Loading...
2020.0337.MP0095 58STA 310A PG8J ATTInstallation, Start--Up Operating and Service and Maintenance Instructions Series G 310AAV/JAV SINGLE--STAGE DELUXE, INDUCED--COMBUSTION 4--WAY MULTIPOISE GAS FURNACE SAFETY CONSIDERATIONS 2........................ INTRODUCTION 3.................................. CODES AND STANDARDS 4.......................... Safety 4......................................... General Installation 4............................... Combustion and Ventilation Air 4..................... Duct Systems 5................................... Acoustical Lining and Fibrous Glass Duct 5............. Gas Piping and Gas Pipe Pressure Testing 5............. Electrical Connections 5............................ Venting 5........................................ LOCATION 5....................................... AIR FOR COMBUSTION AND VENTILATION 7......... INSTALLATION 10.................................. Bottom Return Air Inlet 10.......................... Side Return Air Inlet 10............................. Leveling Legs (If Desired) 11........................ Bottom Return Air Inlet 12.......................... Suspended Furnace Support 12....................... Platform Furnace Support 12......................... Roll--Out Protection 12............................. Bottom Return Air Inlet 12.......................... Side Return Air Inlet 12............................. General Requirements 13............................ Ductwork Acoustical Treatment 13.................... Supply Air Connections 13.......................... Return Air Connections 19.......................... 115--V Wiring 21.................................. J--box Relocation 21............................... Electrical Connection to J--Box 21..................... Power Cord Installation in Furnace J--Box 22............ BX Cable Installation in Furnace J--Box 22.............. 24--V Wiring 24................................... Accessories 24.................................... General Venting Requirements 24..................... Masonry Chimney Requirements 25................... Appliance Application Requirements 27................ Sidewall Venting 27................................ START--UP, ADJUSTMENT, AND SAFETY CHECK 32..... General 32....................................... Start--Up Procedures 32............................. Adjustments 37................................... Check Safety Controls 37........................... Checklist 38...................................... SERVICE AND MAINTENANCE PROCEDURES 43....... Introduction 43................................... Care and Maintenance 44........................... Sequence of Operation 47........................... Wiring Diagrams 48............................... Troubleshooting 48................................ PARTS REPLACEMENT INFORMATION GUIDE 51....... Always Ask For Use of the AHRI Certified TM Mark indicates a manufacturer’s participation in the program. For verification of certification for individual products, go to www.ahridirectory.org. NOTE: Read the entire instruction manual before starting the installation. Portions of the text and tables are reprinted from NFPA 54/ANSI Z223.1--2012E, with permission of Nation Fire Protection Association, Quincy, MA 02269 and American Gas Association, Washington DC 20001. This reprinted material is not the complete and official position of the NFPA or ANSI on the referenced subject, which is represented only by the standard in its entirely. 2 SAFETY CONSIDERATIONS FIRE, EXPLOSION, ELECTRICAL SHOCK, AND CARBON MONOXIDE POISONING HAZARD Failure to follow this warning could result in personal injury, death, or property damage. Improper installation, adjustment, alteration, service, maintenance, or use can cause carbon monoxide poisoning, explosion, fire, electrical shock, or other conditions which may cause personal injury or property damage. Consult a qualified service agency, local gas supplier, or your distributor or branch for information or assistance. The qualified service agency must use only factory--authorized and listed kits or accessories when modifying this product. !WARNING FURNACE RELIABILITY HAZARD Failure to follow this caution may result in unit component damage. Application of this furnace should be indoors with special attention given to vent sizing and material, gas input rate, air temperature rise, unit leveling, and unit sizing. CAUTION! CUT HAZARD Failure to follow this caution may result in personal injury. Sheet metal parts may have sharp edges or burrs. Use care and wear appropriate protective clothing, safety glasses and gloves when handling parts, and servicing furnaces. CAUTION! Improper installation, adjustment, alteration, service, maintenance, or use can cause explosion, fire, electrical shock, or other conditions which may cause death, personal injury, or property damage. Consult a qualified installer, service agency, or your distributor or branch for information or assistance. The qualified installer or agency must use factory--authorized kits or accessories when modifying this product. Refer to the individual instructions packaged with the kits or accessories when installing. Follow all safety codes. Wear safety glasses, protective clothing, and work gloves. Have a fire extinguisher available. Read these instructions thoroughly and follow all warnings or cautions include in literature and attached to the unit. Consult local building codes, the current editions of the National Fuel Gas Code (NFGC) NFPA 54/ANSI Z223.1 and the National Electrical Code (NEC) NFPA 70. Recognize safety information. This is the safety--alert symbol . When you see this symbol on the unit and in instructions or manuals, be alert to the potential for personal injury. Understand the signal words DANGER,WARNING,and CAUTION. These words are used with the safety--alert symbol. DANGER identifies the most serious hazards which will result in severe personal injury or death.WARNING signifies hazards which could result in personal injury or death.CAUTION is used to identify unsafe practices which may result in minor personal injury or product and property damage.NOTE is used to highlight suggestions which will result in enhanced installation, reliability, or operation. 1. Use only with type of gas approved for this furnace. Refer to the furnace rating plate. 2. Install this furnace only in a location and position as spe- cified in the “Location” section of these instructions. 3. Provide adequate combustion and ventilation air to the furnace space as specified in “Air for Combustion and Ventilation” section. 4. Combustion products must be discharged outdoors. Con- nect this furnace to an approved vent system only, as spe- cified in the “Venting” section of these instructions. 5. Never test for gas leaks with an open flame. Use a com- mercially available soap solution made specifically for the detection of leaks to check all connections, as specified in the “Gas Piping” section. 6. Always install furnace to operate within the furnace’s in- tended temperature--rise range with a duct system which has an external static pressure within the allowable range, as specified in the “Start--Up, Adjustments, and Safety Check” section. See furnace rating plate. 7. When a furnace is installed so that supply ducts carry air circulated by the furnace to areas outside the space con- taining the furnace, the return air shall also be handled by duct(s) sealed to the furnace casing and terminating out- side the space containing the furnace. See “Air Ducts” sec- tion. 8. A gas--fired furnace for installation in a residential garage must be installed as specified in the warning box in the “Location” section. 9. The furnace may be used for construction heat provided that the furnace installation and operation complies with the first CAUTION in the LOCATION section of these in- structions. 10. These Multipoise Gas--Fired Furnaces are CSA (formerly A.G.A. and C.G.A.) design--certified for use with natural and propane gases (see furnace rating plate) and for install- ation in alcoves, attics, basements, closets, utility rooms, crawlspaces, and garages. The furnace is factory--shipped for use with natural gas. A CSA (A.G.A. and C.G.A.) lis- ted accessory gas conversion kit is required to convert fur- nace for use with propane gas. 11. See Fig. 1 for required clearances to combustible construc- tion. 12. Maintain a 1--in. (25 mm) clearance from combustible ma- terials to supply air ductwork for a distance of 36 in. (914 mm) horizontally from the furnace. See NFPA 90B or loc- al code for further requirements. 13. These furnaces SHALL NOT be installed directly on car- peting, tile, or any other combustible material other than wood flooring. In downflow installations, factory access- ory floor base MUST be used when installed on combust- ible materials and wood flooring. Special base is not re- quired when this furnace is installed on manufacturer’s Coil Assembly Part No. CNPV, CNRV, CAR or CAP or when Coil Box Part No. KCAKC is used. See Fig. 1 for clearance to combustible construction information.310AAV 3 AA B [736.9][736.9] 2929 Ø7/8Ø7/8 [22.2][22.2] ACCESSORYACCESSORY 5 15/165 15/16 [150.7][150.7] 28.3928.39 [721.2][721.2] Ø7/8Ø7/8 [22.2][22.2] ACCESSORYACCESSORY 14 7/814 7/8 [337.3][337.3] (BOTH SIDES)(BOTH SIDES) Ø7/8Ø7/8 [22.2][22.2] ACCESSORYACCESSORY Ø7/8Ø7/8 [22.2][22.2] ACCESSORYACCESSORY Ø1 3/4Ø1 3/4 [44.5][44.5] GAS ENTRYGAS ENTRY Ø1/2Ø1/2 [12.7][12.7] THERMOSTAT WIRE ENTRYTHERMOSTAT WIRE ENTRY 22 1/1622 1/16 [560][560] SIDE INLETSIDE INLET (BOTH SIDES)(BOTH SIDES) 11 7/1611 7/16 [290.7][290.7] 9 11/169 11/16 [245.4][245.4][197.8][197.8] 7 13/167 13/16 Ø7/8Ø7/8 [22.2][22.2] J.BOX PROVISIONJ.BOX PROVISION Ø7/8Ø7/8 [22.2][22.2] JUNCTION BOXJUNCTION BOX LOCATIONLOCATION Ø1 3/4Ø1 3/4 [44.5][44.5] GAS ENTRYGAS ENTRY 1 15/161 15/16 [49.2][49.2] 1 [25.4][25.4] 1 1/41 1/4 [31.8][31.8] 29 9/1629 9/16 [750.7][750.7] 1 15/161 15/16 [49.2][49.2] 5 5/85 5/8 [143.3][143.3]5 7/165 7/16 [138.5][138.5] 6 13/166 13/16 [172.3][172.3] Ø1/2Ø1/2 [12.7][12.7] THERMOSTAT WIRE ENTRYTHERMOSTAT WIRE ENTRY 1919 [481.7][481.7] OUTLETOUTLET D21.621.6 [549.5][549.5] BOTTOM INLETBOTTOM INLET C 33 1/433 1/4 [843.9][843.9] 9 9/169 9/16 [243.3][243.3] 3/43/4 [19.1][19.1] 5 7/85 7/8 [148.5][148.5] 3 7/163 7/16 [86.8][86.8] 9 7/89 7/8 [250.7][250.7] 27 3/427 3/4 [704.7][704.7] 2 5/162 5/16 [59][59]FRONT OF CASINGFRONT OF CASINGTOP OF CASINGTOP OF CASING 4 13/164 13/16 [122.2][122.2] 27 3/427 3/4 [704.7][704.7] 5 7/85 7/8 [148.5][148.5] 8 5/88 5/8 [219][219] 5 1/25 1/2 [140.3][140.3] 8 7/168 7/16 [213.5][213.5]FRONT OF CASINGFRONT OF CASINGTOP OF CASINGTOP OF CASING 6.16.1 [155.7][155.7] 2 1/162 1/16 [51.6][51.6] 5.15.1 [130.5][130.5] 1.71.7 [43.5][43.5] Ø7/8Ø7/8 [22.2][22.2] ACCESSORY (2)ACCESSORY (2) AIR FLOWAIR FLOW AIR FLOWAIR FLOW BOTTOM RETURNBOTTOM RETURN WIDTHWIDTH AIR FLOWAIR FLOW KNOCK OUTS FORKNOCK OUTS FOR VENTING(5 VENTING(5 PLACES)PLACES) A10290 NOTES: 1. Two additional 7/8---in. (22 mm) diameter holes are located in the top plate. 2. Minimum return---air openings at furnace, based on metal duct. If flex duct is used, see flex duct manufacturer’s recommendations for equivalent diameters. (a.)For 800 CFM---16---in. (406 mm) round or 14 1/2 x 12---in. (368 x 305 mm) rectangle. (b.)For 1200 CFM---20---in. (508 mm) round or 14 1/2 x 19 1/2---in. (368 x 495 mm) rectangle. (c.)For 1600 CFM---22---in. (559 mm) round or 14 1/2 x 22 1/16---in. (368 x 560mm) rectangle. (d.)For airflow requirements above 1800 CFM, see Air Delivery table in Product Data literature for specific use of single side inlets. The use of both side inlets, a combination of 1 side and the bottom, or the bottom only will ensure adequate return air openings for airflow requirements above 1800 CFM. FURNACE SIZE A CABINET WIDTH B OUTLET WIDTH C TOP & BOTTOM FLUE COLLAR LOCATION D BOTTOM INLET WIDTH VENT CONNECTION SIZE SHIP WT LB (KG) 045---08/024045 14---3/16 (360)12---9/16 (319)9---5/16 (237)12---11/16 (322)4 (102)104 (47) 045---12/036045 14---3/16 (360)12---9/16 (319)9---5/16 (237)12---11/16 (322)4 (102)107 (49) 070---08/024070 14---3/16 (360)12---9/16 (319)9---5/16 (237)12---11/16 (322)4 (102)111 (50) 070---12/036070 14---3/16 (360)12---9/16 (319)9---5/16 (237)12---11/16 (322)4 (102)115 (52) 070---16/048070 17---1/2 (445)15---7/8 (403)11---9/16 (294)16 (406)4 (102)126 (57) 090---14/042090 17---1/2 (445)15---7/8 (403)11---9/16 (294)16 (406)4 (102)127 (58) 090---16/048090 21 (533)19---3/8 (492)13---5/16 (338)19---1/2 (495)4 (102)140 (64) 090---20/060090 21 (533)19---3/8 (492)13---5/16 (338)19---1/2 (495)4 (102)146 (66) 110---12/036110 17---1/2 (445)15---7/8 (403)11---9/16 (294)16 (406)4 (102)135 (61) 110---16/048110 21 (533)19---3/8 (492)13---5/16 (338)19---1/2 (495)4 (102)146 (66) 110---22/066110 21 (533)19---3/8 (492)13---5/16 (338)19---1/2 (495)4 (102)152 (69) 135---16/048135 21 (533)19---3/8 (492)13---5/16 (338)19---1/2 (495)4 (102)*149 (68) 135---22/066135 24---1/2 (622)22---7/8 (581)15---1/16 (383)23 (584)4 (102)*163 (74) 155---20/060155 24---1/2 (622)22---7/8 (581)15---1/16 (383)23 (584)4 (102)*170 (77) *135 and 155 size furnaces require a 5 or 6---in. (127 or 152 mm) vent. Use a vent adapter between furnace and vent stack. See Installation Instructions for complete installation requirements. Fig. 1 ---Dimensional Drawing 310AAV 4 A10269 Fig. 2 ---Clearances to Combustibles 60 80 / 27 C / 16 C A06745 Fig. 3 ---Return Air Temperature INTRODUCTION This 4--way multipoise Category I fan--assisted furnace is CSA design--certified. A Category I fan--assisted furnace is an appliance equipped with an integral mechanical means to either draw or force products of combustion through the combustion chamber and/or heat exchanger. The furnace is factory--shipped for use with natural gas. This furnace is not approved for installation in mobile homes, recreational vehicles, or outdoors. This furnace is designed for minimum continuous return--air temperature of 60_F(16_C) db or intermittent operation down to 55_F(13_C) db such as when used with a night setback thermostat. Return--air temperature must not exceed 80_F(27_C) db. Failure to follow these return--air temperature limits may affect reliability of heat exchangers, motors, and controls. (See Fig. 3.) For accessory installation details, refer to the applicable instruction literature. NOTE: Remove all shipping brackets and materials before operating the furnace. CODES AND STANDARDS Follow all national and local codes and standards in addition to these instructions.The installation must comply with regulations of the serving gas supplier, local building, heating, plumbing, and other codes. In absence of local codes, the installation must comply with the national codes listed below and all authorities having jurisdiction. In the United States , follow all codes and standards for the following: Step 1 —Safety310AAV 5 S National Fuel Gas Code (NFGC) NFPA 54--2012/AN- SI Z223.1--2012 and the Installation Standards, Warm Air Heating and Air Conditioning Systems ANSI/ NFPA 90B Step 2 —General Installation S Current edition of the NFGC and the NFPA 90B. For copies, contact the National Fire Protection Association Inc., Batterymarch Park, Quincy, MA 02269; (www.NFPA.org) or for only the NFGC, contact the American Gas Association, 400 N. Capitol Street, N.W., Washington, DC 20001 (www.AGA.org). Step 3 —Combustion and Ventilation Air S Section 9.3 of the NFGC, NFPA 54 / ANSI Z223.1--2012 Air for Combustion and Ventilation Step 4 —Duct Systems S Air Conditioning Contractors Association (ACCA) Manual D, Sheet Metal and Air Conditioning Contract- ors National Association (SMACNA), or American Society of Heating, Refrigeration, and Air Condition- ing Engineers (ASHRAE) 2001 Fundamentals Hand- book Chapter 34 or 2000 HVAC Systems and Equip- ment Handbook Chapters 9 and 16. Step 5 —Acoustical Lining and Fibrous Glass Duct S Current edition of SMACNA and NFPA 90B as tested by UL Standard 181 for Class I Rigid Air Ducts Step 6 —Gas Piping and Gas Pipe Pressure Testing S NFGC; NFPA 54 / ANSI Z223.1--2012 chapters 5, 6, 7 and 8 and National Plumbing Codes Step 7 —Electrical Connections S National Electrical Code (NEC) ANSI/NFPA 70--2011 Step 8 —Venting S NFGC NFPA 54 / ANSI Z223.1--2012; chapters 12 and 13 ELECTROSTATIC DISCHARGE (ESD) PRECAUTIONS PROCEDURE FURNACE RELIABILITY HAZARD Failure to follow this caution may result in furnace component damage. Electrostatic discharge can affect electronic components. Follow the Electrostatic Discharge Precautions Procedure listed below during furnace installation and servicing to protect the furnace electronic control. Precautions will prevent electrostatic discharges from personnel and hand tools which are held during the procedure. These precautions will help to avoid exposing the control to electrostatic discharge by putting the furnace, the control, and the person at the same electrostatic potential. CAUTION! 1. Disconnect all power to the furnace. Multiple disconnects may be required. DO NOT TOUCH THE CONTROL OR ANY WIRE CONNECTED TO THE CONTROL PRIOR TO DISCHARGING YOUR BODY’S ELECTROSTATIC CHARGE TO GROUND. 2. Firmly touch the clean, unpainted, metal surface of the fur- nace chassis which is close to the control. Tools held in a person’s hand during grounding will be satisfactorily dis- charged. 3. After touching the chassis, you may proceed to service the control or connecting wires as long as you do nothing to recharge your body with static electricity (for example; DO NOT move or shuffle your feet, do not touch un- grounded objects, etc.). 4. If you touch ungrounded objects (and recharge your body with static electricity), firmly touch a clean, unpainted metal surface of the furnace again before touching control or wires. 5. Use this procedure for installed and uninstalled (ungroun- ded) furnaces. 6. Before removing a new control from its container, dis- charge your body’s electrostatic charge to ground to pro- tect the control from damage. If the control is to be in- stalled in a furnace, follow items 1 through 4 before bringing the control or yourself in contact with the fur- nace. Put all used and new controls into containers before touching ungrounded objects. 7. An ESD service kit (available from commercial sources) mayalsobeusedtopreventESDdamage. LOCATION CARBON MONOXIDE POISONING AND UNIT DAMAGE HAZARD Failure to follow this warning could result in personal injury or death, and unit component damage. Corrosive or contaminated air may cause failure of parts containing flue gas, which could leak into the living space. Air for combustion must not be contaminated by halogen compounds, which include fluoride, chloride, bromide, and iodide. These elements can corrode heat exchangers and shorten furnace life. Air contaminants are found in aerosol sprays, detergents, bleaches, cleaning solvents, salts, air fresheners, and other household products. Do not install furnace in a corrosive or contaminated atmosphere. Make sure all combustion and circulating air requirements are met, in addition to all local codes and ordinances. !WARNING GENERAL This multipoise furnace is shipped in packaged configuration. Some assembly and modifications are required when used in any of the four applications shown in Fig. 4. This furnace must: S be installed so the electrical components are protected from water. S not be installed directly on any combustible material other than wood flooring for upflow applications. Downflow installations require use of a factory--ap- proved floor base or coil assembly when installed on combustible materials or wood flooring. (Refer to SAFETY CONSIDERATIONS).310AAV 6 THE BLOWER IS LOCATED TO THE RIGHT OF THE BURNER SECTION, AND AIR CONDITIONED AIR IS DISCHARGED TO THE LEFT. THE BLOWER IS LOCATED BELOW THE BURNER SECTION, AND CONDITIONED AIR IS DISCHARGED UPWARD. THE BLOWER IS LOCATED ABOVE THE BURNER SECTION, AND CONDITIONED AIR IS DISCHARGED DOWNWARD THE BLOWER IS LOCATED TO THE LEFT OF THE BURNER SECTION, AND CONDITIONED AIR IS DISCHARGED TO THE RIGHT. A02097 Fig. 4 ---Multipoise Orientations S be located as close to the chimney or vent and attached to an air distribution system. Refer to Air Ducts section. S be provided ample space for servicing and cleaning. Always comply with minimum fire protection clear- ances shown on the furnace clearance to combustible label. S The following types of furnace installations may re- quire OUTDOOR AIR for combustion due to chemical exposures: S Commercial buildings S Buildings with indoor pools S Laundry rooms S Hobby or craft rooms, and S Chemical storage areas If air is exposed to the following substances, it should not be used for combustion air, and outdoor air may be required for combustion: S Permanent wave solutions S Chlorinated waxes and cleaners S Chlorine based swimming pool chemicals S Water softening chemicals S De--icing salts or chemicals S Carbon tetrachloride S Halogen type refrigerants S Cleaning solvents (such as perchloroethylene) S Printing inks, paint removers, varnishes, etc. S Hydrochloric acid S Cements and glues S Antistatic fabric softeners for clothes dryers S Masonry acid washing materials All fuel--burning equipment must be supplied with air for fuel combustion. Sufficient air must be provided to avoid negative pressure in the equipment room or space. A positive seal must be made between the furnace cabinet and the return--air duct to prevent pulling air from the burner area and from draft safeguard opening. FIRE AND EXPLOSION HAZARD Failure to follow this warning could result in personal injury, death, and/or property damage. When the furnace is installed in a residential garage, the burners and ignition sources must be located at least 18 inches above the floor. The furnace must be located or protected to avoid damage by vehicles. When the furnace is installed in a public garage, airplane hangar, or other building having a hazardous atmosphere, the furnace must be installed in accordance with the NFGC. (See Fig. 5.) !WARNING310AAV 7 PERSONAL INJURY AND/OR PROPERTY DAMAGE HAZARD Failure to follow this caution may result in furnace component damage. This gas furnace may be used for heating buildings under construction provided that: --The furnace is permanently installed with all electrical wiring, piping, venting and ducting installed according to these installation instructions. A return air duct is provided, sealed to the furnace casing, and terminated outside the space containing the furnace. This prevents a negative pressure condition as created by the circulating air blower, causing a flame rollout and/or drawing combustion products into the structure. --The furnace is controlled by a thermostat. It may not be hot wired to provide heat continuously to the structure without thermostatic control. --Clean outside air is provided for combustion. This is to minimize the corrosive effects of adhesives, sealers and other construction materials. It also prevents the entrainment of drywall dust into combustion air, which can cause fouling and plugging of furnace components. --The temperature of the return air to the furnace is maintained between 55_F(13_C) and 80_F(27_C), with no evening setback or shutdown. The use of the furnace while the structure is under construction is deemed to be intermittent operation per our installation instructions. --The air temperature rise is within the rated rise range on the furnace rating plate, and the gas input rate has been set to the nameplate value. --The filters used to clean the circulating air during the construction process must be either changed or thoroughly cleaned prior to occupancy. --The furnace, ductwork and filters are cleaned as necessary to remove drywall dust and construction debris from all HVAC system components after construction is completed. --Verify proper furnace operating conditions including ignition, gas input rate, air temperature rise, and venting according to these installation instructions. CAUTION! 18-IN. (457.2 mm) MINIMUM TO BURNERS A93044 Fig. 5 ---Installation in a Garage FIRE HAZARD Failure to follow this warning could result in personal injury, death and/or property damage. Do not install the furnace on its back or hang furnace with control compartment facing downward. Safety control operation will be adversely affected. Never connect return--air ducts to the back of the furnace. (See Fig. 6.) !WARNING A02054 Fig. 6 ---Prohibit Installation on Back LOCATION RELATIVE TO COOLING EQUIPMENT The cooling coil must be installed parallel with, or on the downstream side of the unit to avoid condensation in the heat exchangers. When installed parallel with the furnace, dampers or other flow control must prevent chilled air from entering the furnace. If the dampers are manually operated, they must be equipped with means to prevent operation of either unit unless the damper is in the full--heat or full--cool position. AIR FOR COMBUSTION AND VENTILATION Provisions for adequate combustion, ventilation, and dilution air must be provided in accordance with: S Section 9.3 of the NFPA 54 / ANSI Z223.1--2012, Air for Combustion and Ventilation, and applicable provi- sions of the local building codes. FURNACE CORROSION HAZARD Failure to follow this caution may result in furnace damage. Air for combustion must not be contaminated by halogen compounds, which include fluoride, chloride, bromide, and iodide. These elements can corrode heat exchangers and shorten furnace life. Air contaminants are found in aerosol sprays, detergents, bleaches, cleaning solvents, salts, air fresheners, and other household products. CAUTION!310AAV 8 CARBON MONOXIDE POISONING HAZARD Failure to follow this warning could result in personal injury or death. The operation of exhaust fans, kitchen ventilation fans, clothes dryers, attic exhaust fans or fireplaces could create a NEGATIVE PRESSURE CONDITION at the furnace. Make--up air MUST be provided for the ventilation devices, in addition to that required by the furnace. Refer to Carbon Monoxide Poisoning Hazard warning in venting section of these instructions to determine if an adequate amount of make--up air is available. !WARNING The requirements for combustion and ventilation air depend upon whether or not the furnace is located in a space having a volume of at least 50 cu/ft. per 1,000 Btuh input rating for all gas appliances installed in the space. S Spaces having less than 50 cu/ft. per 1,000 Btuh re- quire the OUTDOOR COMBUSTION AIR METHOD. S Spaces having at least 50 cu/ft. per 1,000 Btuh may use the INDOOR COMBUSTION AIR, STANDARD or KNOWN AIR INFILTRATION METHOD. Outdoor Combustion Air Method 1. Provide the space with sufficient air for proper combus- tion, ventilation, and dilution of flue gases using perman- ent horizontal or vertical duct(s) or opening(s) directly communicating with the outdoors or spaces that freely communicate with the outdoors. 2. Fig. 7 illustrates how to provide TWO OUTDOOR OPENINGS, one inlet and one outlet combustion and ventilation air opening, to the outdoors. e. One opening MUST commence within 12 in. (300 mm) of the ceiling and the second opening MUST commence within 12 in. (300 mm) of the floor. f. Size openings and ducts per Fig. 7 and Table 1. g. TWO HORIZONTAL DUCTS require 1 sq./in. of free area per 2,000 Btuh (1,100 mm 2/kW) of combined input for all gas appliances in the space per Fig. 7 and Table 1. h. TWO OPENINGS OR VERTICAL DUCTS require 1 sq./in. of free area per 4,000 Btuh (550 mm 2/kW) for combined input of all gas appliances in the space per Fig. 7 and Table 1. 3. ONE OUTDOOR OPENING requires: a. 1 square inch of free area per 3,000 Btuh (734 mm2/kW) for combined input of all gas appliances in the space per Table 1 and b. Not less than the sum of the areas of all vent connect- ors in the space. The opening shall commence within 12 in. (300 mm) of the ceiling. Appliances in the space shall have clearances of at least 1 in. (25 mm) from the sides and back and 6 in. (150 mm) from the front. The opening shall directly communicate with the outdoors or shall communicate through a vertical or horizontal duct to the outdoors or spaces (crawl or attic) that freely communicate with the outdoors. Indoor Combustion Air NFPA & AGA Standard and Known--Air--Infiltration Rate Methods Indoor air is permitted for combustion, ventilation, and dilution, if the Standard or Known--Air--Infiltration Method is used. CARBON MONOXIDE POISONING HAZARD Failure to follow this warning could result in death and/or personal injury. Many homes require air to be supplied from outdoors for furnace combustion, ventilation, and dilution of flue gases. The furnace combustion air supply must be provided in accordance with this instruction manual. !WARNING Table 1—Minimum Free Area Required for Each Combustion Air Opening of Duct to Outdoors FURNACE INPUT (BTUH) TWO HORIZONTAL DUCTS SINGLE DUCT OR OPENING TWO OPENINGS OR VERTICAL DUCTS (1 SQ. IN./2,000 BTUH) (1,100 SQ. MM/KW) (1 SQ. IN./3,000 BTUH) (734 SQ. MM/KW) (1 SQ. IN./4,000 BTUH) (550 SQ. MM/KW) Free Area of Open- ing and Duct Sq. In. (Sq. mm) Round Duct Dia. In. (mm) Free Area of Open- ing and Duct Sq. In. (Sq. mm) Round Duct Dia. In. (mm) Free Area of Open- ing and Duct Sq. In. (Sq. mm) Round Duct Dia. In. (mm) 44,000 22 (14194)6 (152)14.7 (9484)5 (127)11 (7096)4 (102) 66,000 33 (21290)7 (178)22.0 (14193)6 (152)16.5 (10645)5 (127) 88,000 44 (28387)8 (203)29.3 (18903)7 (178)22 (14193)6 (152) 110,000 55 (35484)9 (229)36.7 (23677)7 (178)27.5 (17742)6 (152) 132,000 66 (42580)10 (254)44 .0 (28387)8 (203)33 (21290)7 (178) 154,000 77 (49677)10 (254)51.3 (33096)9 (229)38.5 (24839)8 (203) EXAMPLES: Determining Free Area FURNACE WATER HEATER TOTAL INPUT 110,000 + 30,000 = (140,000 divided by 4,000) = 35.0 Sq. In. for each two Vertical Ducts or Openings 66,000 + 40,000 = (106,000 divided by 3,000) = 35.3 Sq. In. for a Single Duct or Opening 88,000 +30,000 =(118,000 divided by 2,000)=59.0 Sq. In. for each of two Horizontal Ducts310AAV 9 Table 2—Minimum Space Volumes for 100% Combustion, Ventilation, and Dilution from Indoors OTHER THAN FAN-ASSISTED TOTAL(1,000’S BTUH GAS INPUT RATE) FAN-ASSISTED TOTAL(1,000’S BTUH GAS INPUT RATE) ACH 30 40 50 44 66 88 110 132 154 SpaceVolumeFt3 (M3) 0.60 1,050(29.7)1,400(39.6)1,750(49.5)1,100(31.1)1,650(46.7)2,200(62.2)2,750(77.8)3,300(93.4)3,850(109.0) 0.50 1,260(35.6)1,680(47.5)2,100(59.4)1,320(37.3)1,980(56.0)2,640(74.7)3,300(93.4)3,960(112.1)4,620(130.8) 0.40 1,575(44.5)2,100(59.4)2,625(74.3)1,650(46.7)2,475(70.0)3,300(93.4)4,125(116.8)4,950(140.1)5,775(163.5) 0.30 2,100(59.4)2,800(79.2)3,500(99.1)2,200(62.2)3,300(93.4)4,400(124.5)5,500(155.7)6,600(186.8)7,700(218.0) 0.20 3,150(89.1)4,200(118.9)5,250(148.6)3,300(93.4)4,950(140.1)6,600(186.8)8,250(233.6)9,900(280.3)11,550(327.0) 0.10 6,300(178.3)8,400(237.8)10,500(297.3)6,600(186.8)9,900(280.3)13,200(373.7)16,500(467.2)19,800(560.6)23,100(654.1) 0.00 NP NP NP NP NP NP NP NP NP NP = Not Permitted 1 SQ IN . PER 4000 BTUH* DUCTS TO O UTDOORS 1 SQ IN. PER 4000 BTUH* C IRCULA TING AIR DUCTS VENT THR OUGH R OOF D B A C E 1 SQ IN. PER 4000 BTUH* DUCT TO OUTDOORS CIRCULA TING AIR DUCT S 1 SQ IN. PER 2000 BTUH* 1 SQ IN. PER 2000 BTUH* DUCT S TO OUTDOORS 12 ″ MAX 12 ″ MAX 12 ″ MAX 12 ″ MAX 12 ″ MAX OUTDOORS 1 SQ IN . PER 4000 BTUH* F G CLEARANCE IN FRONT OF COMB USTION AIR OPENINGS SHALL BE AT LEAST 3 IN . (305mm) (305mm) (305mm) (305mm) (305mm) (76mm) *Minimum dimensions of 3---in. (76 mm). NOTE: Use any of the following combinations of openings:A&BC&DD&EF&G A03174 Fig. 7 ---Air for Combustion, Ventilation, and Dilution for Outdoors CIRCULATING AIR DUCTS 6" MIN (FRONT)Ü CIRCULATING AIR DUCTS VENT THROUGH ROOF 1 SQ IN. PER 1000 BTUH* IN DOOR OR WALL 12" MAX 1 SQ IN. PER 1000 BTUH* IN DOOR OR WALL 12" MA X UNCONFINED SPACE INTERIOR HEATED SPACE CLEARANCE IN FRONT OF COMBUSTION AIR OPENINGS SHALL BE AT LEAST 3 IN. (305mm) (152mm) (305mm) * Minimum opening size is 100 sq in. (64516 sq. mm)with minimum dimensions of3in.(76mm) †Minimumof3in.(76mm)whentype-B1ventisused. A03175 Fig. 8 ---Air for Combustion, Ventilation, and Dilution from Indoors 310AAV 10 The Standard Method: 1. The space has no less volume than 50 cu/ft. per 1,000 Btuh of the maximum input ratings for all gas appliances installed in the space and 2. The air infiltration rate is not known to be less than 0.40 air changes per hour (ACH). The Known Air Infiltration Rate Method shall be used, if the infiltration rate is known to be: 1. Less than 0.40 ACH and 2. Equal to or greater than 0.10 ACH Infiltration rates greater than 0.60 ACH shall not be used. The minimum required volume of the space varies with the number of ACH and shall be determined per Table 2 or Equations 1 and 2. Determine the minimum required volume for each appliance in the space and add the volumes together to get the total minimum required volume for the space. Table 2 -- Minimum Space Volumes were determined by using the following equations from the National Fuel Gas Code ANSI Z223.1--2012/NFPA 54--2012, 9.3.2.2: 1. For other than fan--assisted appliances, such as a draft hood--equipped water heater: Volume Other =21ft3 ACH I other 1000 Btu/hr A04002 2. For fan--assisted appliances such as this furnace: Volume Fan =15ft3 ACH I fan 1000 Btu/hr A04003 If: Iother = combined input of all other than fan--assisted appliances in Btuh/hr Ifan = combined input of all fan--assisted appliances in Btuh/hr ACH = air changes per hour (ACH shall not exceed 0.60.) The following requirements apply to the Standard Method and to the Known Air Infiltration Rate Method. 1. Adjoining rooms can be considered part of a space if: a. There are no closeable doors between rooms. b. Combining spaces on same floor level. Each opening shall have free area of at least 1 in. 2/1,000 Btuh (2,000 mm2/kW) of the total input rating of all gas appliances in the space, but not less than 100 in. 2 (0.06 m2). One opening shall commence within 12 in. (300 mm) of the ceiling and the second opening shall commence within 12 in. (300 mm) of the floor. The minimum dimension of air openings shall be at least 3 in. (80 mm). (See Fig. 8.) c. Combining space on different floor levels. The volumes of spaces on different floor levels shall be considered as communicating spaces if connected by one or more permanent openings in doors or floors having free area of at least 2 in. 2/1,000 Btuh (4,400 mm2/kW) of total input rating of all gas appliances. 2. An attic or crawlspace may be considered a space that freely communicates with the outdoors provided there are adequate permanent ventilation openings directly to out- doors having free area of at least 1--in. 2/4,000 Btuh of total input rating for all gas appliances in the space. 3. In spaces that use the Indoor Combustion Air Method, in- filtration should be adequate to provide air for combus- tion, permanent ventilation and dilution of flue gases. However, in buildings with unusually tight construction, additional air MUST be provided using the methods de- scribedintheOutdoor Combustion Air Method section. Unusually tight construction is defined as Construction with: a. Walls and ceilings exposed to the outdoors have a con- tinuous, sealed vapor barrier. Openings are gasketed or sealed and b. Doors and openable windows are weatherstripped and c. Other openings are caulked or sealed. These include joints around window and door frames, between sole plates and floors, between wall--ceiling joints, between wall panels, at penetrations for plumbing, electrical and gas lines, etc. Combination of Indoor and Outdoor Air 1. Indoor openings shall comply with the Indoor Combus- tion Air Method below and, 2. Outdoor openings shall be located as required in the Out- door Combustion Air Method mentioned previously and, 3. Outdoor openings shall be sized as follows: a. Calculate the Ratio of all Indoor Space volume divided by required volume for Indoor Combustion Air Method below. b. Outdoor opening size reduction Factor is 1 minus the Ratio in a. above. c. Minimum size of Outdoor openings shall be the size required in Outdoor Combustion Air Method above multiplied by reduction Factor in b. above. The min- imum dimension of air openings shall be not less than 3in.(80mm). INSTALLATION UPFLOW INSTALLATION Bottom Return Air Inlet These furnaces are shipped with bottom closure panel installed in bottom return--air opening. Remove and discard this panel when bottom return air is used. To remove bottom closure panel, perform the following: 1. Tilt or raise furnace and remove 2 screws holding bottom filler panel. (See Fig. 9.) Bottom Closure Panel Bottom Filler Panel A10273 Fig. 9 ---Removing Bottom Closure Panel 2. Rotate bottom filler panel downward to release holding tabs. 3. Remove bottom closure panel. 4. Reinstall bottom filler panel and screws. Side Return Air Inlet These furnaces are shipped with bottom closure panel installed in bottom return--air opening. This panel MUST be in place when only side return air is used.310AAV 11 NOTE: Side return--air openings can be used in UPFLOW and most HORIZONTAL configurations. Do not use side return--air openings in DOWNFLOW configuration. In upflow position with side return inlet(s), leveling legs may be used. (See Fig. 10.) Install field--supplied, 5/16 x 1--1/2 in. (8 x 38 mm) (max) corrosion--resistant machine bolts, washers and nuts. NOTE: Bottom closure must be used when leveling legs are used. It may be necessary to remove and reinstall bottom closure panel to install leveling legs. To remove bottom closure panel, see Item 1. in Bottom Return Air Inlet section. 1 3 / 4  1 3 / 4  1 3/ 4  1 3/ 4  5/ 16  5 / 16  5/ 16  5/ 16  (44mm) (8mm) (44mm) (8mm) (8mm) (8mm) (44mm) (44mm) A89014 Fig. 10 ---Leveling Legs Leveling Legs (If Desired) To install leveling legs: 1. Position furnace on its back. Locate and drill a hole in each bottom corner of furnace. (See Fig. 10.) 2. For each leg, install nut on bolt and then install bolt and nut in hole. (Install flat washer if desired.) 3. Install another nut on other side of furnace base. (Install flat washer if desired.) 4. Adjust outside nut to provide desired height, and tighten inside nut to secure arrangement. 5. Reinstall bottom closure panel if removed. DOWNFLOW INSTALLATION NOTE: For downflow applications, this furnace is approved for use on combustible flooring when any one of the following 3 accessories are used: S Special Base, KGASB S Cased Coil Assembly Part No. CNPV, CNRV, CAR, or CAP S Coil Box Part No. KCAKC 1. Determine application being installed from Table 3. 2. Construct hole in floor per Table 3 and Fig. 11. 3. Construct plenum to dimensions specified in Table 4 and Fig. 11. 4. If downflow subbase, KGASB is used, install as shown in Fig. 12. If Coil Assembly Part No. CNPV, CNRV, CAR, or CAP or Coil Box Part No. KCAKC is used, install as shown in Fig. 13. PLENUM OPENING C A B D FLOOR OPENING A96283 Fig. 11 ---Floor and Plenum Opening Dimensions NOTE: It is recommended that the perforated supply--air duct flanges be completely folded over or removed from furnace when installing the furnace on a factory--supplied cased coil or coil box. To remove the supply--air duct flange, use wide duct pliers or hand seamers to bend flange back and forth until it breaks off. Be careful of sharp edges. (See Fig. 14.) DOWNFLOW SUBBASE SHEET METAL PLENUM FLOOR OPENING FURNACE (OR COIL CASING WHEN USED) COMBUSTIBLE FLOORING A96285 Fig. 12 ---Furnace, Plenum, and Subbase Installed on a Combustible Floor 310AAV 12 APPROVEDCOIL ASSEMBLY OR COIL BOX FURNACE SHEET METALPLENUM FLOOROPENING COMBUSTIBLEFLOORING A08556 Fig. 13 ---Furnace, Plenum, and Coil Assembly or Coil Box Installed on a Combustible Floor Bottom Return Air Inlet These furnaces are shipped with bottom closure panel installed in bottom return--air opening. Remove and discard this panel when bottom return air is used. To remove bottom closure panel, perform the following: 1. Tilt or raise furnace and remove 2 screws holding bottom filler panel. (See Fig. 9.) 2. Rotate bottom filler panel downward to release holding tabs. 3. Remove bottom closure panel. 4. Reinstall bottom filler panel and screws. HORIZONTAL INSTALLATION FIRE, EXPLOSION, AND CARBON MONOXIDE POISONING HAZARD Failure to follow this warning could result in personal injury, death, or property damage. Do not install the furnace on its back or hang furnace with control compartment facing downward. Safety control operation will be adversely affected. Never connect return--air ducts to the back of the furnace. !WARNING The furnace can be installed horizontally in an attic or crawl space on either the left--hand (LH) or right--hand (RH) side. The furnace can be hung from floor joists, rafters or trusses or installed on a non--combustible platform, blocks, bricks or pad. Suspended Furnace Support The furnace may be supported under each end with threaded rod, angle iron or metal plumber’s strap as shown. (See Fig. 15 and 16.) Secure angle iron to bottom of furnace as shown. Heavy--gauge sheet metal straps (plumber’s straps) may be used to suspend the furnace from each bottom corner. To prevent screws from pulling out, use 2 #8 x 3/4--in. (19 mm) screws into the side and 2 #8 x 3/4--in. (19 mm) screws in the bottom of the furnace casing for each strap. (See Fig. 15 and 16.) If the screws are attached to ONLY the furnace sides and not the bottom, the straps must be vertical against the furnace sides and not pull away from the furnace sides, so that the strap attachment screws are not in tension (are loaded in shear) for reliable support. Platform Furnace Support Construct working platform at location where all required furnace clearances are met. (See Fig. 2 and 17.) For furnaces with 1--in. (25 mm) clearance requirement on side, set furnace on non-- combustible blocks, bricks or angle iron. For crawl space installations, if the furnace is not suspended from the floor joists, the ground underneath furnace must be level and the furnace set on blocks or bricks. Roll--Out Protection Provide a minimum 17--3/4 in. x 22 in. (451 x 559 mm) piece of sheet metal for flame roll--out protection in front of burner area for furnaces closer than 12 inches (305 mm) above the combustible deck or suspended furnaces closer than 12 inches (305 mm) to joists. The sheet metal MUST extend underneath the furnace casing by 1 in. (25 mm) with the door removed. The bottom closure panel on furnaces of widths 17--1/2 in. (445 mm) and larger may be used for flame roll--out protection when bottom of furnace is used for return air connection. See Fig. 17 for proper orientation of roll--out shield. Bottom Return Air Inlet These furnaces are shipped with bottom closure panel installed in bottom return--air opening. Remove and discard this panel when bottom return air is used. To remove bottom closure panel, perform the following: 1. Tilt or raise furnace and remove 2 screws holding bottom filler panel. (See Fig. 9.) 2. Rotate bottom filler panel downward to release holding tabs. 3. Remove bottom closure panel. 4. Reinstall bottom filler panel and screws. Side Return Air Inlet These furnaces are shipped with bottom closure panel installed in bottom return--air opening. This panel MUST be in place when side return air inlet(s) is used without a bottom return air inlet. Not all horizontal furnaces are approved for side return air connections. (See Fig. 20.) FILTER ARRANGEMENT CARBON MONOXIDE AND POISONING HAZARD Failure to follow this warning could result in personal injury, death and/or property damage. Never operate a furnace without a filter or with filter access door removed. !WARNING There are no provisions for an internal filter rack in these furnaces. Refer to the instructions supplied with accessory Media Cabinet for assembly and installation options. This furnace requires a field--supplied external filter rack or a suitable field--supplied substitute, such as the media cabinet. See the Product Data Sheet for accessory list. Refer to the instructions supplied with external filter rack for assembly and installation options.310AAV 13 Table 3—Opening Dimensions -- In. (mm) FURNACE CASING WIDTH APPLICATION PLENUM OPENING FLOOR OPENING A B C D 14–3/16 (360) Upflow Applications on Combustible or Noncombustible Floor- ing (KGASB subbase not required) 12---11/16 (322) 21---5/8 (549) 13---5/16 (338) 22---1/4 (565) Downflow Applications on Noncombustible Flooring (KGASB subbase not required) 12---9/16 (319) 19 (483) 13---3/16 (335) 19---5/8 (498) Downflow applications on combustible flooring (KGASB sub- base required) 11---13/16 (284) 19 (483) 13---7/16 (341) 20---5/8 (600) Downflow Applications on Combustible Flooring with CNPV, CNRV, CAR, or CAP Coil Assembly or KCAKC coil box (KGASB subbase not required) 12---5/16 (319) 19 (483) 13---5/16 (338) 20 (508) 17–1/2 (445) Upflow Applications on Combustible or Noncombustible Floor- ing (KGASB subbase not required) 16 (406) 21---5/8 (549) 16---5/8 (422) 22---1/4 (565) Downflow Applications on Noncombustible Flooring (KGASB subbase not required) 15---7/8 (403) 19 (483) 16---1/2 (419) 19---5/8 (498) Downflow applications on combustible flooring (KGASB sub- base required) 15---1/8 (384) 19 (483) 16---3/4 (425) 20---5/8 (600) Downflow Applications on Combustible Flooring with CNPV, CNRV, CAR, or CAP Coil Assembly or KCAKC coil box (KGASB subbase not required) 15---1/2 (394) 19 (483) 16---1/2 (419) 20 (508) 21 (533) Upflow Applications on Combustible or Noncombustible Floor- ing (KGASB subbase not required) 19---1/2 (495) 21---5/8 (549) 20---1/8 (511) 22---1/4 (565) Downflow Applications on Noncombustible Flooring (KGASB subbase not required) 19---3/8 (492) 19 (483) 20 (508) 19---5/8 (498) Downflow applications on combustible flooring (KGASB sub- base required) 18---5/8 (473) 19 (483) 20---1/4 (514) 20---5/8 (600) Downflow Applications on Combustible Flooring with CNPV, CNRV, CAR, or CAP Coil Assembly or KCAKC coil box (KGASB subbase not required) 19 (483) 19 (483) 20 (508) 20 (508) 24---1/2 (622) Upflow Applications on Combustible or Noncombustible Floor- ing (KGASB subbase not required) 23 (584) 21---1/8 (537) 23---5/8 (600) 22---1/4 (565) Downflow Applications on Noncombustible Flooring (KGASB subbase not required) 22---7/8 (581) 19 (483) 23---1/2 (597) 19---5/8 (498) Downflow applications on Combustible flooring (KGASB sub- base required) 22---1/8 (562) 19 (483) 23---3/4 (603) 20---5/8 (600) Downflow Applications on Combustible Flooring with CNPV, CNRV, CAR, or CAP Coil Assembly or KCAKC coil box (KGASB subbase not required) 22---1/2 (572) 19 (483) 23---1/2 (597) 20 (508) AIR DUCTS General Requirements The duct system should be designed and sized according to accepted national standards such as those published by: Air Conditioning Contractors Association (ACCA), Sheet Metal and Air Conditioning Contractors National Association (SMACNA) or American Society of Heating, Refrigerating and Air Conditioning Engineers (ASHRAE) or consult The Air Systems Design Guidelines reference tables available from your local distributor. The duct system should be sized to handle the required system design CFM at the design external static pressure. The furnace airflow rates are provided in Table 4 -- AIR DELIVERY--CFM (With Filter). When a furnace is installed so that the supply ducts carry air circulated by the furnace to areas outside the space containing the furnace, the return air shall also be handled by duct(s) sealed to the furnace casing and terminating outside the space containing the furnace. Secure ductwork with proper fasteners for type of ductwork used. Seal supply-- and return--duct connections to furnace with code approved tape or duct sealer. NOTE: Flexible connections should be used between ductwork and furnace to prevent transmission of vibration. Ductwork passing through unconditioned space should be insulated and sealed to enhance system performance. When air conditioning is used, a vapor barrier is recommended. Maintain a 1--in. (25 mm) clearance from combustible materials to supply air ductwork for a distance of 36 in. (914 mm) horizontally from the furnace. See NFPA 90B or local code for further requirements. Ductwork Acoustical Treatment NOTE: Metal duct systems that do not have a 90 degree elbow and 10 ft. (3 M) of main duct to the first branch take--off may require internal acoustical lining. As an alternative, fibrous ductwork may be used if constructed and installed in accordance with the latest edition of SMACNA construction standard on fibrous glass ducts. Both acoustical lining and fibrous ductwork shall comply with NFPA 90B as tested by UL Standard 181 for Class 1 Rigid air ducts. Supply Air Connections For a furnace not equipped with a cooling coil, the outlet duct shall be provided with a removable access panel. This opening shall be accessible when the furnace is installed and shall be of such a size that the heat exchanger can be viewed for possible openings using light assistance or a probe can be inserted for sampling the air stream. The cover attachment shall prevent leaks.310AAV 14 Table 4—Air Delivery -- CFM (with Filter)* FURNACE SIZE RETURN---AIR INLET SPEED EXTERNAL STATIC PRESSURE (In. W.C.) 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0 045---08/ 024045 Bottom or Side(s) High Med --- High Med --- Low 1035 865 760 995 830 720 945 790 680 895 745 635 835 690 580 770 625 520 675 545 445 565 440 345 390 250 220 195 195 195 045---12/ 036045 Bottom or Side(s) High Med --- High Med --- Low 1440 1360 1250 1375 1300 1210 1305 1240 1160 1240 1175 1100 1160 1115 1040 1070 1040 965 975 950 885 870 850 790 730 725 670 560 575 520 070---08/ 024070 Bottom or Side(s) High Med --- High Med --- Low 1030 835 725 1005 815 700 965 790 675 925 755 635 870 710 595 810 660 545 740 590 460 645 480 350 465 325 250 280 205 --- --- 070---12/ 036070 Bottom or Side(s) High Med --- High Med --- Low 1425 1320 1200 1375 1280 1175 1320 1240 1145 1265 1205 1105 1200 1140 1050 1125 1075 990 1035 995 920 940 905 840 830 790 725 655 620 555 070---16/ 048070 Bottom or Side(s) High Med --- High Med --- Low 1755 1550 1355 1700 1520 1340 1635 1475 1310 1570 1430 1280 1505 1375 1240 1435 1310 1190 1350 1240 1125 1260 1155 1060 1160 1070 975 1055 970 890 090---14/ 042090 Bottom or Side(s) High Med --- High Med --- Low 1605 1470 1310 1570 1445 1295 1535 1410 1265 1465 1380 1230 1385 1300 1195 1285 1220 1120 1175 1115 1025 1055 990 915 895 830 710 645 600 565 090---16/ 048090 Bottom or Side(s) High Med --- High Med --- Low 1940 1740 1505 1880 1700 1505 1805 1650 1480 1720 1590 1440 1635 1525 1375 1540 1440 1300 1425 1335 1190 1290 1195 1045 1090 1010 890 830 820 740 090---20/ 060090 Bottom Only High Med --- High Med --- Low 2405 2170 1920 2310 2110 1875 2220 2040 1835 2130 1970 1780 2025 1895 1715 1920 1785 1630 1790 1675 1535 1660 1565 1420 1530 1420 1275 1350 1260 1135 Both Sides or 1 Side & Bottom High Med --- High Med --- Low 2530 2230 1895 2450 2170 1890 2365 2110 1845 2270 2050 1815 2165 1985 1755 2065 1890 1685 1940 1780 1600 1805 1660 1480 1670 1525 1350 1505 1360 1180 1Side Only High Med --- High Med --- Low 2475 2105 1850 2395 2145 1860 2300 2070 1810 2200 2010 1770 2090 1940 1715 1985 1845 1650 1865 1735 1555 1730 1620 1445 1585 1475 1310 1425 1325 1150 110---12/ 036110 Bottom or Side(s) High Med --- High Med --- Low 1600 1475 1315 1550 1435 1295 1490 1395 1265 1425 1335 1220 1355 1285 1155 1260 1185 1080 1135 1070 985 990 890 810 785 725 675 530 450 440 110---16/ 048110 Bottom or Side(s) High Med --- High Med --- Low 1980 1745 1530 1915 1710 1515 1835 1650 1470 1750 1560 1400 1655 1450 1310 1495 1340 1215 1365 1205 1095 1185 1090 990 965 865 830 700 605 670 110---22/ 066110 Bottom Only High Med --- High Med --- Low 2485 2135 1855 2415 2100 1840 2340 2060 1815 2255 2000 1775 2160 1930 1725 2080 1860 1675 1950 1765 1600 1840 1670 1510 1720 1555 1405 1565 1425 1290 Bottom Sides or 1 Side & Bot- tom High Med --- High Med --- Low --- --- 2140 1855 --- --- 2100 1840 2355 2050 1815 2285 1990 1775 2190 1935 1725 2090 1865 1675 1965 1760 1600 1850 1670 1510 1705 1545 1405 1535 1410 1290 1Side Only High Med --- High Med --- Low 2495 2030 --- --- 2440 2025 1735 2370 2000 1725 2290 1950 1695 2205 1905 1650 2120 1850 1595 2015 1750 1535 1910 1660 1455 1775 1555 1335 1625 1425 1230 * A filter is required for each return---air inlet. Airflow performance included 3/4---in. (19 mm) washable filter media such as contained in factory --- authorized ac- cessory filter rack. To determine airflow performance without this filter, assume an additional 0.1 In. W.C. available external static pressure. ------ Indicates unstable operating conditions.310AAV 15 Table 5 Air Delivery -- CFM (with Filter)* (Continued) FURNACE SIZE RETURN---AIR INLET SPEED EXTERNAL STATIC PRESSURE (In. W.C.) 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0 135---16/ 048135 Bottom or Side(s) High Med --- High Med --- Low 2065 1790 1480 2000 1755 1480 1930 1705 1480 1835 1640 1450 1710 1550 1380 1590 1465 1295 1420 1295 1160 1235 1145 1005 1025 945 855 835 775 670 135---22/ 066135 Bottom Only High Med --- High Med --- Low 2445 2130 1860 2365 2080 1830 2280 2025 1800 2190 1960 1755 2085 1880 1705 1980 1795 1630 1850 1690 1530 1705 1550 1415 1520 1405 1280 1355 1255 1140 Bottom, Sides or 1 Side & Bot- tom High Med --- High Med --- Low --- --- 2120 1860 --- --- 2075 1830 2355 1995 1800 2280 1970 1755 2160 1905 1725 2065 1835 1630 1930 1735 1530 1805 1645 1415 1655 1515 1280 1465 1325 1140 1SideOnly High Med --- High Med --- Low --- --- 2070 1860 --- --- 2015 1830 2215 1970 1800 2130 1935 1755 2030 1855 1725 1920 1765 1630 1795 1655 1530 1675 1550 1415 1540 1445 1280 1385 1265 1140 155---20/ 060155 Bottom Only High Med --- High Med --- Low 2465 2115 1800 2430 2095 1790 2375 2055 1770 2305 2005 1735 2215 1940 1695 2110 1845 1640 2000 1820 1570 1865 1675 1465 1715 1525 1345 1530 1390 1225 Both Sides Or 1 Side & Bottom High Med --- High Med --- Low --- --- 2155 1800 --- --- 2125 1790 2375 2075 1770 2285 2015 1735 2185 1935 1695 2105 1830 1640 1995 1780 1570 1870 1635 1465 1720 1485 1345 1555 1365 1225 1Side Only High Med --- High Med --- Low --- --- 2140 1800 --- --- 2085 1790 2260 2020 1770 2180 1950 1735 2070 1850 1695 1975 1745 1640 1865 1695 1570 1740 1545 1465 1595 1415 1345 1440 1290 1225 * A filter is required for each return---air inlet. Airflow performance included 3/4---in. (19 mm) washable filter media such as contained in factory --- authorized ac- cessory filter rack. To determine airflow performance without this filter, assume an additional 0.1 In. W.C. available external static pressure. ------ Indicates unstable operating conditions. UPFLOW DOWNFLOW HORIZONTAL YES NO NO YES YES YES NO 120MIN YES 120MIN YES120MIN 9090 A02020 Fig. 14 ---Duct Flanges 310AAV 16 1 / 4 " (6mm) THREADED ROD 4 REQ. SECURE ANGLE IRON TO BOTTOM OF FURNACE WITH 3 #8 x 3/4" (19mm) SCREWS TYPICAL FOR 2 SUPPORTS 1” (25mm) SQUARE, 1-1/4”x1-1/4”x1/8” (32x32x3mm) ANGLE IRON OR UNI-STRUT MAY BE USED (2) HEX NUTS, (2) WASHERS & (2) LOCK WASHERS REQ. PER ROD 8" (203mm) MIN FOR DOOR REMOVAL OUTER DOOR A S SEMBLY A10130 Fig. 15 ---Horizontal Unit Suspension METHOD 2 USE (4) #8 x 3/4 (19 mm) SHEET METAL SCREWS FOR EACH STRAP. THE STRAPS SHOULD BE VERTICAL AGAINST THE FURNACE SIDES AND NOT PULL AWAY FROM THE FURNACE SIDES. METHOD 1 FOLD ALL STRAPS UNDER FURNACE AND SECURE WTH (4) #8 x 3/4 (19 mm) SHEET METAL SCREWS (2 SCREWS IN SIDE AND 2 SCREWS IN BOTTOM). A10131 Fig. 16 ---Horizontal Suspension with Straps310AAV 17 30-IN . (762mm) MIN WORK AREA 6 ″ M IN * TYPE-B VENT 17 3 / 4 ″ 22 ″ SHEET MET AL SEDIMENT TRAP EQUIPMENT MANU AL SHUT -OFF GAS VA LV E LINE CONT A CT ONL Y PERMISSIBLE BETWEEN LINES FORMED BY INTERSECTIONS OF THE T OP AND TW O SIDES OF THE FURNA CE JA CKET AND BUILDING JOISTS , STUDS , OR FRAMING. GAS ENTR Y 17 3 / 4 ″ (451mm)OVERALL 4 3 / 4 ″ (121mm) UNDER DOOR 1 ″ (25mm) UNDER FURNACE EXTEND OUT 12 ″ (305mm) FR OM FA CE OF DOOR * WHEN USED W ITH SINGLE W ALL VEN T CONNECTIONS UNION (152mm ) (451mm) (559m m ) A10164 Fig. 17 ---Typical Attic Installation A02075 Fig. 18 ---Upflow Return Air Configurations and Restrictions 310AAV 18 A02163 Fig. 19 ---Downflow Return Air Configurations and Restrictions A02162 Fig. 20 ---Horizontal Return Air Configurations and Restrictions Upflow and Horizontal Furnaces Connect supply--air duct to flanges on furnace supply--air outlet. Bend flange upward to 90_with wide duct pliers. (See Fig. 14.) The supply--air duct must be connected to ONLY the furnace supply--outlet--air duct flanges or air conditioning coil casing (when used). DO NOT cut main furnace casing side to attach supply air duct, humidifier, or other accessories. All accessories MUST be connected to duct external to furnace main casing. NOTE: For horizontal applications, the top--most flange may be bent past 90_to allow the evaporator coil to hang on the flange temporarily while the remaining attachment and sealing of the coil are performed. Downflow Furnaces Connect supply--air duct to supply--air outlet on furnace. Bend flange inward past 90_with wide duct pliers. (See Fig. 14.) The supply--air duct must be connected to ONLY the furnace supplyoutlet or air conditioning coil casing (when used). When installed on combustible material, supply--air duct must be connected to ONLY the factory--approved accessory subbase or a factory--approved air conditioning coil casing. DO NOT cut main furnace casing to attach supply side air duct, humidifier, or other310AAV 19 accessories. All accessories MUST be connected to duct external to furnace casing. FIRE HAZARD A failure to follow this warning could result in personal injury, or death and/or property damage. Never connect return--air ducts to the back of the furnace. Follow instructions below. !WARNING Return Air Connections Downflow Furnaces The return--air duct must be connected to return--air opening (bottom inlet) as shown in Fig. 19. DO NOT cut into casing sides (left or right). Side opening is permitted for only upflow and most horizontal furnaces. (See Fig. 19.) Bypass humidifier connections should be made at ductwork or coil casing sides exterior to furnace. Upflow and Horizontal Furnaces The return--air duct must be connected to bottom, sides (left or right), or a combination of bottom and side(s) of main furnace casing as shown in Fig. 18 and 20. Bypass humidifier may be attached into unused return air side of the furnace casing. (See Fig. 18 and 20.) Not all horizontal furnaces are approved for side return air connections. (See Fig. 20.) GAS PIPING FIRE OR EXPLOSION HAZARD Failure to follow this warning could result in personal injury, death, and/or property damage. Never purge a gas line into a combustion chamber. Never test for gas leaks with an open flame. Use a commercially available soap solution made specifically for the detection of leaks to check all connections. A fire or explosion may result causing property damage, personal injury or loss of life. !WARNING FIRE OR EXPLOSION HAZARD Failure to follow this warning could result in personal injury, death, and/or property damage. Use proper length of pipe to avoid stress on gas control manifold and a gas leak. !WARNING Gas piping must be installed in accordance with national and local codes. Refer to current edition of NFGC. Installations must be made in accordance with all authorities having jurisdiction. If possible, the gas supply line should be a separate line running directly from meter to furnace. NOTE: In the state of Massachusetts: 1. Gas supply connections MUST be performed by a li- censed plumber or gas fitter. 2. When flexible connectors are used, the maximum length shall not exceed 36 inches (915 mm). 3. When lever handle type manual equipment shutoff valves are used, they shall be T--handle valves. 4. The use of copper tubing for gas piping is NOT approved by the state of Massachusetts. Refer to Table 5 for recommended gas pipe sizing. Risers must be used to connect to furnace and to meter. Support all gas piping with appropriate straps, hangers, etc. Use a minimum of 1 hanger every 6 ft. (1.8 M) Joint compound (pipe dope) should be applied sparingly and only to male threads of joints. Pipe dope must be resistant to the action of propane gas. Table 5—Maximum Capacity of Pipe NOMINALIRON PIPESIZEIN. (MM) INTERNALDIA.IN. (MM) LENGTH OF PIPE --- FT (M) 10(3.0)20(6.0)30(9.1)40(12.1)50(15.2) 1/2 (12.7) 0.622(158)175 120 97 82 73 3/4 (19.0) 0.824(20.9)360 250 200 170 151 1( 25.4) 1.049(26.6)680 465 375 320 285 1-1/4(31.8)1.380(35.0)1400 950 770 660 580 1-1/2(38.1)1.610(40.9)2100 1460 1180 990 900 * Cubic ft. of natural gas per hr for gas pressures of 0.5 psig (14---In. W.C.) or less and a pressure drop of 0.5---In. W.C. (based on a 0.60 specific gravity gas). Ref: Table 6 and ANSI Z223---2012/NFPA 54---2012. FIRE OR EXPLOSION HAZARD Failure to follow this warning could result in personal injury, death, and/or property damage. If local codes allow the use of a flexible gas appliance connector, always use a new listed connector. Do not use a connector which has previously served another gas appliance. Black iron pipe shall be installed at the furnace gas control valve and extend a minimum of 2 in. (51 mm) outside the furnace. !WARNING FURNACE OVERHEAT HAZARD Failure to follow this caution may result in unit component damage. Connect gas pipe to gas valve using a backup wrench to avoid damaging gas controls and burner misalignment. CAUTION! An accessible manual equipment shutoff valve MUST be installed external to furnace casing and within 6 ft. (1.8 M) of furnace. A 1/8--in. (3 mm) NPT plugged tapping,accessible for test gauge connection, MUST be installed immediately upstream of gas supply connection to furnace and downstream of manual equipment shutoff valve. NOTE: The furnace gas valve inlet pressure tap connection is suitable to use as test gauge connection providing test pressure DOES NOT exceed maximum 0.5 psig (14--In. W.C.) stated on gas control valve. (See Fig. 42.) Some installations require gas entry on right side of furnace (as viewed in upflow.) (See Fig. 21.) Install a sediment trap in riser leading to furnace as shown in Fig. 22. Connect a capped nipple into lower end of tee. Capped nipple should extend below level of furnace gas controls. Place a ground joint union between furnace gas control valve and exterior manual equipment gas shutoff valve. A 1/8--in. (3 mm) NPT plugged tapping,accessible for test gauge connection, MUST be installed immediately upstream of gas supply connection to furnace and downstream of manual equipment shutoff valve.310AAV 20 2” (51mm) Street Elbow A08551 Fig. 21 ---Burner and Manifold UNION SEDIMENT TRAP MANUAL SHUTOFF VALVE (REQUIRED) GAS SUPPLY A02035 Fig. 22 ---Typical Gas Pipe Arrangement Piping should be pressure and leak tested in accordance with NFGC, local, and national plumbing and gas codes before the furnace has been connected. After all connections have been made, purge lines and check for leakage at furnace prior to operating furnace. If pressure exceeds 0.5 psig (14--In. W.C.), gas supply pipe must be disconnected from furnace and capped before and during supply pipe pressure test. If test pressure is equal to or less than 0.5 psig (14--In. W.C.), turn off electric shutoff switch located on furnace gas control valve and accessible manual equipment shutoff valve before and during supply pipe pressure test. After all connections have been made, purge lines and check for leakage at furnace prior to operating furnace. The gas supply pressure shall be within the maximum and minimum inlet supply pressures marked on the rating plate with the furnace burners ON and OFF. FactoryFactory InstalledInstalled AlternateAlternate LocationLocation A10291 Fig. 23 ---Relocating J--Box A10141 Fig. 24 ---Field--Supplied Electrical Box on Furnace Casing ELECTRICAL CONNECTIONS ELECTRICAL SHOCK HAZARD Failure to follow this warning could result in personal injury or death. Blower access panel door switch opens 115--v power to control. No component operation can occur. Do not bypass or close switch with panel removed. !WARNING See Fig. 26 for field wiring diagram showing typical field 115--v wiring. Check all factory and field electrical connections for tightness.310AAV 21 ELECTRICAL SHOCK AND FIRE HAZARD Failure to follow this warning could result in personal injury, death, or property damage. The cabinet MUST have an uninterrupted or unbroken ground according to NEC ANSI/NFPA 70--2011 or local codes to minimize personal injury if an electrical fault should occur. This may consist of electrical wire, conduit approved for electrical ground or a listed, grounded power cord (where permitted by local code) when installed in accordance with existing electrical codes. Refer to the power cord manufacturer’s ratings for proper wire gauge. Do not use gas piping as an electrical ground. !WARNING FURNACE MAY NOT OPERATE Failure to follow this caution may result in intermittent furnace operation. Furnace control must be grounded for proper operation or else control will lock out. Control must remain grounded through green/yellow wire routed to gas valve and manifold bracket screw. CAUTION! 115--V WIRING Verify that the voltage, frequency, and phase correspond to that specified on unit rating plate. Also, check to be sure that service provided by utility is sufficient to handle load imposed by this equipment. Refer to rating plate or Table 6 for equipment electrical specifications. Make all electrical connections in accordance with National Electrical Code (NEC) ANSI/NFPA 70--2011 and any local codes or ordinances that might apply. FIRE HAZARD Failure to follow this warning could result in personal injury, death, or property damage. Do not connect aluminum wire between disconnect switch and furnace. Use only copper wire. !WARNING Use a separate, fused branch electrical circuit with a properly sized fuse or circuit breaker for this furnace. See Table 6 for wire size and fuse specifications. A readily accessible means of electrical disconnect must be located within sight of the furnace. NOTE: Proper polarity must be maintained for 115--v wiring. If polarity is incorrect, control LED status indicator light will flash rapidly and furnace will NOT operate. J--BOX RELOCATION NOTE: If factory location of J--Box is acceptable, go to next section (ELECTRICAL CONNECTION TO J--BOX). NOTE: On 14--in. (356 mm) wide casing models, the J--Box shall not be relocated to other side of furnace casing when the vent pipe is routed within the casing. 1. Remove and save two screws holding J--Box. (See Fig. 23.) NOTE: The J--Box cover need not be removed from the J--Box in order to move the J--Box. Do NOT remove green ground screw inside J--Box. The ground screw is not threaded into the casing flange and can be lifted out of the clearance hole in casing while swinging the front edge of the J--Box outboard of the casing. 2. Cut wire tie on loop in furnace wires attached to J--box. 3. Move J--Box to desired location. 4. Fasten J--Box to casing with two screws removed in Step 1. 5. Route J--Box wires within furnace away from sharp edges, rotating parts and hot surfaces. ELECTRICAL CONNECTION TO J--BOX Field--Supplied Electrical Box on Furnace J--Box Bracket See Fig. 24. 1. Remove cover from furnace J--Box. 2. Attach electrical box to furnace J--Box bracket with at least two field--supplied screws through holes in electrical box into holes in bracket. Use blunt--nose screws that will not pierce wire insulation. 3. Route furnace power wires through holes in electrical box and J--Box bracket, and make field--wire connections in electrical box. Use best practices (NEC in U.S.) for wire bushings, strain relief, etc. 4. Route and secure field ground wire to green ground screw on J--Box bracket. 5. Connect line voltage leads as shown in Fig. 26. 6. Reinstall cover to J--Box. Do not pinch wires between cover and bracket. Electrical Box on Furnace Casing Side See Fig. 24. FIRE OR ELECTRICAL SHOCK HAZARD Failure to follow this warning could result in personal injury, death, or property damage. If field--supplied manual disconnect switch is to be mounted on furnace casing side, select a location where a drill or fastener cannot damage electrical or gas components. !WARNING 1. Select and remove a hole knockout in the casing where the electrical box is to be installed. NOTE: Check that duct on side of furnace will not interfere with installed electrical box. 2. Remove the desired electrical box hole knockout and posi- tion the hole in the electrical box over the hole in the fur- nace casing. 3. Fasten the electrical box to casing by driving two field supplied screws from inside electrical box into casing steel. 4. Remove and save two screws holding J--Box. (See Fig. 23.) 5. Pull furnace power wires out of 1/2--in. (12 mm) diameter hole in J--Box. Do not loosen wires from strain--relief wire--tie on outside of J--Box. 6. Route furnace power wires through holes in casing and electrical box and into electrical box. 7. Pull field power wires into electrical box. 8. Remove cover from furnace J--Box. 9. Route field ground wire through holes in electrical box and casing, and into furnace J--Box. 10. Reattach furnace J--Box to furnace casing with screws re- movedinStep4. 11. Secure field ground wire to J--Box green ground screw.310AAV 22 Table 6—Electrical Data FURNACE SIZE VO LTS --- H ER TZ --- PHASE OPERATING VOLTAGE RANGE MAXIMUM UNIT AMPS UNIT AMPACITY# MAXIMUM WIRE LENGTH FT. (M)‡ MAXIMUM FUSE OR CKT BKR AMPS† MINIMUM WIRE GAUGEMaximum*Minimum* 045---08/024045 115 --- 60 --- 1 127 104 5.2 7.26 49 (14.9)15 14 045---12/036045 115 --- 60 --- 1 127 104 7.2 9.79 37 (11.2)15 14 070---08/024070 115 --- 60 --- 1 127 104 5.1 7.14 51 (15.5)15 14 070---12/036070 115 --- 60 --- 1 127 104 7.2 9.72 38 (11.5)15 14 070---16/048070 115 --- 60 --- 1 127 104 9.5 12.60 29 (8.8)15 14 090---14/042090 115 --- 60 --- 1 127 104 8.6 11.39 32 (9.7)15 14 090---16/048090 115 --- 60 --- 1 127 104 10.0 13.09 28 (8.5)15 14 090---20/060090 115 --- 60 --- 1 127 104 14.1 18.2 31 (9.4)20 12 110---12/036110 115 --- 60 --- 1 127 104 8.6 11.27 32 (9.7)15 14 110---16/048110 115 --- 60 --- 1 127 104 10.2 13.34 27 (8.2)15 14 110---22/066110 115 --- 60 --- 1 127 104 15.1 19.42 29 (8.8)20 12 135---16/048135 115 --- 60 --- 1 127 104 10.5 13.63 27 (8.2)15 14 135---22/066135 115 --- 60 --- 1 127 104 14.5 18.72 30 (9.1)20 12 155---20/060155 115 --- 60 --- 1 127 104 15.4 19.83 29 (8.8)20 12 * Permissible limits of the voltage range at which the unit operates satisfactorily. # Unit ampacity = 125 percent of largest operating component’s full load amps plus 100 percent of all other potential operating components’ (EAC, humidifier, etc.) full load amps. {Time---delay type is recommended. }Length shown is as measured 1 way along wire path between unit and service panel for maximum 2 percent voltage drop. 12. Complete electrical box wiring and installation. Connect line voltage leads as shown in Fig. 26. Use best practices (NEC) for wire bushings, strain relief, etc. 13. Reinstall cover to J--Box. Do not pinch wires between cover and bracket. POWER CORD INSTALLATION IN FURNACE J--BOX NOTE: Power cords must be able to handle the electrical requirements listed in Table 6. Refer to power cord manufacturer’s listings. 1. Remove cover from J--Box. 2. Route listed power cord through 7/8--in. (22 mm) diameter hole in J--Box. 3. Secure power cord to J--Box bracket with a strain relief bushing or a connector approved for the type of cord used. 4. Secure field ground wire to green ground screw on J--Box bracket. 5. Connect line voltage leads as shown in Fig. 26. 6. Reinstall cover to J--Box. Do not pinch wires between cover and bracket. BX CABLE INSTALLATION IN FURNACE J--BOX 1. Remove cover from J--Box. 2. Route BX cable into 7/8--inch (22 mm) diameter hole in J--Box. 3. Secure BX cable to J--Box bracket with connectors ap- proved for the type of cable used. 4. Secure field ground wire to green ground screw on J--Box bracket. 5. Connect line voltage leads as shown in Fig. 26. 6. Reinstall cover to J--Box. Do not pinch wires between cover and bracket.310AAV 23BLWNUETRALSTATUS CODE LEDSEC-2 SEC-1 EAC-2 L2 FUSE 3-AMP 0.5 AMP@24VAC HUM TEST/TWIN G Com W Y R24V120 18090 150BLOWER OFF-DELAY COOL HEATSPARE-1 SPARE-2 PR-1L1 PL2 1 24-V THERMOSTAT TERMINALS 3-AMP FUSE LED OPERATION & DIAGNOSTIC LIGHT 115-VAC(L2)NEUTRAL CONNECTIONS COOL HEAT SPARE-1 SPARE-2 BLOWER SPEED SELECTION TERMINALS EAC-1 TERMINAL (115-VAC 1.0 AMP MAX.) 115 VAC (L1) LINE VOLTAGE CONNECTION PL2-HOT SURFACE IGNITER & INDUCER MOTOR CONNECTOR PL1-LOW VOLTAGE MAIN HARNESS CONNECTOR TRANSFORMER 24-VAC CONNECTIONS HUMIDIFIER TERMINAL (24-VAC 0.5 AMP MAX.) TWINNING AND/OR COMPONENT TEST TERMINAL BLOWER OFF-DELAY J2J2 JUMPER PLTPL1SPARE-3 SPARE-31 A11619 Fig. 25 ---Furnace Control 115-V FIELD-SUPPLIEDDISCONNECT AUXILIARYJ-BOX 24-V TERMINALBLOCK THREE-WIREHEATING-ONLY FIVE WIRE NOTE 1 NOTE 2 FIELD-SUPPLIED DISCONNECT CONDENSINGUNIT TWOWIRE FURNACE CO NTR OL R G COM WCR GY GND GND FIELD 24-V WIRINGFIELD 115-, 208/230-, 460-V WIRINGFACTORY 24-V WIRING FACTORY 115-V WIRING 208/230- OR460-V THREEPHASE 208/230-V SINGLEPHASE BLOWER DOOR SWITCH WHT BLK WHT BLK NOTES:Connect Y-terminal in furnace as shown for proper blower operation.Some thermostats require a "C" terminal connection as shown.If any of the original wire, as supplied, must be replaced, use same type or equivalent wire. W Y/Y2 GND THERMOSTATTERMINALS 1.2.3. A99440 Fig. 26 ---Heating and Cooling Application Wiring Diagram with Single Stage Thermostat 310AAV 24 24--V WIRING Make field 24--v connections at the 24--v terminal strip. (See Fig. 25.) Connect terminal Y as shown in Fig. 26 for proper cooling operation. Use only AWG No. 18, color--coded, copper thermostat wire. The 24--v circuit contains an automotive--type, 3--amp. fuse located on the control. Any direct shorts during installation, service, or maintenance could cause this fuse to blow. If fuse replacement is required, use ONLY a 3--amp. fuse of identical size. ACCESSORIES 1. Electronic Air Cleaner (EAC) Connect an accessory Electronic Air Cleaner (if used) us- ing 1/4--in female quick connect terminals to the two male 1/4--in quick--connect terminals on the control board marked EAC--1 and EAC--2. The terminals are rated for 115 VAC, 1.0 amps maximum and are energized during blower motor operation. (See Fig. 24.) 2. Humidifier (HUM) Connect an accessory 24 VAC, 0.5 amp. maximum hu- midifier (if used) to the 1/4--in male quick--connect HUM terminal and COM--24V screw terminal on the control board thermostat strip. The HUM terminal is energized when gas valve relay (GVR) is energized. (See Fig. 24.) NOTE: A field--supplied, 115--v controlled relay connected to EAC terminals may be added if humidifier operation is desired during blower operation. NOTE: DO NOT connect furnace control HUM terminal to HUM (humidifier) terminal on Thermidistatt, Zone Controller or similar device. See Thermidistatt, Zone Controller, thermostat, or controller manufacturer’s instructions for proper connection. VENTING The furnace shall be connected to a listed factory built chimney or vent, or a clay--tile lined masonry or concrete chimney. Venting into an unlined masonry chimney or concrete chimney is prohibited. When an existing Category I furnace is removed or replaced, the original venting system may no longer be sized to properly vent the attached appliances. An improperly sized Category I venting system could cause the formation of condensate in the furnace and vent, leakage of condensate and combustion products, and spillage of combustion products into the living space. Vent system or vent connectors may need to be resized. Vent systems or vent connectors, must be sized to approach minimum size as determined using appropriate table found in the NFGC. GENERAL VENTING REQUIREMENTS Follow all safety codes for proper vent sizing and installation requirements, including local building codes, the National Fuel Gas Code ANSI Z223.1--2012/NFPA 54--2012 (NFGC), Parts 12 and 13, local building codes, and furnace and vent manufacturers’ instructions. CARBON MONOXIDE POISONING HAZARD Failure to follow the steps outlined below for each appliance connected to the venting system being placed into operation could result in carbon monoxide poisoning or death. The following steps shall be followed for each appliance connected to the venting system being placed into operation, while all other appliances connected to the venting system are not in operation: 1. Seal any unused openings in venting system. 2. Inspect the venting system for proper size and horizontal pitch, as required in the National Fuel Gas Code, ANSI Z223.1/NFPA 54 and these instructions. Determine that there is no blockage or restriction, leakage, corrosion and other deficiencies, which could cause an unsafe condition. 3. As far as practical, close all building doors and windows and all doors between the space in which the appliance(s) connected to the venting system are located and other spaces of the building. 4. Close fireplace dampers. 5. Turn on clothes dryers and any appliance not connected to the venting system. Turn on any exhaust fans, such as range hoods and bathroom exhausts, so they are operating at maximum speed. Do not operate a summer exhaust fan. 6. Follow the lighting instructions. Place the appliance being inspected into operation. Adjust the thermostat so appliance is operating continuously. 7. Test for spillage from draft hood equipped appliances at the draft hood relief opening after 5 minutes of main burner operation. Use the flame of a match or candle. 8. If improper venting is observed during any of the above tests, the venting system must be corrected in accordance with the National Fuel Gas Code, ANSI Z223.1/NFPA 54 . 9. After it has been determined that each appliance connected to the venting system properly vents when tested as outlined above, return doors, windows, exhaust fans, fireplace dampers and any other gas--fired burning appliance to their previous conditions of use. !WARNING These furnaces are design--certified as Category I furnaces in accordance with ANSI Z21.47--2012/CSA 2.3--2012 and operate with a non--positive vent static pressure to minimize the potential for vent gas leakage. Category I furnaces operate with a flue loss not less than 17 percent to minimize the potential for condensation in the venting system. These furnaces are approved for common venting and multistory venting with other fan assisted or draft hood equipped appliances in accordance with the NFGC, the local building codes, and furnace and vent manufacturers’ instructions. The following information and warning must be considered in addition to the requirements defined in the NFGC. CARBON MONOXIDE POISONING HAZARD Failure to follow this warning could result in personal injury or death. Do not bypass the draft safeguard switch, as an unsafe condition could exist which must be corrected. !WARNING310AAV 25 1. If a vent (common or dedicated) becomes blocked, the fur- nace will be shut off by the draft safeguard switch located on the vent elbow. 2. Do not connect this Category I furnace into a single--wall dedicated or common vent. The dedicated or common vent is considered to be the vertical portion of the vent system that terminates outdoors. 3. Vent connectors serving Category I furnaces shall not be connected into any portion of a mechanical draft system operating under positive pressure. 4. Do not vent this appliance with any solid fuel burning ap- pliance. 5. Category I furnaces must be vented vertically or nearly vertically unless equipped with a listed power venter. 6. Do not vent this appliance into an unlined masonry chim- ney. Refer to Chimney Inspection Chart, Fig. 27. MASONRY CHIMNEY REQUIREMENTS NOTE: These furnaces are CSA design--certified for use in exterior clay tile--lined masonry chimneys with a factory accessory Chimney Adapter Kit. Refer to the furnace rating plate for correct kit usage. The Chimney Adapter Kits are for use with ONLY furnaces having a Chimney Adapter Kit numbers marked on the furnace rating plate. If a clay tile--lined masonry chimney is being used and it is exposed to the outdoors below the roof line, relining might be required. Chimneys shall conform to the Standard for Chimneys, Fireplaces, Vents, and Solid Fuel Burning Appliances ANSI/NFPA 211--2012 and must be in good condition. U.S.A.--Refer to NFPA 54/ANSI Z223.1--2012 Sections 13.1.8 and 13.2.20 of the NFGC or the authority having jurisdiction to determine whether relining is required. If relining is required, use a properly sized listed metal liner, Type--B vent, or a listed alternative venting design. NOTE: See the NFPA 54 / ANSI Z223.1--2012, 13.1.8 and 13.2.20 regarding alternative venting design and the Exception, which cover installations such as the Chimney Adapter Kits which are listed for use with these furnaces. The Chimney Adapter Kit is listed alternative venting system for these furnaces. See the kit instructions for complete details. See the Product Data Sheet for accessory list. This furnace is permitted to be vented into a clay tile--lined masonry chimney that is exposed to the outdoors below the roof line, provided: 1. Vent connector is Type--B double--wall, and 2. This furnace is common vented with at least 1 draft hood equipped appliance, and 3. The combined appliance input rating is less than the max- imum capacity given in Table 7 , and 4. The input rating of each space heating appliance is greater than the minimum input rating given in Table 8 for the local 99% Winter Design Temperature. Chimneys having internal areas greater than 38 in 2 (24516 mm 2)require fur- nace input ratings greater than the input ratings of these furnaces. See footnote at bottom of Table 8, and 5. The authority having jurisdiction approves. If all of these conditions cannot be met, an alternative venting design shall be used, such as the listed chimney adapter kit with these furnaces, which are listed for use with the kit, a listed chimney--lining system, or a Type--B common vent. Inspections before the sale and at the time of installation will determine the acceptability of the chimney or the need for repair and/or (re)lining. Refer to the Fig. 27 to perform a chimney inspection. If the inspection of a previously used tile--lined chimney: a. Shows signs of vent gas condensation, the chimney should be relined in accordance with local codes and the authority having jurisdiction. The chimney should be relined with a listed metal liner, Type--B vent, or a listed chimney adapter kit shall be used to reduce con- densation. If a condensate drain is required by local code, refer to the NFPA 54 / ANSI Z223.1--2012, Sec- tion 12.10 for additional information on condensate drains. b. Indicates the chimney exceeds the maximum permiss- ible size in the tables, the chimney should be rebuilt or relined to conform to the requirements of the equip- ment being installed and the authority having jurisdic- tion. A chimney without a clay tile liner, which is otherwise in good condition, shall be rebuilt to conform to ANSI/NFPA 211 or be lined with a UL listed metal liner or UL listed Type--B vent. Relining with a listed metal liner or Type--B vent is considered to be a vent--in--a--chase. If a metal liner or Type--B vent is used to line a chimney, no other appliance shall be vented into the annular space between the chimney and the metal liner.310AAV 26 CHIMNEY INSPECTION CHART For additional requirements refer to the National Fuel Gas Code NFPA 54/ANSI Z223.1 and ANSI/NFPA 211 Chimneys, Fireplaces, Vents, and Solid Fuel Burning Appliances Consult Part C of chimney adapter venting instructions for application suitability Is chimney lined with properly sized, listed liner or Type-B vent? Is chimney to be dedicated to a single furnace? Chimney exposed to outdoors below roof line? Repair liner or top seal or reline chimney as necessary. Mortar or tile debris? Clay tile misalignment, missing sections, gaps? Debris in cleanout? Mortar, tile, metal vent, fuel oil residue? Is liner and top seal in good condition? Is chimney property lined with clay tile liner? Crown condition: Missing mortar or brick? Rebuild crown.Yes Yes No No No Reline Yes Repair Yes YesYes NoNo Remove mortar and tile debris Remove metal vent or liner. No No No No Yes Yes Suitable Suitable Not Suitable Line chimney with property sized, listed flexible metal liner or Type-B vent per NFGC Vent Sizing Tables and liner or vent manufacturer’s Installation instructions. Install chimney adapter per instructions. Chimney is acceptable for use. Install chimney adapter per instructions. Consult Part B of chimney adapter venting instructions for application suitability. Yes Not Suitable Condensate drainage at bottom of chimney? Yes No A10133 Fig. 27 ---Chimney Inspection Chart310AAV 27 APPLIANCE APPLICATION REQUIREMENTS Appliance operation has a significant impact on the performance of the venting system. If the appliances are sized, installed, adjusted, and operated properly, the venting system and/or the appliances should not suffer from condensation and corrosion. The venting system and all appliances shall be installed in accordance with applicable listings, standards, and codes. The furnace should be sized to provide 100 percent of the design heating load requirement plus any margin that occurs because of furnace model size capacity increments. Heating load estimates can be made using approved methods available from Air Conditioning Contractors of America (Manual J); American Society of Heating, Refrigerating, and Air--Conditioning Engineers; or other approved engineering methods. Excessive oversizing of the furnace could cause the furnace and/or vent to fail prematurely. When a metal vent or metal liner is used, the vent must be in good condition and be installed in accordance with the vent manufacturer’s instructions. To prevent condensation in the furnace and vent system, the following precautions must be observed: 1. The return--air temperature must be at least 60_F(16_C) db except for brief periods of time during warm--up from setback at no lower than 55_F(13_C) db or during initial start--up from a standby condition. 2. Adjust the gas input rate per the installation instructions. Low gas input rate causes low vent gas temperatures, caus- ing condensation and corrosion in the furnace and/or vent- ing system. Derating is permitted only for altitudes above 2000 ft. (610 M). 3. Adjust the air temperature rise to the midpoint of the rise range or slightly above. Low air temperature rise can cause low vent gas temperature and potential for condensation problems. 4. Set thermostat heat anticipator or cycle rate to reduce short cycling. Air for combustion must not be contaminated by halogen compounds which include chlorides, fluorides, bromides, and iodides. These compounds are found in many common home products such as detergent, paint, glue, aerosol spray, bleach, cleaning solvent, salt, and air freshener, and can cause corrosion of furnaces and vents. Avoid using such products in the combustion--air supply. Furnace use during construction of the building could cause the furnace to be exposed to halogen compounds, causing premature failure of the furnace or venting system due to corrosion. Vent dampers on any appliance connected to the common vent can cause condensation and corrosion in the venting system. Do not use vent dampers on appliances common vented with this furnace. ADDITIONAL VENTING REQUIREMENTS A 4--in. (102 mm) round vent elbow is supplied with the furnace. A 5--in. (127 mm) or 6--in. (152 mm) vent connector may be required for some model furnaces. A field--supplied 4--in. (102 mm) to 5--in. (127 mm) or 4--in. (102 mm) to 6--in. (152 mm) sheet metal increaser fitting is required when 5--in. (127 mm) or 6--in. (152 mm) vent connector is used. See Fig. 28 -- 40 Venting Orientation for approved vent configurations. NOTE: Vent connector length for connector sizing starts at furnace vent elbow. The 4--in. (102 mm) vent elbow is shipped for upflow configuration and may be rotated for other positions. Remove the 3 screws that secure vent elbow to furnace, rotate furnace vent elbow to position desired, reinstall screws. The factory--supplied vent elbow does NOT count as part of the number of vent connector elbows. The vent connector can exit the cabinet of the furnace through one of 5 locations. 1. Attach the single wall vent connector to the furnace vent elbow, and fasten the vent connector to the vent elbow with at least two field--supplied, corrosion--resistant, sheet metal screws located 180_apart. NOTE: An accessory flue extension is available to extend from the furnace elbow to outside the furnace casing. See the Product Data Sheet for accessory list. If flue extension is used, fasten the flue extension to the vent elbow with at least two field--supplied, corrosion--resistant, sheet metal screws located 180_apart. Fasten the vent connector to the flue extension with at least two field--supplied, corrosion resistant sheet metal screws located 180_apart. 2. Vent the furnace with the appropriate connector as shown in Fig. 28 -- 40. CUT HAZARD Failure to follow this caution may result in personal injury. Sheet metal parts may have sharp edges or burrs. Use care and wear appropriate protective clothing, safety glasses and gloves when handling parts and servicing furnaces. CAUTION! 3. Determine the correct location of the knockout to be re- moved. 4. Use a hammer and screwdriver to strike a sharp blow between the tie points and work the slug back and forth until the slug breaks free. BURN HAZARD Failure to follow this caution may cause personal injury. Hot vent pipe is within reach of small children when installed in downflow position. See the following instruction. CAUTION! An accessory Vent Guard Kit is REQUIRED for downflow applications for use where the vent exits through the lower portion of the furnace casing. Refer to the Vent Guard Kit Instructions for complete details. See the Product Data Sheet for accessory list. The horizontal portion of the venting system shall slope upwards not less than 1/4--in. (6 mm) per linear ft. (21 mm/m) from the furnace to the vent and shall be rigidly supported every 5 ft. (1.5 M) or less with metal hangers or straps to ensure there is no movement after installation. SIDEWALL VENTING This furnace is not approved for direct sidewall horizontal venting. Per section 12.4.3 of the NFPA 54 / ANSI Z223.1--2012, any listed mechanical venter may be used, when approved by the authority having jurisdiction.310AAV 28 Table 7—Exterior Masonry Chimney Fan + Nat Installations with Type--B Double Wall Vent Connectors ENFPA & AGA Combined Appliance Maximum Input Rating in Thousands of Btuh per Hour VENT HEIGHT FT. (M) INTERNAL AREA OF CHIMNEY SQ. IN. (SQ. MM) 12 (7741) 19 (12258) 28 (18064) 38 (24516) 6 (1.8)74 119 178 257 8 (2.4)80 130 193 279 10 (3.0)84 138 207 299 15 (4.5)NR 152 233 334 20 (6.0)NR NR 250 368 30 (9.1)NR NR NR 404 Table 8—Minimum Allowable Input Rating of Space--Heat- ing Appliance in Thousands of Btuh per Hour VENT HEIGHT FT. (M) INTERNAL AREA OF CHIMNEY SQ. IN. (SQ. MM) 12 (7741) 19 (12258) 28 18064) 38 (24516) Local 99% Winter Design Temperature: 17 to 26 degrees F 6 0 55 99 141 8 52 74 111 154 10 NR 90 125 169 15 NR NR 167 212 20 NR NR 212 258 30 NR NR NR 362 Local 99% Winter Design Temperature: 5 to 16 degrees F* 6 NR 78 121 166 8 NR 94 135 182 10 NR 111 149 198 15 NR NR 193 247 20 NR NR NR 293 30 NR NR NR 377 Local 99% Winter Design Temperature: ---10 to 4 degrees F* 6 NR NR 145 196 8 NR NR 159 213 10 NR NR 175 231 15 NR NR NR 283 20 NR NR NR 333 30 NR NR NR NR Local 99% Winter Design Temperature: ---11_F(16_C)or lower Not recommended for any vent configuration. *The 99.6% heating db temperatures found in the 1997 or 2001 ASHRAE Fundamentals Handbook, Climatic Design Information chapter, Table 1A (United States) or the 2005 ASHRAE Fundamentals handbook, Climatic Design Information chapter, and the CD---ROM included with the 2005 ASHRAE Fundamentals Handbook.310AAV 29 Table 9—Minimum Vent Heights Caution!! for the following applications, use the minimum vertical vent heights as specified below. For all other applications, follow exclusively the national fuel gas code. FURNACE ORIENTATION VENT ORIENTATION FURNACE INPUT (BTUH/HR) MINIMUM VENT DIAMETER IN. (mm)* MINIMUM VERTICAL VENT HEIGHT FT. (M)** Downflow Vent elbow left, then up Fig. 32 154,000 132,000 110,000(036/---12 only) 5 (127)12 (3.6) Horizontal Left Vent elbow right, then up Fig. 35 154,000 132,000 5 (127)7 (.65) Horizontal Left Vent Elbow up Fig.36 154,000 132,000 5 (127)7 (,65) Horizontal Left Vent elbow right Fig. 37 154,000 5 (127)7 (.65) Downflow Vent elbow up then left Fig. 30 110,000 (036/---12 only) 5 (127)10 (3.0) Downflow Vent elbow up, then right Fig.33 110,000 (036/---12 only) 5 (127)10 (3.0) * 4 in. (102 mm) inside casing or vent guard ** Including 4 in. (102 mm) vent section (s) NOTE:All vent configurations must also meet National Fuel Gas Code (NFGC) venting requirements NOTE: For all unlisted vent configurations, refer to National Fuel Gas Code (NFGC) venting requirements. SEE NOTES: 1,2,4,7,8,9on the page following these figures A03208 Fig. 28 ---Upflow Application--Vent Elbow Up SEE NOTES: 1,2,3,4,7,8,9 on the pages followingthese figures A03209 Fig. 29 ---Upflow Application--Vent Elbow Right 310AAV 30 SEE NOTES:1,2,3,4,5,7,8,9on the page followingthese figures A03210 Fig. 30 ---Downflow Application--Vent Elbow Up then Left SEE NOTES: 1,2,4,5,7,8,9on the page followingthese figures A03211 Fig. 31 ---Downflow Application--Vent Elbow Up SEE NOTES: 1,2,4,5,6,7,8,9,10on the page following these figures A03207 Fig. 32 ---Downflow Application--Vent Elbow Left then Up SEE NOTES:1,2,3,4,5,7,8,9 on the page following these figures. A03212 Fig. 33 ---Downflow Application--Vent Elbow Up then Right SEE NOTES: 1,2,4,7,8,9 on the pagefollowing these figures A03213 Fig. 34 ---Horizontal Left Application--Vent Elbow Left310AAV 31 SEE NOTES: 1,2,4,5,7,8,9 on the pagefollowing these figures A03214 Fig. 35 ---Horizontal Left Application--Vent Elbow Right then Up SEE NOTES: 1,2,4,5,7,8,9 on the pagefollowing these figures A03215 Fig. 36 ---Horizontal Left Application--Vent Elbow Up SEE NOTES: 1,2,4,5,7,8,9 on the pagefollowing these figures A03216 Fig. 37 ---Horizontal Left Application--Vent Elbow Right SEE NOTES: 1,2,4,7,8,9 on the pagefollowing these figures A03218 Fig. 38 ---Horizontal Right Application--Vent Elbow Right SEE NOTES: 1,2,4,5,7,8,9 on the pagefollowing these figures A03219 Fig. 39 ---Horizontal Right Application--Vent Elbow Left then Up SEE NOTES: 1,2,4,5,7,8,9 A02068 Fig. 40 ---Horizontal Right Application--Vent Elbow Left NOTES FOR FIGURES 28 -- 40 1.For common vent, vent connector sizing and vent material, use the NFGC. 2.Immediately increase to 5--in. (127 mm) or 6--in. (152 mm) vent connector outside furnace casing when 5--in. (127 mm) vent connector is required, refer to Note 1 above. 3.Side outlet vent for upflow and downflow installations must use Type B vent immediately after exiting the furnace, except when field--approved Downflow Vent Guard Kit, is used in the downflow position. See Product Data Sheet for accessory list. 4.Type--B vent where required, refer to the Note 1 above. 5.A 4--in. (102 mm) single--wall (26 ga. minimum) vent must be used inside furnace casing and when the field--approved Downflow Vent Guard Kit is used external to the furnace. See Product Data Sheet for accessory list. 6.Accessory Downflow Vent Guard Kit required in downflow installations with lower vent configuration. See Product Data Sheet for accessory list. 7.Chimney Adapter Kit may be required for exterior masonry chimney applications. Refer to Chimney Adapter Kit for sizing and complete application details. See Product Data Sheet for accessory list. 8.Secure vent connector to furnace elbow with (2) corrosion--resistant sheet metal screws, spaced approximately 180apart. 9.Secure all other single wall vent connector joints with (3) corrosion resistant screws spaced approximately 120apart. Secure Type--B vent connect- ors per vent connector manufacturer’s recommendations. 10.The total height of the vent and connector shall be at least seven ft. (2.1 M) for the 154,000 Btuh gas input rate model when installed in a downflow application with furnace elbow turned to left side with the connector elbow outside furnace casing pointing upward. (See Fig. 31.)310AAV 32 START--UP, ADJUSTMENT, AND SAFETY CHECK Step 1 —General FIRE HAZARD Failure to follow this warning could result in personal injury, death and/or property damage. This furnace is equipped with manual reset limit switches in the gas control area. The switches open and shut off power to the gas valve if a flame rollout or overheating condition occurs in the gas control area. DO NOT bypass the switches. Correct inadequate combustion air supply problem before resetting the switches. !WARNING CUT HAZARD Failure to follow this caution may result in personal injury. Sheet metal parts may have sharp edges or burrs. Use care and wear appropriate protective clothing, safety glasses, and gloves when handling parts and servicing furnaces. CAUTION! 1. Maintain 115--v wiring and ground. Improper polarity will result in rapid flashing LED and no furnace operation. 2. Make thermostat wire connections at the 24--v terminal block on the furnace control. Failure to make proper con- nections will result in improper operation. (See Fig. 26.) 3. Gas supply pressure to the furnace must be greater than 4.5--In. W.C. (0.16 psig ) but not exceed 14--In. W.C. (0.5 psig). 4. Check all manual--reset switches for continuity. 5. Install blower compartment door. Door must be in place to operate furnace. 6. Replace outer door. Step 2 —Start--Up Procedures FIRE AND EXPLOSION HAZARD Failure to follow this warning could result in personal injury, death and or property damage. Never test for gas leaks with an open flame. Use a commercially available soap solution made specifically for the detection of leaks to check all connections. A fire or explosion may result causing property damage, personal injury or loss of life. !WARNING 1. Purge gas lines after all connections have been made. 2. Check gas lines for leaks. ELECTRICAL SHOCK HAZARD Failure to follow this warning could result in personal injury, or death. Blower access door switch opens 115--v power to control. No component operation can occur unless switch is closed. Caution must be taken when manually closing this switch for service purposes. !WARNING 3. To Begin Component Self--Test: Remove blower access door. Disconnect the thermostat R lead from the furnace control board. Manually close the blower door switch. Short (jumper) the COM--24v terminal on control to the TEST/TWIN 3/16--inch quick connect terminal on control until LED goes out (approximately 2 sec). Gas valve and humidifier will not be turned on. (See Fig. 25.) NOTE: The furnace control allows all components, except the gas valve, to be run for short period of time. This feature helps diagnose a system problem in case of a component failure. Component test feature will not operate if any thermostat signal is present at the control. Component test sequence is as follows: Refer to service label attached to furnace or see Fig. 45. a. LED will display previous status code 4 times. b. Inducer motor starts and continues to run until Step f of component test sequence. c. Hot surface igniter is energized for 15 sec., then off. d. Blower motor operates on HEAT speed for 10 sec. e. Blower motor operates on COOL speed for 10 sec. f. Inducer motor stops. g. Reconnect R lead to furnace control board, release blower door switch and re--install blower door. 4. Operate furnace per instruction on door. 5. Verify furnace shut down by lowering thermostat setting below room temperature. 6. Verify furnace restarts by raising thermostat setting above room temperature. Step 3 —Adjustments Table 10—Altitude Derate Multiplier for U.S.A. ALTITUDE FT. (M) PERCENT OF DERATE DERATE MULTIPLIER FACTOR* 0–2000 (0---610)0 1.00 2001–3000 (610---914)8–12 0.90 3001–4000 (914---1219)12–16 0.86 4001–5000 (1219---1524)16–20 0.82 5001–6000 1524---1829)20–24 0.78 6001–7000 (1829---2134)24–28 0.74 7001–8000 (2134---2438)28–32 0.70310AAV 33 8001–9000 (2438---2743)32–36 0.66 9001–10,000 (2743---3048)36–40 0.62 * Derate multiplier factors are based on midpoint altitude for altitude range. FIRE HAZARD Failure to follow this warning could result in injury, death and/or property damage. DO NOT bottom out gas valve regulator adjusting screw. This can result in unregulated manifold pressure and result in excess overfire and heat exchanger failures. !WARNING FURNACE DAMAGE HAZARD Failure to follow this caution may result in reduced furnace life. DO NOT redrill orifices. Improper drilling (burrs, out--of round holes, etc.) can cause excessive burner noise and misdirection of burner flames. This can result in flame impingement of heat exchangers, causing failures. (See Fig. 43.) CAUTION! Furnace gas input rate on rating plate is for installations at altitudes up to 2000 ft. (610 M). Furnace input rate must be within +/--2 percent of furnace rating plate input. 1. Determine the correct gas input rate. The input rating for altitudes above 2,000 ft. (610 M) must be reduced by 4 percent for each 1,000 ft. (305 M) above sea level. For installations below 2000 ft., refer to the unit rating plate. For installations above 2000 ft. (610 M), mul- tiply the input on the rating plate by the derate multiplier in Table 10 for the correct input rate. 2. Determine the correct orifice and manifold pressure adjust- ment. There are two different orifice and manifold adjust- ment tables. All models in all positions, except Low NOx models in downflow or horizontal positions, use Table 14 (22,000 Btuh/Burner). Low NOx models in the downflow or horizontal positions must use Table 15 (21,000 Btuh/Burner). See input listed on rating plate. a. Obtain average yearly gas heat value (at installed alti- tude) from local gas supplier. b. Obtain average yearly gas specific gravity from local gas supplier. c. Find installation altitude in Table 14 or 15. d. Find closest natural gas heat value and specific gravity in Table 14 or 15. e. Follow heat value and specific gravity lines to point of intersection to find orifice size and manifold pressure settings for proper operation. f. Check and verify burner orifice size in furnace. NEVER ASSUME ORIFICE SIZE. ALWAYS CHECK AND VERIFY. g. Replace orifice with correct size if required by Table 14 or 15. Use only factory--supplied orifices. See EXAMPLE 2. EXAMPLE 2:(0--2000 ft. (0--610 M) altitude) For 22,000 Btuh per burner application use Table 14. Heating value = 1000 Btuh/cu ft. Specific gravity = 0.62 Therefore: Orifice No. 43* Manifold pressure: 3.7--In. W.C. *Furnace is shipped with No. 43 orifices. In this example all main burner orifices are the correct size and do not need to be changed to obtain proper input rate. 3. Adjust manifold pressure to obtain correct input rate. a. Turn gas valve ON/OFF switch to OFF. b. Remove manifold pressure tap plug from gas valve. (See Fig. 42.) c. Connect a water column manometer or similar device to manifold pressure tap. d. Turn gas valve ON/OFF switch to ON. e. Manually close blower door switch. f. Set thermostat to call for heat. g. Jumper R and W thermostat connections on furnace control board to start furnace. h. Remove regulator seal cap and turn regulator adjusting screw counterclockwise (out) to decrease input rate of clockwise (in) to increase input rate. i. Install regulator seal cap. j. Leave manometer or similar device connected and proceed to Step 4. NOTE: DO NOT set manifold pressure less than 3.2--In. W.C. or more than 3.8--In. W.C. for natural gas at sea level. If manifold pressure is outside this range, change main burner orifices or refer Table 14 or 15. NOTE: If orifice hole appears damaged or it is suspected to have been redrilled, check orifice hole with a numbered drill bit of correct size. Never redrill an orifice. A burr--free and squarely aligned orifice hole is essential for proper flame characteristics. 4. Verify natural gas input rate by clocking meter. NOTE: Gas valve regulator adjustment cap must be in place for proper input to be clocked. a. Turn off all other gas appliances and pilots served by the meter. b. Run furnace for 3 minutes in heating operation. c. Measure time (in sec) for gas meter to complete 1 re- volution and note reading. The 2 or 5 cubic feet dial provides a more accurate measurement of gas flow. d. Refer to Table 12 for cubic ft. of gas per hr. e. Multiply gas rate (cu ft./hr) by heating value (Btu/cu ft.) to obtain input. If clocked rate does not match required input from Step 1, increase manifold pressure to increase input or decrease manifold pressure to decrease input. Repeat steps b through e until correct input is achieved. Reinstall regulator seal cap on gas valve. 5. Set temperature rise. The furnace must operate within the temperature rise ranges specified on the furnace rating plate. Do not exceed temperature rise range specified on unit rating plate. Determine the temperature rise as fol- lows: NOTE: Blower access door must be installed when taking temperature rise reading. Leaving blower access door off will result in incorrect temperature measurements. a. Place thermometers in return and supply ducts as close to furnace as possible. Be sure thermometers do not see radiant heat from heat exchangers. Radiant heat affects temperature rise readings. This practice is par- ticularly important with straight--run ducts.310AAV 34 b. When thermometer readings stabilize, subtract return-- air temperature from supply--air temperature to determ- ine air temperature rise. NOTE: Blower access door must be installed for proper temperature rise measurement. NOTE: If the temperature rise is outside this range, first check: S Gas input for heating operation. S Derate for altitude if applicable. S Return and supply ducts for excessive restrictions caus- ing static pressures greater than 0.50--In. W.C. S Dirty filter. ELECTRICAL SHOCK HAZARD Failure to follow this warning could result in personal injury or death. Disconnect 115--v electrical power and install lockout tag before changing speed tap. !WARNING c. Adjust air temperature rise by adjusting blower speed. Increase blower speed to reduce temperature rise. Decrease blower speed to increase temperature rise. d. Turn thermostat down below room temperature and remove blower access door. e. To change motor speed selection for heating, remove blower motor lead from control HEAT terminal (See Fig. 25.) Select desired blower motor speed lead from one of the other terminals and relocate it to the HEAT terminal (See Table 11 for lead color identification). Reconnect original lead to SPARE terminal. Table 11—Speed Selection COLOR SPEED AS SHIPPEDWhiteCommonBLWBlackHighCOOLYellow{Med --- High SPAREBlue*Med --- Low SPARERed*Low HEAT * 1/5 HP motor models: BLUE to HEAT, RED to SPARE {Not available on 1/5 HP motors. NOTE:Continuous blower is the HEAT speed. f. Repeat steps a through e. g. When correct input rate and temperature rise is achieved, turn gas valve ON/OFF switch to OFF. h. Remove manometer or similar device from gas valve. i. Reinstall manifold pressure tap plug in gas valve. FIRE HAZARD Failure to follow this warning could result in personal injury, death and/or property damage. Reinstall manifold pressure tap plug in gas valve to prevent gas leak. !WARNING j. Reinstall blower access door if removed. k. Turn gas valve ON/OFF switch to ON. FURNACE OVERHEATING HAZARD Failure to follow this caution may result in reduced furnace life. Recheck temperature rise. It must be within limits specified on the rating plate. Recommended operation is at the midpoint of rise range or slightly above. CAUTION! 6. Set thermostat heat anticipator. a. Mechanical thermostat -- Set thermostat heat anticipat- or to match the amp. draw of the electrical components in the R--W circuit. Accurate amp. draw readings can be obtained at the wires normally connected to ther- mostat subbase terminals, R and W. The thermostat anticipator should NOT be in the circuit while measur- ing current. (1.) Remove thermostat from subbase or from wall. (2.) Connect an amp. meter as shown in Fig. 44 across the R and W subbase terminals or R and W wires at wall. (3.) Record amp. draw across terminals when furnace is in heating and after blower starts. (4.) Set heat anticipator on thermostat per thermostat instructions and install on subbase or wall. b. Electronic thermostat: Set cycle rate for 4 cycles per hr. 7. Adjust blower off delay The blower off delay has 4 ad- justable settings from 90 sec to 180 sec. The blower off delay jumpers are located on the furnace control board. (See Fig. 25.) To change the blower off delay setting, move the jumper from one set of pins on the control to the pins used for the selected blower off delay. Factory off delay setting is 120 sec. 8. Set airflow CFM for cooling Select the desired blower motor speed lead for cooling airflow. See Table 4--Air De- livery--CFM (With Filter). See Table 11 for lead color identification.310AAV 35 A13111 Fig. 41 ---Wiring Diagram 310AAV 36 A06666 Fig. 42 ---Gas Control Valve BURNER ORIFICE A93059 Fig. 43 ---Orifice Hole R Y W G 10 TURNS THERMOSTAT SUBBASETERMINALS WITHTHERMOSTAT REMOVED (ANITICIPATOR, CLOCK, ETC.,MUST BE OUT OF CIRCUIT.) HOOK-AROUNDAMMETER EXAMPLE:5.0 AMPS ON AMMETER 10 TURNS AROUND JAWS = 0.5 AMPS FOR THERMOSTAT ANTICIPATOR SETTING FROM UNIT 24-VCONTROL TERMINALS A96316 Fig. 44 ---Amp. Draw Check With Ammeter310AAV 37 Step 4 —Check Safety Controls The flame sensor, gas valve, and pressure switch were all checked in the Start--up procedure section as part of normal operation. 1. Check Main Limit Switch(es) This control shuts off combustion control system and en- ergizes air--circulating blower motor, if furnace overheats. By using this method to check limit control, it can be es- tablished that limit is functioning properly and will operate if there is a restricted duct system or motor failure. If limit control does not function during this test, cause must be determined and corrected. a. Run furnace for at least 5 minutes. b. Gradually block off return air with a piece of card- board or sheet metal until the limit trips. c. Unblock return air to permit normal circulation. d. Burners will re--light when furnace cools down. 2. Check draft safeguard switch. The purpose of this control is to cause the safe shutdown of the furnace during certain blocked vent conditions. a. Verify vent pipe is cool to the touch. b. Disconnect power to furnace and remove vent con- nector from furnace vent elbow. c. Restore power to furnace and set room thermostat above room temperature. d. After normal start--up, allow furnace to operate for 2 minutes, then block vent elbow in furnace 80 percent of vent area with a piece of flat sheet metal. e. Furnace should cycle off within 2 minutes. If gas does not shut off within 2 minutes, determine reason draft safeguard switch did not function properly and correct condition. f. Remove blockage from furnace vent elbow. g. Switch will auto--reset when it cools. h. Re--install vent connector. NOTE: Should switch remain open longer than 3 minutes, furnace control board will lockout the furnace for 3 hrs. To reset furnace control board, turn thermostat below room temperature or from HEAT to OFF and turn 115v power OFF, then back ON. 3. Check Pressure Switch This control proves operation of the draft inducer blower. a. Turn off 115--v power to furnace. b. Disconnect inducer motor lead wires from wire har- ness. c. Turn on 115--v power to furnace. d. Set thermostat to “call for heat” and wait 1 minute. When pressure switch is functioning properly, hot sur- face igniter should NOT glow and control diagnostic light flashes a status code 32. If hot surface igniter glows when inducer motor is disconnected, shut down furnace immediately. e. Determine reason pressure switch did not function properly and correct condition. f. Turn off 115--v power to furnace. g. Reconnect inducer motor wires, replace outer door, andturnon115--vpower. h. Blower will run for 90 sec before beginning the call for heat again. i. Furnace should ignite normally. Step 5 —Checklist 1. Put away tools and instruments. Clean up debris. 2. Verify that blower OFF--DELAY time is selected as de- sired. 3. Verify that blower and burner access doors are properly in- stalled. 4. Cycle test furnace with room thermostat. 5. Check operation of accessories per manufacturer’s instruc- tions. 6. Review User’s Guide with owner. 7. Attach literature packet to furnace.310AAV 38 Table 12—Gas Rate (cu ft./hr) SECONDS FOR 1 REVOLUTION SIZE OF TEST DIAL SECONDS FOR 1 REVOLUTION SIZE OF TEST DIAL 1CuFt 2CuFt 5CuFt 1CuFt 2CuFt 5CuFt 10 360 720 1800 50 72 144 360 11 327 655 1636 51 71 141 355 12 300 600 1500 52 69 138 346 13 277 555 1385 53 68 136 340 14 257 514 1286 54 67 133 333 15 240 480 1200 55 65 131 327 16 225 450 1125 56 64 129 321 17 212 424 1059 57 63 126 316 18 200 400 1000 58 62 124 310 19 189 379 947 59 61 122 305 20 180 360 900 60 60 120 300 21 171 343 857 62 58 116 290 22 164 327 818 64 56 112 281 23 157 313 783 66 54 109 273 24 150 300 750 68 53 106 265 25 144 288 720 70 51 103 257 26 138 277 692 72 50 100 250 27 133 267 667 74 48 97 243 28 129 257 643 76 47 95 237 29 124 248 621 78 46 92 231 30 120 240 600 80 45 90 225 31 116 232 581 82 44 88 220 32 113 225 563 84 43 86 214 33 109 218 545 86 42 84 209 34 106 212 529 88 41 82 205 35 103 206 514 90 40 80 200 36 100 200 500 92 39 78 196 37 97 195 486 94 38 76 192 38 95 189 474 96 38 75 188 39 92 185 462 98 37 74 184 40 90 180 450 100 36 72 180 41 88 176 439 102 35 71 178 42 86 172 429 104 35 69 173 43 84 167 419 106 34 68 170 44 82 164 409 108 33 67 167 45 80 160 400 110 33 65 164 46 78 157 391 112 32 64 161 47 76 153 383 116 31 62 155 48 75 150 375 120 30 60 150 49 73 147 367 Table 13—Filter Size Information (In. / mm) FURNACE CASING WIDTH FILTER SIZE FILTER TYPESIDE RETURN BOTTOM RETURN 14---1/2 (368) 16 x25 x3/4 (406 x635 x19) 14 x25 x3/4 (356 x635 x19) Washable* 17---1/2 (445) 16 x25 x3/4 (406 x635 x19) 16 x25 x3/4 (406 x635 x19) Washable* 21 (533) 16 x25 x3/4 (406 x635 x19) 20 x25 x3/4 (508 x635 x19) Washable* 24 (610) 16 x25 x3/4 (406 x635 x19) 24 x25 x3/4 (610 x635 x19) Washable* * Recommended ** Some furnaces may have 2 filters.310AAV 39 Table 14—Orifice Size* and Manifold Pressure (In. W.C.) for Gas Input Rate (Tabulated data based on 22,000 btuh per burner, derated 4 percent for each 1000 ft. (305 M) above sea level) ALTITUDE RANGE FT. (M) AVG. GAS HEAT VALUE AT ALTITUDE (BTU/CU FT.) SPECIFIC GRAVITY OF NATURAL GAS 0.58 0.60 0.62 0.64 Orifice No. Manifold Pressure Orifice No. Manifold Pressure Orifice No. Manifold Pressure Orifice No. Manifold Pressure U.S.A. 0to 2000 (0 to 610) 900 42 3.5 42 3.6 42 3.7 41 3.5 925 42 3.3 42 3.4 42 3.5 42 3.7 950 43 3.8 42 3.3 42 3.4 42 3.5 975 43 3.6 43 3.8 42 3.2 42 3.3 1000 43 3.5 43 3.6 43 3.7 43 3.8 1025 43 3.3 43 3.4 43 3.5 43 3.6 1050 44 3.6 43 3.2 43 3.4 43 3.5 1075 44 3.4 44 3.5 43 3.2 43 3.3 1100 44 3.3 44 3.4 44 3.5 43 3.2 U.S.A. 2001 to 3000 (610 to 914) 800 42 3.4 42 3.5 42 3.6 42 3.7 825 42 3.2 42 3.3 42 3.4 42 3.5 850 43 3.7 43 3.8 42 3.2 42 3.3 875 43 3.5 43 3.6 43 3.7 43 3.8 900 43 3.3 43 3.4 43 3.5 43 3.6 925 43 3.1 43 3.2 43 3.3 43 3.4 950 43 2.9 43 3.0 43 3.1 43 3.2 975 43 2.8 43 2.9 43 3.0 43 3.1 1000 43 2.6 43 2.7 43 2.8 43 2.9 U.S.A. 3001 to 4000 (914 to 1219) 775 42 3.2 42 3.3 42 3.4 42 3.5 800 43 3.6 43 3.8 42 3.2 42 3.3 825 43 3.4 43 3.5 43 3.7 43 3.8 850 43 3.2 43 3.3 43 3.4 43 3.6 875 43 3.0 43 3.1 43 3.3 43 3.4 900 43 2.9 43 3.0 43 3.1 43 3.2 925 43 2.7 43 2.8 43 2.9 43 3.0 950 43 2.6 43 2.7 43 2.8 43 2.8 U.S.A. 4001 to 5000 (1219 to 1524) 750 43 3.6 43 3.8 42 3.2 42 3.3 775 43 3.4 43 3.5 43 3.6 43 3.8 800 43 3.2 43 3.3 43 3.4 43 3.5 825 43 3.0 43 3.1 43 3.2 43 3.3 850 43 2.8 43 2.9 43 3.0 43 3.1 875 43 2.7 43 2.8 43 2.9 43 2.9 900 43 2.5 43 2.6 43 2.7 43 2.8 925 43 2.4 43 2.5 43 2.6 43 2.6 * Orifice numbers 43 are factory installed.310AAV 40 Table 14–Orifice Size* and Manifold Pressure (In. W.C.) for Gas Input Rate (Continued) (Tabulated data based on 22,000 btuh per burner, derated 4 percent for each 1000 ft. (305 M) above sea level) ALTITUDE RANGE FT. (M) AVG. GAS HEAT VALUE AT ALTITUDE (BTU/CU FT.) SPECIFIC GRAVITY OF NATURAL GAS 0.58 0.60 0.62 0.64 Orifice No. Manifold Pressure Orifice No. Manifold Pressure Orifice No. Manifold Pressure Orifice No. Manifold Pressure U.S.A. 5001 to 6000 (1524 to 1829) 725 43 3.4 43 3.5 43 3.6 43 3.7 750 43 3.2 43 3.3 43 3.4 43 3.5 775 43 3.0 43 3.1 43 3.2 43 3.3 800 43 2.8 43 2.9 43 3.0 43 3.1 825 43 2.6 43 2.7 43 2.8 43 2.9 850 43 2.5 43 2.5 43 2.6 43 2.7 875 43 2.3 43 2.4 43 2.5 43 2.6 900 43 2.2 43 2.3 43 2.3 43 2.4 U.S.A. 6001 to 7000 (1829 to 2134) 675 43 3.4 43 3.5 43 3.6 43 3.7 700 43 3.1 43 3.3 43 3.4 43 3.5 725 43 2.9 43 3.0 43 3.1 43 3.2 750 43 2.7 43 2.8 43 2.9 43 3.0 775 43 2.6 43 2.7 43 2.7 43 2.8 800 43 2.4 43 2.5 43 2.6 43 2.7 825 43 2.3 43 2.3 43 2.4 43 2.5 850 43 2.1 43 2.2 43 2.3 43 2.4 U.S.A. 7001 to 8000 (2134 to 2438) 650 43 3.1 43 3.2 43 3.4 43 3.5 675 43 2.9 43 3.0 43 3.1 43 3.2 700 43 2.7 43 2.8 43 2.9 43 3.0 725 43 2.5 43 2.6 43 2.7 43 2.8 750 43 2.4 43 2.4 43 2.5 43 2.6 775 43 2.2 43 2.3 43 2.4 43 2.4 800 43 2.1 43 2.1 43 2.2 43 2.3 825 48 3.7 43 2.0 43 2.1 43 2.2 U.S.A. 8001 to 9000 (2438 to 2743) 625 43 2.9 43 3.0 43 3.1 43 3.2 650 43 2.7 43 2.8 43 2.9 43 3.0 675 43 2.5 43 2.6 43 2.7 43 2.8 700 43 2.3 43 2.4 43 2.5 43 2.6 725 43 2.2 43 2.2 43 2.3 43 2.4 750 43 2.0 43 2.1 43 2.2 43 2.2 U.S.A. 9001 to 10,000 (2743 to 3048) 600 43 2.7 43 2.8 43 2.9 43 3.0 625 43 2.5 43 2.6 43 2.6 43 2.7 650 43 2.3 43 2.4 43 2.4 43 2.5 675 43 2.1 43 2.2 43 2.3 43 2.3 700 48 3.7 43 2.0 43 2.1 43 2.2 725 48 3.5 48 3.6 48 3.7 43 2.0 775 48 3.6 48 3.7 43 2.0 43 2.1 * Orifice numbers 43 are factory installed.310AAV 41 Table 15—Orifice Size* and Manifold Pressure (In. W.C.) for Gas Input Rate (Tabulated data based on 21,000 btuh per burner, derated 4 percent for each 1000 ft. (305 M) above sea level) ALTITUDE RANGE FT. (M) SPECIFIC GRAVITY OF NATURAL GAS AVG. GAS HEAT VALUE AT ALTITUDE (BTU/CU FT.) 0.58 0.60 0.62 0.64 Orifice No. Manifold Pressure Orifice No. Manifold Pressure Orifice No. Manifold Pressure Orifice No. Manifold Pressure U.S.A.0 to 2000 (0 to 610) 900 42 3.2 42 3.3 42 3.4 42 3.5 925 43 3.7 43 3.8 42 3.2 42 3.3 950 43 3.5 43 3.6 43 3.7 43 3.8 975 43 3.3 43 3.4 43 3.5 43 3.7 1000 44 3.6 43 3.3 43 3.4 43 3.5 1025 44 3.4 44 3.6 43 3.2 43 3.3 1050 44 3.3 44 3.4 44 3.5 43 3.2 1075 45 3.8 44 3.2 44 3.3 44 3.4 1100 46 3.8 45 3.7 44 3.2 44 3.3 U.S.A. 2001 to 3000 (610 to 914) 800 43 3.8 42 3.2 42 3.3 42 3.4 825 43 3.5 43 3.7 43 3.8 42 3.2 850 43 3.3 43 3.5 43 3.6 43 3.7 875 43 3.2 43 3.3 43 3.4 43 3.5 900 43 3.0 43 3.1 43 3.2 43 3.3 925 43 2.8 43 2.9 43 3.0 43 3.1 950 43 2.7 43 2.8 43 2.9 43 2.9 975 43 2.5 43 2.6 43 2.7 43 2.8 1000 43 2.4 43 2.5 43 2.6 43 2.7 U.S.A. 3001 to 4000 (914 to 1219) 775 43 3.5 43 3.7 43 3.8 42 3.2 800 43 3.3 43 3.4 43 3.5 43 3.7 825 43 3.1 43 3.2 43 3.3 43 3.4 850 43 2.9 43 3.0 43 3.1 43 3.2 875 43 2.8 43 2.9 43 3.0 43 3.1 900 43 2.6 43 2.7 43 2.8 43 2.9 925 43 2.5 43 2.6 43 2.7 43 2.7 950 43 2.4 43 2.4 43 2.5 43 2.6 U.S.A. 4001 to 5000 (1219 to 1524) 750 43 3.3 43 3.4 43 3.5 43 3.6 775 43 3.1 43 3.2 43 3.3 43 3.4 800 43 2.9 43 3.0 43 3.1 43 3.2 825 43 2.7 43 2.8 43 2.9 43 3.0 850 43 2.6 43 2.7 43 2.8 43 2.8 875 43 2.4 43 2.5 43 2.6 43 2.7 900 43 2.3 43 2.4 43 2.5 43 2.5 925 43 2.2 43 2.2 43 2.3 43 2.4 * Orifice numbers 43 are factory installed.310AAV 42 Table 15—Orifice Size* and Manifold Pressure (In. W.C.) for Gas Input Rate (Continued) (Tabulated data based on 21,000 btuh per burner, derated 4 percent for each 1000 ft. (305 M) above sea level) ALTITUDE RANGE FT. (M) AVG. GAS HEAT VALUE AT ALTITUDE (BTU/CU FT.) SPECIFIC GRAVITY OF NATURAL GAS 0.58 0.60 0.62 0.64 Orifice No. Manifold Pressure Orifice No. Manifold Pressure Orifice No. Manifold Pressure Orifice No. Manifold Pressure U.S.A. 5001 to 6000 (1524 to 1829) 725 43 3.1 43 3.2 43 3.3 43 3.4 750 43 2.9 43 3.0 43 3.1 43 3.2 775 43 2.7 43 2.8 43 2.9 43 3.0 800 43 2.5 43 2.6 43 2.7 43 2.8 825 43 2.4 43 2.5 43 2.5 43 2.6 850 43 2.2 43 2.3 43 2.4 43 2.5 875 43 2.1 43 2.2 43 2.3 43 2.3 900 43 2.0 43 2.1 43 2.1 43 2.2 U.S.A. 6001 to 7000 (1829 to 2134) 675 43 3.1 43 3.2 43 3.3 43 3.4 700 43 2.9 43 3.0 43 3.1 43 3.2 725 43 2.7 43 2.8 43 2.9 43 2.9 750 43 2.5 43 2.6 43 2.7 43 2.8 775 43 2.3 43 2.4 43 2.5 43 2.6 800 43 2.2 43 2.3 43 2.3 43 2.4 825 43 2.1 43 2.1 43 2.2 43 2.3 850 48 3.7 43 2.0 43 2.1 43 2.1 U.S.A. 7001 to 8000 (2134 to 2438) 650 43 2.9 43 3.0 43 3.1 43 3.2 675 43 2.7 43 2.7 43 2.8 43 2.9 700 43 2.5 43 2.6 43 2.6 43 2.7 725 43 2.3 43 2.4 43 2.5 43 2.5 750 43 2.1 43 2.2 43 2.3 43 2.4 775 43 2.0 43 2.1 43 2.2 43 2.2 800 48 3.6 48 3.7 43 2.0 43 2.1 825 48 3.3 48 3.5 48 3.6 48 3.7 U.S.A. 8001 to 9000 (2438 to 2743) 625 43 2.7 43 2.7 43 2.8 43 2.9 650 43 2.5 43 2.5 43 2.6 43 2.7 675 43 2.3 43 2.4 43 2.4 43 2.5 700 43 2.1 43 2.2 43 2.3 43 2.3 725 48 3.7 43 2.0 43 2.1 43 2.2 750 48 3.5 48 3.6 48 3.7 43 2.0 U.S.A. 9001 to 10,000 (2743 to 3048) 600 43 2.4 43 2.5 43 2.6 43 2.7 625 43 2.3 43 2.3 43 2.4 43 2.5 650 43 2.1 43 2.2 43 2.2 43 2.3 675 48 3.6 48 3.8 43 2.1 43 2.1 700 48 3.4 48 3.5 48 3.6 48 3.7 725 49 3.7 49 3.8 48 3.4 48 3.5 775 49 3.8 48 3.4 48 3.5 48 3.6 * Orifice numbers 43 are factory installed.310AAV 43 To initiate the component test sequence, shut OFF the room thermostat or disconnect the "R" thermostat lead. Briefly short the TEST/TWIN terminal to the "Com 24V" terminal. Status LED will flash code and then turn ON the inducer motor. The inducer motor will run for the entire component test. The hot surface ignitor, blower motor fan speed (on AMBER LED boards only) blower motor-heat speed, and blower motor-cool speed will be turned ON for 10-15 seconds each. Gas Valve and Humidifier will not be turned on. CONTINUOUS OFF - Check for 115VAC at L1 and L2, and 24VAC at SEC-1 and SEC-2. CONTINUOUS ON - Control has 24VAC power. RAPID FLASHING - Line voltage (115VAC) polarity reversed. If twinned, refer to twinning kit instructions. LED CODE STATUS 11 NO PREVIOUS CODE - Stored status code is erased automatically after 72 hours. On RED LED boards stored status codes can also be erased when power (115 VAC or 24 VAC) to control is interrupted. 12 BLOWER ON AFTER POWER UP (115 VAC or 24 VAC) -Blower runs for 90 seconds, if unit is powered up during a call for heat (R-W closed) or R-W opens during blower on-delay. 13 LIMIT CIRCUIT LOCKOUT - Lockout occurs if the limit, draft safeguard, flame rollout, or blocked vent switch (if used) is open longer than 3 minutes. - Control will auto reset after three hours. - Refer to #33. 14 IGNITION LOCKOUT -Control will auto-reset after three hours. Refer to #34. 21 GAS HEATING LOCKOUT - Control will NOT auto reset. Check for: - Mis-wired gas valve -Defective control (valve relay) 22 ABNORMAL FLAME-PROVING SIGNAL - Flame is proved while gas valve is de- energized. Inducer will run until fault is cleared. Check for: - Leaky gas valve - Stuck-open gas valve 23 PRESSURE SWITCH DID NOT OPEN Check for: - Obstructed pressure tubing. - Pressure switch stuck closed. 24 SECONDARY VOLTAGE FUSE IS OPEN Check for: - Short circuit in secondary voltage (24VAC) wiring. If status code recall is needed, briefly remove then reconnect one main limit wire to display stored status code. On RED LED boards do not remove power or blower door before initiating status code recall. After status code recall is completed component test will occur. 327596-101 REV. B 31 PRESSURE SWITCH DID NOT CLOSE OR REOPENED - If open longer than five minutes, inducer shuts off for 15 minutes before retry. Check for: - Excessive wind - Proper vent sizing - Defective inducer motor - Low inducer voltage (115VAC) - Defective pressure switch - Inadequate combustion air supply - Disconnected or obstructed pressure tubing - Low inlet gas pressure (if LGPS used) - Restricted vent If it opens during blower on-delay period, blower will come on for the selected blower off-delay. 33 LIMIT CIRCUIT FAULT -Indicates a limit, draft safeguard, flame rollout, or blocked vent switch (if used) is open. Blower will run for 4 minutes or until open switch remakes whichever is longer. If open longer than 3 minutes, code changes to lockout #13. If open less than 3 minutes status code #33 continues to flash until blower shuts off. Flame rollout switch and BVSS require manual reset. Check for: - Restricted vent - Proper vent sizing - Loose blower wheel. - Excessive wind - Dirty filter or restricted duct system. - Defective blower motor or capacitor. - Defective switch or connections. - Inadequate combustion air supply (Flame Roll-out Switch open). 34 IGNITION PROVING FAILURE - Control will try three more times before lockout #14 occurs. If flame signal lost during blower on-delay period, blower will come on for the selected blower off-delay. Check for: - Flame sensor must not be grounded - Oxide buildup on flame sensor (clean with fine steel wool). - Proper flame sense microamps (.5 microamps D.C. min., 4.0 - 6.0 nominal). - Gas valve defective or gas valve turned off - Manual valve shut-off - Defective Hot Surface Ignitor - Control ground continuity - Low inlet gas pressure - Inadequate flame carryover or rough ignition - Green/Yellow wire MUST be connected to furnace sheet metal 45 CONTROL CIRCUITRY LOCKOUT Auto-reset after one hour lockout due to; - Gas valve relay stuck open - Flame sense circuit failure - Software check error Reset power to clear lockout. Replace control if status code repeats. SERVICE COMPONENT TEST EACH OF THE FOLLOWING STATUS CODES IS A TWO DIGIT NUMBER WITH THE FIRST DIGIT DETERMINED BY THE NUMBER OF SHORT FLASHES AND THE SECOND DIGIT BY THE NUMBER OF LONG FLASHES. A04223 Fig. 45 ---Service Label SERVICE AND MAINTENANCE PROCEDURES FIRE, EXPLOSION, ELECTRICAL SHOCK HAZARD Failure to follow this warning could result in personal injury, death and/or property damage. The ability to properly perform maintenance on this equipment requires certain knowledge, mechanical skills, tools, and equipment. If you do not possess these, do not attempt to perform any maintenance on this equipment other than those procedures recommended in the User’s Manual. !WARNING ELECTRICAL SHOCK, FIRE OR EXPLOSION HAZARD Failure to follow this warning could result in personal injury or death, or property damage. Before servicing, disconnect all electrical power and install lockout tag to furnace. Verify proper operation after servicing. !WARNING ELECTRICAL OPERATION HAZARD Failure to follow this caution may result in improper furnace operation. Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous operation. CAUTION! ENVIRONMENTAL HAZARD Failure to follow this caution may result in environmental pollution. Remove and recycle all components or materials (i.e. oil, refrigerant, et.) before unit final disposal. CAUTION! Step 1 —Introduction GENERAL These instructions are written as if the furnace is installed in an upflow application. An upflow furnace application is where the blower is located below the combustion and controls section of the furnace, and conditioned air is discharged upward. Since this furnace can be installed in any of the 4 positions shown in Fig. 4, you must revise your orientation to component location accordingly. ELECTRICAL CONTROLS AND WIRING ELECTRICAL SHOCK HAZARD Failure to follow this warning could result in personal injury or death. Before installing, modifying, or servicing system, main electrical disconnect switch must be in the OFF position and install a lockout tag. There may be more than one electrical supply to the furnace. Check accessories and cooling unit for additional electrical supplies that must be shut off during furnace servicing. Lockout and tag switch with a suitable warning label. Verify proper operation after servicing. !WARNING The electrical ground and polarity for 115--v wiring must be properly maintained. Refer to Fig. 26 for field wiring information and to Fig. 41 for furnace wiring information. NOTE: If the polarity is not correct, the STATUS LED on the control will flash rapidly and prevent the furnace from heating.310AAV 44 The control system also requires an earth ground for proper operation of the control and flame--sensing electrode. The 24--v circuit contains an automotive--type, 3--amp. fuse located on the control. (See Fig. 25.) Any shorts of the 24--v wiring during installation, service, or maintenance will cause this fuse to blow. If fuse replacement is required, use ONLY a 3--amp. fuse. The control LED will display status code 24 when fuse needs to be replaced. Proper instrumentation is required to service electrical controls. The control in this furnace is equipped with a Status Code LED (Light--Emitting Diode) to aid in installation, servicing, and troubleshooting. It can be viewed through the sight glass in blower access door. The furnace control LED is either ON continuously, rapid flashing, or a code composed of 2 digits. The first digit is the number of short flashes, the second digit is the number of long flashes. For an explanation of status codes, refer to service label located on blower access door or Fig. 45 and the troubleshooting guide which can be obtained from your distributor. The furnace control will store 1 status code for 72 hrs. See Fig. 49, a brief Troubleshooting Guide. 1. To retrieve status code, proceed with the following: NOTE: NO thermostat signal may be present at control, and all blower--OFF delays must be completed. a. Leave 115--v power to furnace turned on. b. Remove outer access door. c. Look into blower access door sight glass for current LED status. d. BRIEFLY remove insulated terminal wire from the draft safeguard (DSS) switch until LED goes out (1 to 2 sec), then reconnect it. 2. When above items have been completed, the LED flashes status code 4 times. Record this status code for further troubleshooting. 3. Component self--test will begin. Refer to component TEST section for complete test sequence. 4. Check LED status. 5. Refer to SERVICE label on front of the blower access door for more information. 6. Check LED status. If no previous faults in history, control will flash status code 11. 7. If LED status indicates proper operation, RELEASE BLOWER ACCESS DOOR SWITCH, reattach wire to R terminal on furnace control board, replace blower access door, and replace burner access door. Step 2 —Care and Maintenance FIRE OR EXPLOSION HAZARD Failure to follow this warning could result in personal injury, death and/or property damage. Never store anything on, near, or in contact with the furnace, such as: 1. Spray or aerosol cans, rags, brooms, dust mops, vacuum cleaners, or other cleaning tools. 2. Soap powders, bleaches, waxes or other cleaning compounds, plastic or plastic containers, gasoline, kerosene, cigarette lighter fluid, dry cleaning fluids, or other volatile fluids. 3. Paint thinners and other painting compounds, paper bags, or other paper products. !WARNING For continuing high performance and to minimize possible equipment failure, periodic maintenance must be performed on this equipment. Consult your local dealer about proper frequency of maintenance and the availability of a maintenance contract. ELECTRICAL SHOCK AND FIRE HAZARD Failure to follow this warning could result in personal injury, death or property damage. Turn off the gas and electrical supplies to the unit and install lockout tag before performing any maintenance or service. Follow the operating instructions on the label attached to the furnace. !WARNING CARBON MONOXIDE POISONING AND FIRE HAZARD Failure to follow this warning could result in personal injury, death and/or property damage. Never operate unit without a filter or with filter access door removed. !WARNING CUT HAZARD Failure to follow this caution may result in personal injury. Sheet metal parts may have sharp edges or burrs. Use care and wear appropriate protective clothing, safety glasses and gloves when handling parts and servicing furnaces. CAUTION! The minimum maintenance on this furnace is as follows: 1. Check and clean air filter each month or more frequently if required. Replace if torn. 2. Check blower motor and wheel for cleanliness each heating and cooling season. Clean as necessary. 3. Check electrical connections for tightness and controls for proper operation each heating season. Service as necessary. 4. Inspect burner compartment before each heating season for rust, corrosion, soot or excessive dust. If necessary, have furnace and burner serviced by a qualified service agency. 5. Inspect the vent pipe/vent system before each heating season for rust, corrosion, water leakage, sagging pipes or broken fittings. Have vent pipes/vent system serviced by a qualified service agency. 6. Inspect any accessories attached to the furnace such as a humidifier or electronic air cleaner. Perform any service or maintenance to the accessories as recommended in the accessory instructions. CLEANING AND/OR REPLACING AIR FILTER The air filter arrangement will vary depending on the application. The filter is exterior to the furnace casing. NOTE: If the filter has an airflow direction arrow, the arrow must point towards the blower.310AAV 45 CUT HAZARD Failure to follow this caution may result in personal injury. Sheet metal parts may have sharp edges or burrs. Use care and wear appropriate protective clothing, safety glasses and gloves when handling parts and servicing furnaces. CAUTION! Media cabinet filter procedures: NOTE: Media cabinet or 3/4--in. (19 mm) filter rack are accessories and are not included from the factory. 1. Turn off electrical supply to furnace before removing filter access door. 2. Remove filter cabinet door. 3. Slide filter out of cabinet. 4. If equipped with permanent, washable 3/4--in. (19 mm) filter, clean filter by spraying cold tap water through filter in opposite direction of airflow. Rinse filter and let dry. Oiling or coating of the filter is not recommended. See Table 13 for size information. 5. If equipped with factory--specified disposable media filter, replace only with media filter having the same part number and size. For expandable replacement media, refer to the instructions included with the replacement media. 6. Slide filter into cabinet. 7. Replace filter cabinet door. 8. Turn on electrical supply to furnace. BLOWER MOTOR AND WHEEL ELECTRICAL SHOCK HAZARD Failure to follow this warning could result in personal injury or death. Blower access door switch opens 115--v power to control. No component operation can occur unless switch is closed. Caution must be taken when manually closing this switch for service purposes. !WARNING NOTE: The blower wheel should not be dropped or bent as balance will be affected. The following steps should be performed by a qualified service agency. To ensure long life and high efficiency, clean accumulated dirt and grease from blower wheel and motor annually. The inducer and blower motors are pre--lubricated and require no additional lubrication. These motors can be identified by the absence of oil ports on each end of the motor. Clean blower motor and wheel as follows: 1. Turn off electrical supply to furnace. 2. Remove outer door. 3. For downflow or horizontal furnaces having vent pipes within the furnace that pass in front of the blower access door: a. Disconnect vent connector from furnace vent elbow. b. Disconnect and remove short piece of vent pipe from within furnace. 4. Remove 2 screws from blower access door and remove blower access door. 5. All factory wires can be left connected, but field thermo- stat connections may need to be disconnected depending on their length and routing. 6. Remove 2 screws holding blower assembly to blower deck and slide blower assembly out of furnace. 7. Clean blower wheel and motor using a vacuum with soft brush attachment. Blower wheel blades may be cleaned with a small paint or flux brush. Do not remove or disturb balance weights (clips) on blower wheel blades. 8. Vacuum any loose dust from blower housing, wheel and motor. 9. If a greasy residue is present on blower wheel, remove wheel from the blower housing and wash it with an appro- priate degreaser. To remove wheel: NOTE: Before disassembly, mark blower motor, and blower housing so motor and each arm is positioned at the same location during reassembly. a. Disconnect capacitor wires and ground wire attached to blower housing. b. Remove screws securing cutoff plate and remove cutoff plate from housing. c. Loosen set screw holding blower wheel on motor shaft (160+/--20 in.--lb. when reassembling). d. Remove bolts holding motor to blower housing and slide motor out of wheel (40+/--10 in.--lb. when reas- sembling). e. Remove blower wheel from housing. f. Clean wheel and housing. 10. Reassemble motor and blower by reversing steps 9f through 9a, finishing with 9a. Be sure to reattach ground wire to the blower housing. 11. Verify that blower wheel is centered in blower housing and set screw contacts the flat portion of the motor shaft. Loosen set screw on blower wheel and reposition if neces- sary. 12. Spin the blower wheel by hand to verify that the wheel does not rub on the housing. 13. Reinstall blower assembly in furnace. UNIT DAMAGE HAZARD Failure to follow this caution may result in shortened heat exchanger life. Heating fan speed(s) MUST be adjusted to provide proper air temperature rise as specified on the rating plate. Recommended operation is at the midpoint of the rise range or slightly above. Refer to SET TEMPERATURE RISE under START--UP, ADJUSTMENT, and SAFETY CHECK. CAUTION! 14. Connect thermostat leads if previously disconnected. 15. To check blower for proper rotation: a. Turn on electrical supply. ELECTRICAL SHOCK HAZARD Failure to follow this warning could result in personal injury, or death. Blower access door switch opens 115--v power to furnace control. No component operation can occur unless switch is closed. Exercise caution to avoid electrical shock from exposed electrical components when manually closing this switch for service purposes. !WARNING b. Manually close blower access door switch.310AAV 46 NOTE: If thermostat terminals are jumpered at the time blower access door switch is closed, blower will run for 90 sec before beginning a heating or cooling cycle. c. Perform component self--test as shown at the bottom of the SERVICE label, located on the front of blower access door. d. Verify blower is rotating in the correct direction 16. If furnace is operating properly, RELEASE BLOWER ACCESS DOOR SWITCH. Remove any jumpers or re- connect any disconnected thermostat leads. Replace blower access door. 17. Downflow or horizontal furnaces with vent pipe through furnace only: a. Install and connect short piece of vent pipe inside fur- nace to existing vent. b. Connect vent connector to vent elbow. 18. Reinstall casing door. 19. Turn on gas supply and cycle furnace through one com- plete heating and cooling cycle. Verify the furnace temper- ature rise as shown in Adjustments Section. Adjust tem- perature rise as shown in Adjustments Section. If outdoor temperature is below 70_F, (21 _C) turn off circuit breaker to outdoor unit before running furnace in the cooling cycle. Turn outdoor circuit breaker on after completing cooling cycle. CLEANING HEAT EXCHANGER The following steps should be performed by a qualified service agency: NOTE: If the heat exchangers get a heavy accumulation of soot and carbon, they should be replaced rather than trying to clean them thoroughly. A heavy build--up of soot and carbon indicates that a problem exists which needs to be corrected, such as improper adjustment of manifold pressure, insufficient or poor quality combustion air, incorrect size or damaged manifold orifice( s), improper gas, or a restricted heat exchanger. Action must be taken to correct the problem. If it becomes necessary to clean the heat exchangers because of dust or corrosion, proceed as follows: 1. Turn OFF gas and electrical power to furnace. 2. Remove outer access door. 3. Disconnect vent connector from furnace vent elbow. 4. For downflow or horizontal furnace having an internal vent pipe, remove internal vent pipe within the casing. 5. Disconnect wires to the following components. Mark wires to aid in reconnection of (be careful when discon- necting wires from switches because damage may occur): a. Draft safeguard switch. b. Inducer motor. c. Pressure switch(es). d. Limit overtemperature switch. e. Gas valve. f. Hot surface igniter. g. Flame--sensing electrode. h. Flame rollout switches. i. Remove NOx baffles on low NOx models. 6. Remove screws that fasten the collector box assembly to the cell panel. Be careful not to damage the collector box. Inducer assembly and elbow need not be removed from collector box. 7. Disconnect gas line from gas manifold. 8. Remove the 5 screws that attach the burner assembly to the cell panel. The gas valve and individual burners need not be removed from support assembly. NOTE: Be very careful when removing burner assembly to avoid breaking igniter. See Fig. 46 and 47 for correct igniter location. 9. Using field--provided 25--caliber rifle cleaning brush, 36--in. (914 mm) long, 1/4 in. (6 mm) diameter steel spring cable, a variable speed, reversible electric drill, and vacuum cleaner, clean cells as follows: a. Remove metal screw fitting from wire brush to allow insertion into cable. b. Insert the twisted wire end of brush into end of spring cable, and crimp tight with crimping tool or crimp by striking with ball--peen hammer. TIGHTNESS IS VERY IMPORTANT. NOTE: The materials needed in item 9 can usually be purchased at local hardware stores. (1) Attach variable--speed, reversible drill to the end of spring cable (end opposite brush). (2) Insert brush end of cable into the outlet opening of cell and slowly rotate with drill. DO NOT force cable. Gradually insert cable into upper pass of cell. (See Fig. 48.) (3) Work cable in and out of cell 3 or 4 times to obtain sufficient cleaning. DO NOT pull cable with great force. Reverse drill and gradually work cable out. A05025 Fig. 46 ---Igniter Position--Side View310AAV 47 1-7/8 (47.6 mm) A05026 Fig. 47 ---Igniter Position--Top View A01050 Fig. 48 ---Cleaning Heat Exchanger Cell (4) Insert brush end of cable in burner inlet opening of cell, and proceed to clean 2 lower passes of cell in same manner as upper pass. (5) Repeat foregoing procedures until each cell in furnace has been cleaned. (6) Using vacuum cleaner, remove residue from each cell. (7) Using vacuum cleaner with soft brush attachment, clean burner assembly. (8) Clean flame sensor with fine steel wool. (9) Install NOx baffles (if removed). (10) Reinstall burner assembly. Center burners in cell openings. 10. Remove old sealant from cell panel and collector box flange. 11. Spray releasing agent on the heat exchanger cell panel where collector box assembly contacts cell panel. NOTE: A releasing agent such as cooking spray or equivalent (must not contain corn or canola oil, aromatic or halogenated hydrocarbons or inadequate seal may occur) and RTV sealant (G.E. 162, 6702, or Dow--Corning 738) are needed before starting installation. DO NOT substitute any other type of RTV sealant. G.E. 162 (P771--9003) is available through RCD in 3--oz tubes. 12. Apply new sealant to flange of collector box and attach to cell panel using existing screws, making sure all screws are secure. 13. Reconnect wires to the following components. (Use con- nection diagram on wiring label, if wires were not marked for reconnection locations.): a. Draft safeguard switch. b. Inducer motor. c. Pressure switch(es). d. Limit over--temperature switch. e. Gas valve. f. Hot surface igniter. g. Flame--sensing electrode. h. Flame rollout switches. i. Install NOx baffles (if removed). 14. Reinstall internal vent pipe, if applicable. 15. Reinstall vent connector on furnace vent elbow. Securely fasten vent connector to vent elbow with 2 field--supplied, corrosion--resistant, sheet metal screws located 180_apart. 16. Replace blower access door only, if it was removed. 17. Set thermostat above room temperature and check furnace for proper operation. 18. Verify blower airflow and speed changes between heating and cooling. FIRE OR EXPLOSION HAZARD Failure to follow this warning could result in personal injury, death and/or property damage. Never test for gas leaks with an open flame. Use a commercially available soap solution made specifically for the detection of leaks to check all connections. A fire or explosion may result causing property damage, personal injury or loss of life. !WARNING 19. Check for gas leaks. 20. Replace outer access door. Step 3 —Sequence of Operation NOTE: Furnace control must be grounded for proper operation or control will lock out. Control is grounded through green/yellow wire routed to gas valve and manifold bracket screw. Using the schematic diagram in Fig. 41, follow the sequence of operation through the different modes. Read and follow the wiring diagram very carefully. NOTE: If a power interruption occurs during a call for heat (W), the control will start a 90--sec blower--only ON period two seconds after power is restored, if the thermostat is still calling for gas heating. The amber LED light will flash code 12 during the 90--sec period, after which the LED will be ON continuous, as long as no faults are detected. After the 90--sec period, the furnace will respond to the thermostat normally. The blower door must be installed for power to be conducted through the blower door interlock switch ILK to the furnace control CPU, transformer TRAN, inducer motor IDM, blower motor BLWM, hot--surface igniter HSI, and gas valve GV. 1.Heating (See Fig. 26 for thermostat connections.) The wall thermo- stat “calls for heat,” closing the R--to--W circuit. The fur- nace control performs a self--check, verifies the pressure switch contacts PRS are open, and starts the inducer motor IDM. a.Inducer Prepurge Period -- As the inducer motor IDM comes up to speed, the pressure switch contacts PRS close, 24 VAC power is supplied for a field in- stalled humidifier at the HUM terminal and the control begins a 15--sec prepurge period. b.Igniter Warm--Up -- At the end of the prepurge period, the Hot--Surface igniter HSI is energized for a 17--second igniter warm--up period. c.Trial--for--Ignition Sequence-- When the igniter warm--up period is completed, the main gas valve re- lay contacts GVR close to energize the gas valve GV, the gas valve opens, The gas valve GV permits gas flow to the burners where it is ignited by the HSI. Five seconds after the GVR closes, a 2--second flame prov- ing period begins. The HSI igniter will remain ener-310AAV 48 gized until the flame is sensed or until the 2--second flame proving period begins. d.Flame--Proving -- When the burner flame is proved at the flame--proving sensor electrode FSE, the furnace control CPU begins the blower--ON delay period and continues to hold the gas valve GV open. If the burner flame is not proved within two seconds, the control CPU will close the gas valve GV, and the control CPU will repeat the ignition sequence for up to three more Trials--For--Ignition before going to Ignition--Lockout. Lockout will be reset automatically after three hours or by momentarily interrupting 115 vac power to the furnace, or by interrupting 24 vac power at SEC1 or SEC2 to the furnace control CPU (not at W, G, R, etc.) If flame is proved when flame should not be present, the furnace control CPU will lock out of Gas--Heating mode and operate the inducer motor IDM until flame is no longer proved. e.Blower--On Delay -- If the burner flame is proven, the blower motor is energized on HEAT speed 25 sec after the gas valve GV is energized. Simultaneously, the electronic air cleaner terminal EAC--1 is energized and remains energized as long as the blower motor BLWM is energized. f.Blower--Off Delay -- When the thermostat is satisfied, the R--to--W circuit is opened, de--energizing the gas valve GV, stopping gas flow to the burners, and de-- energizing the humidifier terminal HUM. The inducer motor IDM will remain energized for a 5--second post--purge period. The blower motor BLWM and air cleaner terminal EAC--1 will remain energized for 90, 120, 150, or 180 seconds (depending on the blower-- OFF delay selection). The furnace control CPU is fact- ory--set for a 120--second blower--OFF delay. 2.Cooling Mode (See Fig. 26 for thermostat connections.) The thermostat closes the R--to--G--and--Y circuits. The R--to--Y circuit starts the outdoor unit, and the R--to--G and Y circuits start the furnace blower motor BLWM on COOL speed. The electronic air cleaner terminal EAC--1 is energized with 115 vac when the blower motor BLWM is operating. When the thermostat is satisfied, the R--to--G--and--Y cir- cuits are opened. The outdoor unit will stop, and the fur- nace blower motor BLWM will continue operating on the COOL speed for an additional 90 sec. Cut jumper J2 to reduce the cooling off--delay to 5 sec. (See Fig. 25.) 3.Continuous Blower Mode When the R--to--G circuit is closed by the thermostat, the blower motor BLWM will operate on continuous--blower speed (same as HEAT speed). Terminal EAC--1 is ener- gized as long as the blower motor BLWM is energized. During a call for heat, the blower BLWM will stop during igniter warm--up (17 sec), ignition, and blower--ON delay (25 sec), allowing the furnace heat exchangers to heat up more quickly, then restarts at the end of the blower--ON delay period at HEAT speed. When the thermostat “calls for cooling”, the blower motor BLWM will operate at COOL speed. When the thermostat is satisfied, the blower motor BLWM will operate an addi- tional 90 sec, on COOL speed before reverting back to continuous blower speed. When the R--to--G circuit is opened, the blower motor BLWM will continue operating for an additional 5 sec, if no other function requires blower motor BLWM opera- tion. 4.Heat Pump When installed with a heat pump, the furnace control auto- matically changes the timing sequence to avoid long blower off times during demand defrost cycles. When the R--to--Wand-- Y or R--to--W--and--Y--and--G circuits are energized the furnace control CPU will continue to turn on the blower motor BLWM at HEAT speed, and begin a heating cycle. The blower motor BLWM will remain on until the end of the prepurge period, then shut off for 24 sec then come back on at HEAT speed. When the W input signal disappears, the furnace control begins a normal in- ducer post--purge period and the blower switches to COOL speed after a 3 sec delay. If the R--to--W--and-- Y--and--G signals disappear at the same time, the blower motor BLWM will remain on for the selected blower-- OFF delay period. If the R--to--W--and--Y signals disap- pear, leaving the G signal, the blower motor BLWM will continue running the blower motor at HEAT speed after the selected blower--OFF delay period is completed. Step 4 —Wiring Diagrams Refer to Fig. 25 and 41 for wiring diagrams. Step 5 —Troubleshooting Refer to the service label. (See Fig. 45–Service Label.) The Troubleshooting Guide can be a useful tool in isolating furnace operation problems. Beginning with the word Start, answer each question and follow the appropriate arrow to the next item. The Guide will help to identify the problem or failed component. After replacing any component, verify correct operation sequence.310AAV 49Is LED status light on?Is LED status light blinking rapidly without apause?Is LED status light blinking ON/OFF slowlywith a combination of short and long flashes?Determine status code. The status code is a2 digit number with the first digit determinedby the number of short flashes and the seconddigit by the number of long flashes?Go to section below for the status code thatwas flashed.Is there 115V at L1 and L2?Is there 24V at SEC-1 and SEC-2?Replace furnace control.Check for correct line voltage polarity. If unitsare twinned, check for proper low-voltage(24V) transformer phasing.To recall status code briefly remove and reconnect one RED wire from the draftsafeguard switch to display stored status code. On RED LED control do notremove power or blower access panel before initiating status code recall. Youcan also recall the previous status code by momentarily shorting the TEST/TWINterminal to Com24V terminal until the LED goes out. LED will flash the statuscode of the previous fault or status code #11 (1 short and 1 long flash) if therewas no previous fault. After the control repeats the code 4 times, the controlwill go through a brief component test sequence. The inducer will start and runfor the entire component test. The HSI, blower motor FAN speed (AMBER LEDboards only) HEAT speed, and COOL speed will run for 10 – 15 seconds each. Gas valve and humidifier will not be turned on.Was there a previous status codeother than #11?Is door switch closed?Is there 115V going to switch?Replace door switch.Replace transformer.Does the control respond to W, Y1 (if present),Y/Y2, and G (24V) thermostat signals?Run system through a heating or cooling cycleto check operation. Status codes are erasedafter 72 hours. On RED LED boards storedstatus codes can also be erased whenever(115V or 24V) is interrupted.Replace furnace control.Is door switch closed?Is circuit breaker closed?Check for continuity in wire from circuit breakerto furnace.Close circuit breaker and go back to START.Check room thermostat orinterconnecting cable.Is 24V present at W, Y1 (if present), Y/Y2 orG thermostat terminals on the furnace control?Disconnect all the thermostat wires from thefurnace control.Does the problem repeat when usinga jumper wire?The thermostat is not compatible with thefurnace control. Either install a ballast resistor,connect the Com24V thermostat terminal tothe thermostat, or replace the thermostat.NOYESYESNONOYESYESYESYESNOYESYESNOYESNOYESNONONOYESNOYESNOSTARTNOA02106aFig. 49 ---Troubleshooting Guide 310AAV 5011 NO PREVIOUS CODE – Stored codesare erased after 72 hours. On RED LEDboards stored status codes can also beerased whenever power (115V or 24V)is interrupted. Run system through aheating or cooling cycle to check system.12 BLOWER ON AFTER POWER UP –(115V OR 24V) – Normal operation.Blower runs for 90 seconds, if unit ispowered up during a call for heat (R-Wclosed) or when (R-W opens) during theblower on-delay period.13 LIMIT CIRCUIT LOCKOUT – Lockoutoccurs if the limit, draft safeguard, flamerollout, or blocked vent switch*(if used) isopen longer than 3 minutes. Control willauto-reset after 3 hours. See code 33.14 IGNITION LOCKOUT – System failed toignite gas and prove flame in 4 attempts.Control will auto-reset after 3 hours.See status code 34.21 GAS HEATING LOCKOUT – Turn offpower and wait 5 minutes to retry.Check for:- Stuck closed gas valve relay on control.- Miswire or short to gas valve wire.22 ABNORMAL FLAME-PROVING SIGNALFlame is proved while gas valve is de-energized. Inducer will run until fault iscleared. Check for:- Stuck open or leaky gas valve.23 PRESSURE SWITCH DID NOT OPENCheck for:- Obstructed pressure tube.- Pressure switch stuck closed.24 SECONDARY VOLTAGE FUSE IS OPENCheck for:- Short circuit in secondary voltage (24V)wiring including thermostat leads.Disconnect thermostat leads to isolateshort circuit.31 PRESSURE SWITCH DID NOT CLOSEOR REOPENED – If open longer than 5minutes, inducer shuts off for 15 minutesbefore retry. If opens during blower on-delay period, blower will come on for theselected blower off-delay. Check for:- Proper vent sizing.- Low inducer voltage (115V).- Low inlet gas pressure (if LGPS used).- Inadequate combustion air supply.- Disconnected or obstructed pressuretubing.- Defective inducer motor.-Defective pressure switch.- Excessive wind.- Restricted vent.33 LIMIT CIRCUIT FAULT – Indicates thelimit, draft safeguard, flame rollout, orblocked vent switch* (if used) is open.Blower will run for 4 minutes or until openswitch remakes whichever is longer. Ifopen longer than 3 minutes, codechanges to lockout #13. If open lessthan 3 min. status code #33 continuesto flash until blower shuts off. Flamerollout switch and BVSS requires manualreset. Check for:- Dirty filter or restricted duct system.- Loose blower wheel.-Defective switch or connections.- Defective blower motor or capacitor.- Inadequate combustion air supply (flame rollout switch open).- Restricted vent.-Proper vent sizing.- Excessive wind.34 IGNITION PROVING FAILURE – If flameis not sensed during the trial for ignitionperiod, the control will repeat the ignitionsequence 3 more times before lockout#14 occurs. If flame signal is lost duringthe blower on-delay period, blower willcome on for the selected blower off-delay. Check the following items first beforeproceeding to the next step.- Gas valve turned off.- Manual shut-off valve.-Green/Yellow wire MUST be connectedto furnace sheet metal.- Flame sensor must not be grounded.To determine whether the problem is inthe gas valve, igniter, or flame sensor thesystem can be operated in the componenttest mode to check the igniter. Firstremove the R thermostat connection fromthe control and initiate the componenttest sequence. Does the igniter gloworange/white by the end of the 15 secondwarm-up period?Unplug igniter harness from control and initiateanother component test sequence. Checkfor 115V between pin 1 and NEUTRAL-L2 onthe control. Was 115V present for the 15second period?Reconnect the R thermostat lead and setthermostat to call for heat. Connect voltmeteracross gas valve connections. Does gas valvereceive 24V?Does gas valve open and allow gas to flow?Do the main burners ignite?Do the main burners stay on?Repeat call for heat and check flame sensorcurrent during trial for ignition period. Is theDC microamps below 0.5?Is current near typical value?Will main burners ignite and stay on?Fixed.Clean flame sensor with fine steel wool andrecheck current. Nominal current is 4.0 to 6.0microamps.45 CONTROL CIRCUITRY LOCKOUTAuto-reset after 1 hour lockout due to:- Flame circuit failure.- Gas valve relay stuck open.- Software check error.Reset power to clear lockout. Replacecontrol if code repeats.Replace furnace control.Check for continuity in the harness and igniter. Replace defective component.Check connections. If OK, replace control.Check that all gas valves are turned on.Replace valve.Check for:-Inadequate flame carryover or roughignition.-Low inlet gas pressure.- Proper firing rate.- Blocked or incorrect carry- over gap.(.045” nominal)Allow blower to come on and repeat test tocheck for intermittent operation.Check connections and retry. If current isnear typical value (4.0-6.0 nominal) andburners will not stay on, replace control.Replace electrode.Replace furnace control.* Blocked vent switch used in Chimney Adapter KitYESYESYESYESNOYESYESYESNOYESNONONOYESNONONONO310AAV 51 PARTS REPLACEMENT INFORMATION GUIDE CASING GROUP Outer door Blower door Top filler plate Bottom filler plate Bottom enclosure ELECTRICAL GROUP Control bracket Junction box Limit switch(es) Circuit board Door switch Transformer Wiring harness 115v Wiring harness 24v BLOWER GROUP Blower housing Blower cutoff Blower motor Blower wheel Capacitor (where used) Capacitor strap (where used) Grommet Power choke (where used) GAS CONTROL GROUP Manifold Burner assembly Orifice Flame sensor Hot surface igniter Gas valve Manual reset limit switches Burner support assembly HEAT EXCHANGER GROUP Heat exchanger cell Cell panel Lox NOx baffle (California models only) INDUCER GROUP Housing assembly Pressure switch Inducer motor Inducer wheel Vent elbow assembly Draft safeguard switch TO OBTAIN INFORMATION ON PARTS:Consult your installing dealer or classified section of your local telephone directory under “Heating Equipment” or “Air Conditioning Contractors and Systems” headings for dealer listing by brand name or contact: BRYANT HEATING & COOLING SYSTEMS Consumer Relations Department P.O. Box 4952 Syracuse, New York 13221--4952 1--800--428--4326 Example of Model Number MODEL VOLTAGE IGNITION TYPE COOLING SIZE (AIRFLOW) HEATING SIZE VARIATION SERIES VARIATION 310A A V 066 135 A E JA WARNING: Improper installation, adjustment, alteration, service, or maintenance can cause personal injury, property damage, or death. Consult a qualified installer, service agency, or your local gas supplier for information or assistance. The qualified installer or service agency must use only factory--authorized replacement parts, kits, or accessories when modifying this product.310AAV 52 Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations. EBryant Heating & Cooling Systems 7310 W. Morris St. Indianapolis, IN 46231 Edition Date: 08/13 Replaces: II310A---45---15 Catalog No. II310A --- 45 --- 16310AAV