWER:TB #2 - RESETABLE 24VDC POWER OUTPUTPOWER LIMITED AND SUPERVISED1 AMP MAXIMUM EACH CIRCUIT**5 AMP MAXIMUM ALL EXTERNAL DEVICES**NOTE: EXTERNAL DEVICES INCLUDE ALL NOTIFICATION APPLIANCES,RELEASING SOLENOIDS, SLC INITIATING AND CONTROLDEVICES AND ALL DEVICES POWERED FROM THE 24 Vdc POWERSUPPLY.SIGNALING LINE CIRCUIT (SLC):TB #1 SIGNALING LINE CIRCUIT WIRING REQUIREMENTSPOWER LIMITED AND SUPERVISEDUP TO 255 ADDRESSABLE DEVICESCLASS "B" STYLE 4350MA MAX / 28VDC MAX / 40 OHMS MAX / 20Pf PER FOOTTWISTED, UNSHIELDED, LOW-CAPACITANCE,ADDRESSABLE-FIRE ALARM WIRENOTIFICATION APPLIANCE CIRCUITS (NAC) AND RELEASINGCIRCUITS:TB #5 AND TB #14 NAC CIRCUITSPOWER LIMITED AND SUPERVISEDNOT "T" TAPPABLEREGULATED 24VDC, 1.5 AMPS MAX PER CIRCUITCLASS "B", STYLE "Y" / CLASS "A", STYLE "Z"MAXIMUM # SYNCHRONIZED DEVICES PER CIRCUIT IS 25TB # 11 AND TB #12 RELEASING CIRCUITSSERIES WIRED INITIATOR ASSEMBLIESSINGLE CONTROL HEAD OR SOLENOID VALVETWO SERIES-SUPERVISED, PARALLEL-ACTUATEDCONTROL HEADS OR SOLENOID VALVESMAX RELEASE CURRENT 2.4 AMPS PER CIRCUITTB #6 AND TB #7 COMBINATION CIRCUITSPROGRAMMED AS NAC CIRCUITS FUNCTION THE SAME ASABOVEPROGRAMMED AS RELEASE CIRCUITS CAN SUPPORT ONECONTROL HEAD OR ONE PRE-ACTION SOLENOID2134RS 4851234SLCNOCNCRELAY 1NOCNCRELAY 2NOCNCRELAY 3NONCCTROUBLE++--BATT OUT4
NAC2
3213421
NAC14312COMBO 24312COMBO 1342AUX 24VDC14321RELEASE 2432J8RS 232 AJ6J3J5J12N LRELEASE 1J4RS 232BUSB BS2J10JTAGAC INPSU120240STYLE 4BUZZER1To PSU Earth Ground)C1+(P L(-P()+()-(CPCP WSBWSA)C DEL)-(DE)+423 5 6 87 1 2 3 4 5 6 7
37C/N O/NMOCC)+()-()+PCPCP )-(CP(++----++POLARIZED NOTIFICATIONAPPLIANCE (TYPICAL)POLARIZED NOTIFICATIONAPPLIANCE (TYPICAL)TB2 AUXILIARY OUTPUTSREGULATED 24 VDC,CURRENT: 1.0 (MAX) EACH OUTPUTAC SUPPLY SELECT SWITCH (S4)SLC-STYLE SWITCH (S2)WHITEBLACKGREEN120 VAC, 50/60 Hz, 3.2 Aor240 VAC, 50/60 Hz, 1.6 A10K IN-LINE RELEASING DEVICE (LOCATEAS CLOSE AS POSSIBLE TO SOLENOID)5K IN-LINE RELEASING DEVICE (TYP 2)LOCATE AS CLOSE AS POSSIBLE TOSOLENOIDDETECTOR BASEAI MONITOR MODULEAO RELAY MODULEPROGRAMMABLERELAYSTROUBLERELAYCJPPFEPGHA / BGHFire Systems9405SILENCESCROLLSYSTEMRESETACKNOWLEDGE386172SUPERVISORYSYSTEM TROUBLESILENCEAC POWERALARMPRE-ALARMSYSTEMSOLENOIDBLKREDSOLENOIDBLKREDSOLENOIDBLKREDTB1TB15TB12TB11TB2TB7TB6TB5 TB14TB13TB3 TB4TB8TB9TB10
10k EOLARIES TYPICAL WIRING DIAGRAMSHEET NUMBER:SHEET TITLE:COMPLIANCEDATEREVDESCRIPTIONDATENICETCERTIFIEDNATHAN SCHERNECKNICET #111032 - LEVEL 4, FIRE ALARMPROJECT INFORMATION:1234DESIGNED BY:DRAWN BY:CHECKED BY:JOB NUMBER:SUBMITTALSNICET STAMPSMANUFACTURER LOGO'SFIRE PROTECTION ENGINEERS STAMPSCALE:NOT TOSCALEUNLESSNOTEDOTHERWISESUPPESSION SYSTEMS INC.SPECIAL HAZARDS FIRE PROTECTION3077 20TH STREET EAST, SUITE BFIFE, WA 98424-1798(253) 926-3300 FAX (253)926-3306RTMYELM MIDDLE SCHOOL
402 WEST YELM AVENUE
YELM, WASHINGTON 98597NMRJACZST2035FIRE SUPPRESSION SYSTEMMULTI LINE WIRINGDIAGRAMFP-3.1 of 7100% SUBMITTAL07/15/20KiddeFire Systems
)C1+(P L(-P()+()-(CPCP WSBWSA)C DEL)-(DE)+423 5 6 87
SLC FROM PREVIOUSDEVICE OR FACPSLC TO NEXTDEVICE OR FACPAI MonitorModuleADDRESSABLE MONITOR MODULEWIRING DETAILABORT STATIONRELEASE STATIONPRESSURE SWITCHDETECTORSMAINTENANCE BYPASSCONTROL HEAD MONITORPRE-ACTION WATERFLOW SWITCHPRE-ACTION TAMPER SWITCHPRE-ACTION LOW AIR SWITCHE.O.L.
10K -+-+37DETECTOR BASEPHOTOELECTRIC OR HEAT DETECTORWIRING DETAILOBSERVE POLARITY( + )( - )( + )( - )SLC INSLC INSLC OUTSLC OUTN.C.N.O.+-KEY-OPERATEDMAINTENANCEBYPASS SWITCHAUX POWERFROM RELEASEPANELTOINPUTMODULE24VDC SOLENOIDKEY OPERATED MAINTENANCE BYPASSSWITCH WIRING DETAILR-NAC FROMRELEASEPANEL+-ADDRESSABLEPANEL4 X 4 EXTRA DEEP BOXGENERAL VERTICAL TANKSOLENOID WIRING DETAIL1 / 2" FLEX CONDUIT NOT TO EXCEED 3'-0" INLENGTHSINGLE GANG BOX CLOSE NIPPLEDTO TANK SOLENOIDTANKSOLENOIDCONTROL HEAD MONITORCONTROL HEAD MONITOR WIRINGEOLBLUEBLUEWHITEWHITECONTROL HEADMONITOROPEN WHEN INACTIVATED POSITIONTO INPUTMODULEADDRESSABLENAC INCEILING MOUNTNAC OUTWALL MOUNTPOTTER STROBE WALLAND CEILING MOUNT WIRING DETAILNAC INNAC OUTCLEAN AGENTSTROBESNAC INCEILING MOUNTNAC OUTWALL MOUNTPOTTER HORN STROBE WALLAND CEILING MOUNT WIRING DETAILNAC IN NAC OUT 4 WIRE CLEAN AGENTHORN / STROBESNAC INNAC OUTNAC OUT
NAC INORANGE PAIR 16 AWG SOLIDBLUE PAIR 16 AWG SOLIDVX WIRE LEGENDRED (+) BLACK ( - ) 16 AWG SOLID TWISTEDRED (+) BLACK ( - ) 16 AWG SOLID TWISTEDGRAY (+) BLACK ( - ) 16 AWG SOLID TWISTEDVIOLET (+) BLACK ( - ) 16 AWG SOLID TWISTEDYELLOW (+) BLACK ( - ) 16 AWG SOLID TWISTEDORANGE (+) BLACK( - ) 16 AWG SOLID TWISTEDBLUE (+) BLACK( - ) 16 AWG SOLID TWISTEDGRAY (+) BLACK ( - ) 16 AWG SOLID TWISTEDVIOLET (+) BLACK ( - ) 16 AWG SOLID TWISTEDYELLOW PAIR 16 AWG SOLIDRS 232 CABLERED (+) BLACK ( - ) 14 AWG SOLID TWISTEDBLUE (+) BLACK ( - ) 14 AWG SOLID TWISTEDBELDON 9841 EIA RS-485 LOW CAPACITANCE CABLEYELLOW (+) BLACK ( - ) 16 AWG SOLID TWISTEDE P SR N M H K J G F C D B A TVIOLET (+) BLACK ( - ) 14 AWG SOLID TWISTEDFERS-232
NETWORK INTERFACEJ3TB7GNCOMBO 1
COMBO 2 TB14NAC 2NAC 1TB5SLCTB1TB4RELAY 1RELAY 2RELAY 3RELAY 4KIDDE ARIESCONTROL PANELBATTERYAC POWERTB8TB9TB10120VAC INPUT POWERWIRING BY OTHERSTB3TB13RS-485TB15USB
J5PJ8RS-232CJTB6AUX 1 & 2
RELEASE 2
RELEASE 1
A / BPMHTB2TB11TB12WIRING BY OTHERSTO BUILDING FIREALARM PANELALARMSUPERVISORYWATER FLOWTROUBLESOLILREOLMHHFN30 cd0.158 AE30 cd0.130 AEOLKA1-003CAIKEOL1-002CAIEOLAI1-001CEOLCHMEOLEOLHNKKAI1-006CKAB350 LB. CYLINDERW/ 327 LBS. OF AGENTVAIC1-012HSSDFIRE 1HSSDAVVANOMINAL: 0.220 AALARM: 0.295 AVESDA VLF-250 DETECTORTERMINATION DETAIL10987654321TERMINAL BLOCK1 GPI PIN 12 GPI PIN 23 DISPLAY TX4 DISPLAY RX5 DISPLAY COMM GND6 DISPLAY POWER -7 DISPLAY POWER +8 POWER IN (+)9 POWER IN (-)10 POWER OUT (+)11 POWER OUT (-)12 NC - FAULT RELAY13 COMMON (ORANGE)14 NO15 NC - ACTION RELAY16 COMMON (PURPLE)17 NO18 NC - FIRE 1 RELAY19 COMMON (RED)20 NOFIRE2FIRE1ACTIONALERT10 1/16"SIDE3"7 1/5"AIR INLET PORT24VDC FROM VESDAPOWER SUPPLYTERMINAL BLOCK1234567891011121314151617181920CEILING SMOKE OR HEAT DETECTORGENERAL SPACING DETAIL36" MAXSSSSS12SS = SPACE BETWEEN DETECTORS = SMOKE DETECTOR OR HEAT DETECTORXLEOL1-017CAIXEOLFL1-019CAIXEOLTC1-018AIC1-021PEOLVAIC1-011HSSDACTIONVAIC1-010HSSDFAULTVSOLPRE-ACTIONRISERILRMMG0.054 A6"EOLAI1-004CEPOSHEET NUMBER:SHEET TITLE:COMPLIANCEDATEREVDESCRIPTIONDATENICETCERTIFIEDNATHAN SCHERNECKNICET #111032 - LEVEL 4, FIRE ALARMPROJECT INFORMATION:1234DESIGNED BY:DRAWN BY:CHECKED BY:JOB NUMBER:SUBMITTALSNICET STAMPSMANUFACTURER LOGO'SFIRE PROTECTION ENGINEERS STAMPSCALE:NOT TOSCALEUNLESSNOTEDOTHERWISESUPPESSION SYSTEMS INC.SPECIAL HAZARDS FIRE PROTECTION3077 20TH STREET EAST, SUITE BFIFE, WA 98424-1798(253) 926-3300 FAX (253)926-3306RTMYELM MIDDLE SCHOOL
402 WEST YELM AVENUE
YELM, WASHINGTON 98597NMRJACZST2035FIRE SUPPRESSION SYSTEMELECTRICAL DETAILS ANDSINGLE LINEFP-3.2 of 7100% SUBMITTAL07/15/20KiddeFire Systems
1 1/2" AND 2" VALVE DETAILSOUTLET CAPMUST USE VALVEOUT ADAPTERPRESSURE GAUGEVALVEACTUATION PORTSAFETY PLUGLIQUID LEVEL INDICATORWARNING:VALVE OUTLET ADAPTER DETAILSSizeDIMENSIONS ( IN INCHES )A -NPTCD1½1.8742.692 12 HEX2BDC1 12 TO11 122.512 UNJ3.123 HEX2 TO 1112(A)SYSTEM PIPE CONNECTION(B)VALVE OUTLET CONNECTIONELECTRIC CONTROL HEAD1 1/2" AND 2" VALVE DETAILSElectric Control HeadStackableDimension5.28 in.3.00 in.7.80 in.2.90 in.Electric Control HeadStackable (Explosion Proof)VoltageAmps24 Vdc0.20 continuous24 Vdc0.27 continuousAB1.25-18UNEF-2ACONNECTION1/2"-14NPTCONDUITCONNECTION(3)18AWG-LEADS18in.LONGSWIVEL NUT1.25-18UNEF-2BCONNECTIONBACylinderDimensionsACD10 LB CYLINDER8.52 in.11.00 in.3/8 in.7.38 in.20 LB CYLINDER8.52 in.11.00 in.3/8 in.12.50 in.40 LB CYLINDER10.69 in.13.00 in.3/8 in.10.63 in.70 LB CYLINDER10.69 in.13.00 in.3/8 in.20.00 in.125 LB CYLINDER14.56 in.18.00 in.9/16 in.20.88 in.200 LB CYLINDER14.56 in.18.00 in.9/16 in.29.63 in.350 LB CYLINDER17.88 in.21.00 in.9/16 in.37.13 in.600 LB CYLINDER25.75 in.27.00 in.9/16 in.38.50 in.900 LB CYLINDER25.75 in.30.00 in.9/16 in.48.50 in.A(TYP)ANCHORSTUDWALLUNISTRUTCYLINDERSUPPORTCYLINDERSTRAPUNISTRUTFLOORLEVELC(BOLTSIZE)CYLINDER(TYP)BDCYLINDER STRAP DETAILSBBB6.48"8.62"8.16"10.69"12.93"14.56"24.83"26.00"21.56"24.12"15.50"17.88"10 - 20 lb.CYLINDERS40 - 70 lb.CYLINDERS125 - 200 lb.CYLINDERS350 lb.CYLINDER600 lb.CYLINDER900 lb.CYLINDER8"6"15-015-05"4"15-015-03"2-1/2"15-015-015-03-1/2"2"1-1/4"1-1/2"12-015-01"3/4"12-0N/ASIZE (in.)THREADED LIGHTWALLSTEEL PIPE EXCEPTNOMINAL PIPETHREADED LIGHTWALLMAXIMUM DISTANCE BETWEEN HANGERS15-0N/A15-0N/A15-0N/AN/AN/AN/AN/A15-0N/AN/A15-0N/AN/AN/AN/AN/AN/A12-012-09-012-0N/AN/AN/AN/A15-06-610-07-010-03-114-55-04-76-08-05-68-03-42-113-9N/ACPVCCOPPER TUBEPOLYBUTYLENE (IPS)POLYBUTYLENE (CTS)5-55-118-012-0N/AN/AN/AN/AN/A12-012-012-012-012-012-0N/ASTEEL PIPE·NFPA 13 2013 EDITION TABLE 9.2.2.1·FSSA PIPE DESIGN GUIDE FOR USE WITH SPECIAL HAZARD FIRE SUPPRESSION SYSTEMSMINIMUM PIPING REQUIREMENTS FOR CLEAN AGENT SYSTEMS 8" NPSA-53 FURNACE" F "801/2" NPSXXXX1) THREADED FITTINGS SHALL BE MALLEABLE IRON CLASS 300 ( EXTRA HEAVY ) AND CONFORM TO ANSI B16.3 WITH A MINIMUM2) GROOVED FITTINGS SHALL MEET A MINIMUM 1000 PSI. WORKING PRESSURE. WHICH MAY BE GRUVLOK FIG. 7001 STANDARD OR8" NPS 7007 RIGIDLOCK OR COMPARABLE. LIGHT WEIGHT FITTINGS SHALL NOT BE USED.WORKING PRESSURE OF 1000 PSI. 150 LB. FITTINGS SHALL NOT BE USED.A-53 FURNACENOTES:" F "1204" NPSXXXX8" NPS8" NPS8" NPS8" NPS8" NPS8" NPS8" NPS8" NPS8" NPS8" NPS8" NPS8" NPS8" NPS8" NPS8" NPS8" NPSMAX. SIZE( WITH CHARGING PRESSURES UP TO AND INCLUDING 360 PSI )A-53 ERW" A "A-53 ERWA-53 ERWA-53 FURNACEA-53 ERW" F "" B "" B "" B "A-106 / A-53 SEAMLESSA-106 / A-53 SEAMLESSA-53 ERWA-53 ERW" A "" A "" C "" C "1204" NPS4012040801/2" NPS4" NPS1/2" NPS1/2" NPS4080801201/2" NPS1/2" NPS1/2" NPS4" NPSA-106 / A-53 SEAMLESSA-106 / A-53 SEAMLESSA-106 / A-53 SEAMLESSA-106 / A-53 SEAMLESSA-106 SEAMLESS" B "" B "" C "" B "" A "A-106 SEAMLESSA-106 SEAMLESSASTM STANDARDGRADE" A "" A "8012040401201/2" NPS4" NPS1/2" NPS1/2" NPS4" NPSSCHEDULE4080MIN. SIZE1/2" NPS1/2" NPSXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXROLL GROOVEDXXXXXXXXXXXXXXXXXXXXXXXXTHREADEDXXXXLNOTE : WHEN MOUNTING TO STUD WALL CONSTRUCTION, BACKING MATERIAL MUST BE INSTALLED IN THE WALL AT 44.0" AFF C . USE 3/8" x 2" WOOD LAG BOLTS. PRE-DRILL HOLES PRIOR TO INSTALLATION OF LAG BOLTS TO MOUNT STRUT. FILL RANGE 150 - 350 POUNDS.VERTICAL FLOOR MOUNTING DETAILFOR 350 POUND CYLINDER1 5/8" STRUTMOUNTING SURFACE16.19"58.36"44.0"AFF16"FINISH FLOOR2" ACTUATION VALVE281866 MOUNTING STRAP53.1"KIDDE ECS NOVEC TEE ORIENTATIONAND DISTRIBUTION DETAIL100% IN25% - 50% OUT50% - 75% OUT10% - 35% OUT65% - 90% OUT100% INBULL TEESIDE TEE·BULL TEES MUST HAVE BOTH OUTLETS IN THE HORIZONTAL PLANE. THEINLET TO A BULL TEE MAY APPROACH IN A HORIZONTAL, VERTICALLY UP ORVERTICALLY DOWN DIRECTION.·SIDE TEES MUST HAVE THE INLET AND BOTH OUTLETS ALL IN THEHORIZONTAL PLANE.·ELBOWS EITHER BEFORE A TEE, OR AFTER, WHICH SPLIT TO A SEPARATEHAZARD MUST BE LOCATED A MINIMUM DISTANCE OF 10 PIPE DIAMETERS(NOMINAL) BEFORE THE TEE.·TEE SPLITS GOING TO SEPARATE HAZARDS FROM A COMMON SUPPLY LINEMUST BE SPACED A MINIMUM OF 10 PIPE DIAMETERS (NOMINAL) APART.KIDDE ECS NOVEC 360° NOZZLEPLACEMENT AND COVERAGE35'-7"35'-7"NOZZLE MAX PROTECTED HEIGHT IS 16'-0", THE MIN PROTECTED HEIGHT 1'-0"NOZZLE MUST BE PERPENDICULAR TO THE CEILING OR SUB-FLOOR SURFACE.NOZZLE MUST BE INSTALLED WITHIN 6" ± 2" OF THE CEILING OR WALLD = 25.2'MAX. AREA OF COVERAGE 1,266 SQ. FT.UNISTRUT BRACING MOUNTING DETAILSDISCHARGE PIPINGUNISTRUT PIPECLAMP OR EQUALDISCHARGE PIPINGUNISTRUT PIPECLAMP OR EQUALDISCHARGE PIPINGWALL MOUNTSECURE UNISTRUT TOSTRUCTURAL MEMBER4-WAY EARTHQUAKE BRACE2-WAY EARTHQUAKE BRACEUNISTRUT PIPECHANNEL OR EQUALUNISTRUT PIPECLAMP OR EQUALWALL MOUNT BRACE45°45°45°CEILING/WALL STRUCTURAL MEMBERUNISTRUT PIPECLAMP OR EQUALDISCHARGE PIPINGUNISTRUT CHANNELOR EQUALWALL MOUNTING PLATESECURE TO STRUCTURALMEMBERCONCRETE CEILINGQUICK BOLTCOUPLERALL THREADSIZE ACCORDINGTO PIPE DIAMETERRING HANGERDISCHARGE PIPINGUNISTRUT CHANNELOR EQUALUNISTRUT PIPE CLAMPOR EQUALSECURE UNISTRUT TO FLOORAS SHOWN OR CEILING MOUNTDISCHARGE PIPINGUNISTRUT BRACERING HANGER BRACEWALL MOUNT PLATE BRACERIGID FOUR WAY NOZZLEBRACING DETAILNOZZLECEILINGSTRUCTURESYSTEMPIPING3 424 5123 43 44 52114 564 523 41 STRUT2 ANGLE BRACKET3 HEX NUT4 BOLT5 SPRING NUT6 PIPE CLAMPSHEET NUMBER:SHEET TITLE:COMPLIANCEDATEREVDESCRIPTIONDATENICETCERTIFIEDNATHAN SCHERNECKNICET #111032 - LEVEL 4, FIRE ALARMPROJECT INFORMATION:1234DESIGNED BY:DRAWN BY:CHECKED BY:JOB NUMBER:SUBMITTALSNICET STAMPSMANUFACTURER LOGO'SFIRE PROTECTION ENGINEERS STAMPSCALE:NOT TOSCALEUNLESSNOTEDOTHERWISESUPPESSION SYSTEMS INC.SPECIAL HAZARDS FIRE PROTECTION3077 20TH STREET EAST, SUITE BFIFE, WA 98424-1798(253) 926-3300 FAX (253)926-3306RTMYELM MIDDLE SCHOOL
402 WEST YELM AVENUE
YELM, WASHINGTON 98597NMRJACZST2035FIRE SUPPRESSION SYSTEMMECHANICAL DETAILSFP-4.1 of 7100% SUBMITTAL07/15/20KiddeFire Systems