2020.0232.FR0013 Material Submittals_ Fort Stevens ESSEP 2019 GFS-100 PAGE 1 OF 6
GENERAL DESCRIPTION
Globe Series GL-QR sprinklers are Listed Quick Response
sprinklers which utilize a 3mm frangible glass bulb as the
thermosensitive operating element. These sprinklers are
available in upright, pendent, and recessed pendent orien-
tations. They are Listed and Approved as Standard Cover-
age sprinklers and are to be installed in accordance with
the guidelines of the appropriate Installation Standard being
mandated by the AHJ (i.e. NFPA 13; FM 2-0). These sprin-
klers are available in various K-factors, temperatures and
finishes as shown. Recessed escutcheons with either ½”
or ¾” vertical adjustment are available (See Approvals Ta-
bles for appropriate sprinkler/escutcheon combinations and
Listings). Some pendent models are additionally available
with a special “Seismic” escutcheon to meet the IBC-ASCE/
SEI 7 requirements for use in seismic design categories C,
D & E.
TECHNICAL DATA
SIN
• Upright: GL2815, GL4215, GL5615, GL8115, GL8118
• Pendent, Recessed Pendent: GL2801, GL4201,
GL5601, GL8101, GL8106
Approvals
• cULus • FM • LPCB • CE
• See Approval Tables
Maximum Working Pressure
• 175 psi (12 bar)
• Factory tested to 500 psi (34 bar)
Minimum Operating Pressure
• 7 psi (48 kPa)
Temperature Rating
• See Approval Tables
Materials of Construction
• Frame - bronze • Deflector - brass • Screw - brass
• Lodgement Wire - stainless steel • Bulb seat - copper
• Spring - nickel alloy • Seal - teflon
• Bulb - glass with alcohol based solution, 3mm
• Escutcheon Assembly - carbon steel
SERIES GL-QR STANDARD COVERAGE, QUICK RESPONSE
UPRIGHT, PENDENT & RECESSED PENDENT SPRINKLERS
K-FACTOR: 2.8, 4.2, 5.6, 8.0
FINISHES AND ACCESSORIES
Finishes
• Factory Bronze • Chrome • White Polyester
• Black Polyester - special order
Escutcheons
• Brass • Chrome • White Polyester • Black Polyester
Wrenches
• Standard • Recess • 1/2” NPT • 3/4” NPT
UPRIGHT
RECESSED PENDENT
RECESSED PENDENT
SEISMIC IBC/ASCE/SEI CODES
PENDENT
OPERATION
Upon exposure to heat such as from a fire, the fluid in the
bulb expands, compressing the air bubble within the bulb.
When the air bubble can no longer compress, the fluid ex-
pansion causes breakage of the glass bulb, resulting in re-
lease of the water seat assembly, and discharge of water
from the sprinkler.
4077 Airpark Dr. Standish, MI 48658 • 989-846-4583 • www.globesprinkler.com
Technical Support • 989-414-2600 • techservice@globesprinkler.com
NOTE:
Users should refer to Globe’s web site (www.globesprinkler.com)
to ensure that the most recent technical literature is being utilized.
NOTE:
Corrosion resistant coatings, where applicable, are utilized to
extend the life of copper alloy sprinklers beyond that which would
otherwise be expected when exposed to corrosive atmospheres.
Although corrosion resistant coated sprinklers have passed the
standard corrosion tests of the applicable approval agencies,
the testing is not representative of all possible corrosive atmo-
spheres. Consequently, it is recommended that the end user be
consulted with respect to the suitability of these coatings for any
given corrosive environment. The effects of ambient temperature,
concentration of chemicals, humidity, and gas/chemical velocity,
should be considered, as a minimum, along with the corrosive
nature of the chemical to which the sprinklers will be exposed.
SERIES GL-QR STANDARD COVERAGE, QUICK RESPONSE UPRIGHT, PENDENT & RECESSED PENDENT SPRINKLERS K-FACTOR: 2.8, 4.2, 5.6, 8.0 SERIES GL-QR STANDARD COVERAGE, QUICK RESPONSE UPRIGHT, PENDENT & RECESSED PENDENT SPRINKLERS K-FACTOR: 2.8, 4.2, 5.6, 8.0 GFS-100 GFS-100
SEP 2019 GFS-100 PAGE 2 OF 6
NOTICE
Do not install any bulb-type sprinkler if the bulb is cracked or there is loss of liquid from the bulb. Sprinklers should be tightened enough to obtain a leak-tight joint when water pressure is applied and/or hydrostatic test is performed. Sprinklers should not be overtightened as this can result in distortion and subsequent leak-age. It is recommended not to exceed 14 ft.-lb. (19.0 Nm) torque for 1/2 inch NPT sprinkler threads; 20 ft.-lb. (26.8 Nm) to 3/4 inch NPT threads.
Step1. Sprinklers must be properly oriented.
Step2. With pipe thread sealant applied to the pipe
threads, hand tighten the sprinkler into the sprin-
kler fitting. Note: Do not grasp the sprinkler by
the deflector.
Step3. Wrench-tighten the sprinkler using only the
appropriate wrench. Wrenches are only to be
applied to the sprinkler wrench flats or wrench
hex as applicable. Note: Do not apply wrench to
frame arms.
INSTALLATION
CARE AND MAINTENANCE
Prior to installation, it is important to read and follow the
“Sprinkler Caution” sheet (GFS-840) included within each
box of sprinklers. This sheet is available on Globe’s web
site (www.globesprinkler.com).
Store sprinklers in a cool, dry place. Exposure to extreme
heat will damage the thermal sensing element, possibly re-
sulting in premature activation. Avoid direct sunlight.
Replace any sprinkler that shows any corrosion, damage,
or loss of liquid from the glass bulb.
Do not attempt to paint or alter the sprinkler’s coating in any
manner after leaving the manufacturing plant.
Do not attach wiring, ropes, decorations or fixtures to a
sprinkler.
Absence of an escutcheon, used to cover a ceiling hole,
may delay sprinkler operation in a fire situation.
It is the owner’s responsibility for inspection, testing and
maintenance of the fire sprinkler system with all components
and devices in accordance with the National Fire Protection
Association Pamphlet 25 as well as any other requirements
as set forth by the local Authority Having Jurisdiction (AHJ).
FIGURE 1: STANDARD SPRINKLER WRENCH
½" NPT P/N 325390
¾" NPT P/N 312366
FIGURE 2: RECESSED SPRINKLER WRENCH
½" NPT P/N 325391
¾" NPT P/N 325401
SEP 2019 GFS-100 PAGE 3 OF 6
SIN GL2815 GL4215 (1)GL5615 (1)GL8115 *GL8118 (1)
ORIENTATION UPRIGHT UPRIGHT UPRIGHT UPRIGHT UPRIGHT
K-FACTOR 2.8 (40 metric)4.2 (60 metric)5.6 (80 metric)8.0 (115 metric)8.0 (115 metric)
NPT 1/2” (15mm)1/2” (15mm)1/2” (15mm)1/2” (15mm)3/4” (20mm)
HAZARD L.H.L.H L.H./O.H.L.H./O.H.L.H./O.H.
cULus Listed
135°F (57°C)
155°F (68°C)
175°F (79°C)
200°F (93°C)
286°F (141°C)
135°F (57°C)
155°F (68°C)
175°F (79°C)
200°F (93°C)
286°F (141°C)
135°F (57°C)
155°F (68°C)
175°F (79°C)
200°F (93°C)
286°F (141°C)
135°F (57°C)
155°F (68°C)
175°F (79°C)
200°F (93°C)
286°F (141°C)
135°F (57°C)
155°F (68°C)
175°F (79°C)
200°F (93°C)
286°F (141°C)
FM Approved NA NA
135°F (57°C)
155°F (68°C)
175°F (79°C)
200°F (93°C)
286°F (141°C)
NA
135°F (57°C)
155°F (68°C)
175°F (79°C)
200°F (93°C)
286°F (141°C)
LPCB
Ref. No. 147c/05 NA NA
135°F (57°C)
155°F (68°C)
175°F (79°C)
200°F (93°C)
286°F (141°C)
NA
135°F (57°C)
155°F (68°C)
175°F (79°C)
200°F (93°C)
286°F (141°C)
CE NA NA
135°F (57°C)
155°F (68°C)
175°F (79°C)
200°F (93°C)
286°F (141°C)
NA
135°F (57°C)
155°F (68°C)
175°F (79°C)
200°F (93°C)
286°F (141°C)
TABLE A: UPRIGHT SPRINKLER APPROVALS
* FOR RETROFIT USE ONLY
(1) cULus LISTED CORROSION RESISTANT WITH POLYESTER COATING.
FIGURE 3: SERIES GL-QR UPRIGHT SPRINKLERS
GL2815, GL4215, GL5615, GL8115
FIGURE 4: SERIES GL-QR UPRIGHT SPRINKLERS
GL8118
SEP 2019 GFS-100 PAGE 4 OF 6
SIN GL2801 GL4201 (1)GL5601 (1)GL8101 *GL8106 (1)
ORIENTATION PENDENT PENDENT PENDENT PENDENT PENDENT
K-FACTOR 2.8 (40 metric)4.2 (60 metric)5.6 (80 metric)8.0 (115 metric)8.0 (115 metric)
NPT 1/2” (15mm)1/2” (15mm)1/2” (15mm)1/2” (15mm)3/4” (20mm)
HAZARD L.H.L.H L.H./O.H.L.H./O.H.L.H./O.H.
cULus Listed
135°F (57°C)
155°F (68°C)
175°F (79°C)
200°F (93°C)
286°F (141°C)
135°F (57°C)
155°F (68°C)
175°F (79°C)
200°F (93°C)
286°F (141°C)
135°F (57°C)
155°F (68°C)
175°F (79°C)
200°F (93°C)
286°F (141°C)
135°F (57°C)
155°F (68°C)
175°F (79°C)
200°F (93°C)
286°F (141°C)
135°F (57°C)
155°F (68°C)
175°F (79°C)
200°F (93°C)
286°F (141°C)
FM Approved NA NA
135°F (57°C)
155°F (68°C)
175°F (79°C)
200°F (93°C)
286°F (141°C)
NA
135°F (57°C)
155°F (68°C)
175°F (79°C)
200°F (93°C)
286°F (141°C)
LPCB
Ref. No. 147c/05 NA NA
135°F (57°C)
155°F (68°C)
175°F (79°C)
200°F (93°C)
286°F (141°C)
NA
135°F (57°C)
155°F (68°C)
175°F (79°C)
200°F (93°C)
286°F (141°C)
CE NA NA
135°F (57°C)
155°F (68°C)
175°F (79°C)
200°F (93°C)
286°F (141°C)
NA
135°F (57°C)
155°F (68°C)
175°F (79°C)
200°F (93°C)
286°F (141°C)
TABLE B: PENDENT SPRINKLER APPROVALS
* FOR RETROFIT USE ONLY
(1) cULus LISTED CORROSION RESISTANT WITH POLYESTER COATING.
FIGURE 5: SERIES GL-QR PENDENT SPRINKLERS
GL2801, GL4201, GL5601, GL8101
FIGURE 6: SERIES GL-QR PENDENT SPRINKLERS
GL8106
SEP 2019 GFS-100 PAGE 5 OF 6
FIGURE 8: SEISMIC RECESSED ESCUTCHEON
Meets IBC-ASCE/SEI 7 Codes for Seismic areas C, D, & E.
A A
4 1/2" (114mm) DIA.
3 7/8" (98mm)-
4"(101mm) DIA. MIN.
HOLE IN CEILING
1 29/32" (48mm) DIA.
1/8" (3mm) MIN.
5/8" (16mm) MAX. -
1/2" (12mm) ADJ.
7/8" (22mm) MAX. -
3/4" (19mm) ADJ.
1/4"(6mm)
1" (25mm) MIN.
1 1/2" (38mm) MAX. - 1/2" ADJ.
1 3/4" (44mm) MAX. - 3/4" ADJ.
CEILING CUP
RETAINER
REDUCER
2 15/16" DIA.
2" DIA. MIN.
HOLE IN CEILING
1 29/32" DIA.
1/8"1" MIN.
1 3/4" MAX.
1/8" MIN.
5/8" MAX. - 1/2" ADJ.
7/8" MAX. - 3/4" ADJ.
REDUCER
RETAINER
CUP
CEILING
FIGURE 7: RECESSED ESCUTCHEON
SIN GL2801 (2)GL4201 (1) (2)GL5601 (1) (2)GL8101 * (1) (2)GL8106 (1) (2) (3)
ORIENTATION RECESSED PEND.RECESSED PEND.RECESSED PEND.RECESSED PEND.RECESSED PEND.
K-FACTOR 2.8 (40 metric)4.2 (60 metric)5.6 (80 metric)8.0 (115 metric)8.0 (115 metric)
NPT 1/2”1/2”1/2”1/2”3/4”
HAZARD L.H.L.H L.H./O.H.L.H./O.H.L.H./O.H.
cULus Listed
135°F (57°C)
155°F (68°C)
175°F (79°C)
200°F (93°C)
286°F (141°C)
135°F (57°C)
155°F (68°C)
175°F (79°C)
200°F (93°C)
286°F (141°C)
135°F (57°C)
155°F (68°C)
175°F (79°C)
200°F (93°C)
286°F (141°C)
135°F (57°C)
155°F (68°C)
175°F (79°C)
200°F (93°C)
286°F (141°C)
135°F (57°C)
155°F (68°C)
175°F (79°C)
200°F (93°C)
286°F (141°C)
FM Approved
Note: ½” Adjustable Recessed
Escutcheon only
NA NA
135°F (57°C)
155°F (68°C)
175°F (79°C)
200°F (93°C)
NA
135°F (57°C)
155°F (68°C)
175°F (79°C)
200°F (93°C)
LPCB
Ref. No. 147c/05 NA NA
135°F (57°C)
155°F (68°C)
175°F (79°C)
200°F (93°C)
286°F (141°C)
NA
135°F (57°C)
155°F (68°C)
175°F (79°C)
200°F (93°C)
286°F (141°C)
CE NA NA
135°F (57°C)
155°F (68°C)
175°F (79°C)
200°F (93°C)
NA
135°F (57°C)
155°F (68°C)
175°F (79°C)
200°F (93°C)
TABLE C: RECESSED PENDENT SPRINKLER APPROVALS
TABLE E: SEISMIC ESCUTCHEONS
3/4" ADJUSTABLE FRICTION FIT RECESSED ESCUTCHEON
(SEISMIC)
FINISH 1/2” NPT 3/4” NPT
Chrome 326170 326177
White 326172-W 326178-W
1/2" ADJUSTABLE FRICTION FIT RECESSED ESCUTCHEON
(SEISMIC)
FINISH 1/2” NPT 3/4” NPT
Chrome 326201 326208
White 326203-W 326210-W
TABLE D: STANDARD ESCUTCHEONS
3/4" ADJUSTABLE FRICTION FIT RECESSED ESCUTCHEON
FINISH 1/2” NPT 3/4” NPT
Chrome 325422 325423
Brass 325424 325420
White Polyester 325426-W 325427-W
Black Polyester 325426-B 325427-B
Stainless Steel 326140 NA
1/2" ADJUSTABLE FRICTION FIT RECESSED ESCUTCHEON
FINISH 1/2” NPT 3/4” NPT
Chrome 332071 326040
Brass 332072 326041
White Polyester 332073-W 326042-W
Black Polyester 332073-B 326042-B
* FOR RETROFIT USE ONLY
(1) cULus LISTED CORROSION RESISTANT SPRINKLER WITH POLYESTER COATING
(2) cULus / LPCB /CE APPROVED WITH 1/2" ADJUSTABLE AND 3/4" ADJUSTABLE RECESSED ESCUTCHEON
(3) FM APPROVED FOR BRASS FINISH ONLY
SEP 2019 GFS-100 PAGE 6 OF 6
PART NUMBER
SIN + TEMPERATURE + FINISH
XXXX XXX XX
SIN TEMPERATURE FINISH
GL2815 2815 135 135°F (57°C)01 BRONZE
GL4215 4215 155 155°F (68°C)02 CHROME
GL5615 5615 175 175°F (79°C)03 WHITE POLYESTER
GL8115 8115 200 200°F (93°C)04 BLACK POLYESTER
GL8118 8118 286 286°F (141°C)
GL2801 2801
GL4201 4201
GL5601 5601 Note: All combinations may not be available.
Refer to Listing/Approval Tables for available listed combinations.GL8101 8101
GL8106 8106
TABLE F: PART NUMBER SELECTION
GLOBE® PRODUCT WARRANTY
Globe agrees to repair or replace any of its manufactured
products found to be defective in material or workmanship
for a period of one year from date of shipment.
For specific details of our warranty please refer to Price List
Terms and Conditions of Sale (Our Price List).
4077 Airpark Dr. Standish, MI 48658 • 989-846-4583 • www.globesprinkler.com
Technical Support • 989-414-2600 • techservice@globesprinkler.com
ORDERING INFORMATION
• SPRINKLER
• ESCUTCHEON
• WRENCH
• Quantity • Finish • Part Number (See TABLE D & TABLE E)
• Quantity • SIN • Orientation • Orifice • NPT • Temperature Rating
• Finish • Part Number (See TABLE F)
• Quantity • Part Number
1/2” NPT Standard . . . . . . . . . . . . . . . . . . . .325390
3/4” NPT Standard . . . . . . . . . . . . . . . . . . . .312366
1/2” NPT Recess . . . . . . . . . . . . . . . . . . . . .325391
3/4” NPT Recess . . . . . . . . . . . . . . . . . . . . .325401
SPECIFY:
PROJECT:
ENGINEER:
LOCATIONS:
CONTRACTOR:
SPECIFICATION REFERENCE:
DATE:
SYSTEM TYPE:
COMMENTS:
SUBMITTAL INFORMATION
FM Approved and Fully Listed Sprinkler Pipe
Wheatland Tube’s Schedule 10 and Schedule
40 steel fire sprinkler pipe is FM Approved
and UL® and C-UL Listed.
Approvals and Specifications
Schedule 10 and Schedule 40 meet or exceed
the following standards:
• ASTM A135, Type E, Grade A
(Schedule 10, 1–8 NPS)
• ASTM A795, Type E, Grade A
(Schedule 40, 1–2 NPS)
• ASTM A53, Type E, Grade B
(Schedule 40, 2–8 NPS)
• ASTM A53, Type F, Grade A
(Schedule 40, 1–4 NPS)
• NFPA® 13 and NFPA 14
Manufacturing Protocols
Schedule 10 and Schedule 40 are subjected
to the toughest possible testing protocols to ensure
the highest quality and long-lasting performance.
Finishes and Coatings
All Wheatland black steel fire sprinkler pipe
receives a proprietary mill coating to ensure a
clean, corrosion-resistant surface that outperforms
and outlasts standard lacquer coatings. This
coating allows the pipe to be easily painted,
without special preparation. Schedule 10 and
Schedule 40 can be ordered in black or hot-dip
galvanized, to meet FM / UL requirements for dry
systems that meet the zinc coating specifications
of ASTM A795 or A53.
Product Marking
Each length of Wheatland fire sprinkler
pipe is continuously stenciled to show
the manufacturer, type of pipe, grade, size
and length. Bar coding is acceptable as a
supplementary identification method.
Fire Sprinkler Pipe
Schedule 10 and Schedule 40
Submittal Data Sheet
BLACK HOT-DIP GALVANIZED
info@wheatland.com
wheatland.com
Follow us on Twitter:
@WheatlandTube
700 South Dock Street
Sharon, PA 16146
P 800.257.8182
F 724.346.7260
Fire Sprinkler Pipe
Schedule 10 and Schedule 40
Submittal Data Sheet
info@wheatland.com
wheatland.com
Follow us on Twitter:
@WheatlandTube
700 South Dock Street
Sharon, PA 16146
P 800.257.8182
F 724.346.7260
WFS-081619
SCHEDULE 10 WEIGHTS AND DIMENSIONS
NPS NOMINAL OD NOMINAL ID NOMINAL WALL WT. / FT.
WT. / FT.
H2O FILLED PCS. / LIFT
WT. / LIFT
21'
WT. / LIFT
24'
WT. / LIFT
25'UL
in.mm in.mm in.mm lbs.lbs.lbs.lbs.lbs.CRR*
1 1.315 33.4 1.097 27.9 0.109 2.77 1.405 1.814 70 2065 2360 2459 11.4
1 1/4 1.660 42.2 1.442 36.6 0.109 2.77 1.807 2.514 61 2315 2645 2756 7.3
1 1/2 1.900 48.3 1.682 42.7 0.109 2.77 2.087 3.049 61 2673 3055 3183 5.8
2 2.375 60.3 2.157 54.8 0.109 2.77 2.640 4.222 37 2051 2344 2442 4.7
2 1/2 2.875 73.0 2.635 66.9 0.120 3.05 3.354 5.895 30 2226 2544 2651 3.5
3 3.500 88.9 3.260 82.8 0.120 3.05 4.336 7.949 19 1730 1977 2060 2.6
4 4.500 114.3 4.260 108.2 0.120 3.05 5.619 11.789 19 2242 2562 2669 1.6
5 5.563 141.3 5.295 134.5 0.134 3.40 7.780 17.309 13 2124 2427 2529 1.5
6 6.625 168.3 6.357 161.5 0.134 3.40 9.298 23.038 10 1953 2232 2325 1.0
8 8.625 219.1 8.249 209.5 0.188 4.78 16.960 40.086 7 2493 2849 2968 2.1
SCHEDULE 40 WEIGHTS AND DIMENSIONS
NPS NOMINAL OD NOMINAL ID NOMINAL WALL WT. / FT.WT. / FT. H2O FILLED PCS. / LIFT WT. / LIFT 21'
WT. / LIFT 24'
WT. / LIFT 25'UL
in.mm in.mm in.mm lbs.lbs.lbs.lbs.lbs.CRR*
1 1.315 33.4 1.049 26.6 0.133 3.38 1.68 2.055 70 2470 2822 2940 1.000
1 1/4 1.660 42.2 1.380 35.1 0.140 3.56 2.27 2.922 51 2431 2778 2894 1.000
1 1/2 1.900 48.3 1.610 40.9 0.145 3.68 2.72 3.602 44 2513 2872 2992 1.000
2 2.375 60.3 2.067 52.5 0.154 3.91 3.66 5.109 24 1845 2108 2196 1.000
2 1/2 2.875 73.0 2.469 62.7 0.203 5.16 5.80 7.871 20 2436 2784 2900 1.000
3 3.500 88.9 3.068 77.9 0.216 5.49 7.58 10.783 13 2069 2365 2464 1.000
3 1/2 4.000 101.6 3.548 90.1 0.226 5.74 9.12 13.400 10 1915 2189 2280 1.000
4 4.500 114.3 4.026 102.3 0.237 6.02 10.80 16.311 10 2268 2592 2700 1.000
5 5.563 141.3 5.047 158.2 0.258 6.55 14.63 23.262 7 2151 2458 2560 1.000
6 6.625 168.3 6.065 154.1 0.280 7.11 18.99 31.498 5 1994 2279 2374 1.000
8**8.625 219.1 7.981 202.7 0.322 8.18 28.58 50.240 5 3001 3430 3573 1.000
* Calculated using Standard UL CRR formula, UL Fire Protection Directory, Category VIZY. The CRR is a ratio value used to measure the ability of a pipe to withstand corrosion.
Threaded Schedule 40 steel pipe is used as the benchmark (value of 1.0).
** 8 NPS Schedule 40 is FM Approved but not UL Listed.