Loading...
2021.0008 21-005 Stevens 4-Plex Hyd Calc1/ 27 / 21Joseph Aaron Pennell 3479-0220-B Level 2 Knight Fire Protection KNIGHFP044LK Knight Fire Protection Inc. 9702 Lathrop Industrial Dr.SW Olympia, Washington 98512 360 786 8606 Job Name :Stevens 4-Plex Building :1 of 1 Location :xxxx Stevens Ave. NE System :111 Contract :21-005 Data File :21-005 Stevens 4-Plex Hyd Calc 111-1.WXF Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 Knight Fire Protection Inc.Page 1 Stevens 4-Plex Date 1-27-21 HYDRAULIC CALCULATIONS for Project name:Stevens 4-Plex Location:xxxx Stevens Ave. NE Drawing no:2 of 2 Date:1-27-21 Design Remote area number:111 Remote area location:2nd Floor Hallway Occupancy classification:Residential Density:.05 - Gpm/SqFt Area of application:512 - SqFt Coverage per sprinkler:256 - SqFt Type of sprinklers calculated:4.9K Res. Conc. Pend No. of sprinklers calculated:2 In-rack demand:N/A - GPM Hose streams:N/A - GPM Total water required (including hose streams):26 - GPM @ 37 - Psi Type of system:Wet Tree Volume of dry or preaction system:N/A - Gal Water supply information Date:7-5-18 Location:Tahoma Blvd. Source:City of Yelm Name of contractor:Knight Fire Protection Address:9702 Lathrop Industrial Drive SE Phone number:360-786-8606 Name of designer:Mark Cantrell Authority having jurisdiction:City of Yelm Notes: (Include peaking information or gridded systems here.) Knight Fire Protection Inc.Page 2 Stevens 4-Plex Date 1-27-21 10 20 30 40 E 50 R 60 U 70 S 80 S 90 E 100 R 110 P 120 130 140 150 200 400 600 800 1000 1200 1400 1600 1800 FLOW ( N ^ 1.85 ) City Water Supply:Demand: C1 C2 C1 - Static Pressure :56 C2 - Residual Pressure:54 C2 - Residual Flow :1130 D1 - Elevation : 6.930 D2 - System Flow :26.339 D2 - System Pressure : 37.187 Hose ( Demand ):_______ D3 - System Demand :26.339 Safety Margin : 18.811 D1 D2 Water Supply Curve C Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 Knight Fire Protection Inc.Page 3 Stevens 4-Plex Date 1-27-21 Fitting Legend Abbrev.Name ½¾1 1¼1½2 2½3 3½4 5 6 8 10 12 14 16 18 20 24 Ball B Ball Milw BB-SC100 2.25 2 2.5 2.25 10 Fsp Flow Switch Potter VSR Fitting generates a Fixed Loss Based on Flow N *CPVC 90'Ell Harvel-Spears 7 7 8 9 11 12 13 0 0 0 0 0 0 0 0 0 0 0 0 O *CPVC Tee - Branch 3 3 5 6 8 10 12 15 0 0 0 0 0 0 0 0 0 0 0 0 Zaa Ames 2000B Fitting generates a Fixed Loss Based on Flow Units Summary Diameter Units Inches Length Units Feet Flow Units US Gallons per Minute Pressure Units Pounds per Square Inch Note: Fitting Legend provides equivalent pipe lengths for fittings types of various diameters. Equivalent lengths shown are standard for actual diameters of Sched 40 pipe and CFactors of 120 except as noted with *. The fittings marked with a * show equivalent lengths values supplied by manufacturers based on specific pipe diameters and CFactors and they require no adjustment. All values for fittings not marked with a * will be adjusted in the calculation for CFactors of other than 120 and diameters other than Sched 40 per NFPA. Fittings Used Summary Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 Knight Fire Protection Inc.Page 4 Stevens 4-Plex Date 1-27-21 Node Elevation K-Fact Pt Pn Flow Density Area Press No.Actual Actual Req. 111H 17.0 4.9 7.0 na 12.96 0.05 256 7.0 112H 17.0 4.9 7.45 na 13.37 0.05 256 7.0 111 17.5 7.68 na 112 17.5 7.9 na A1 17.5 8.0 na TOR1 8.5 17.18 na BOR1 3.0 23.19 na FLG1 0.5 28.55 na SRC 1.0 37.19 na The maximum velocity is 8.88 and it occurs in the pipe between nodes A1 and TOR1 Pressure / Flow Summary - STANDARD Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 Knight Fire Protection Inc.Page 5 Stevens 4-Plex Date 1-27-21 Hyd.Qa Dia.Fitting Pipe Pt Pt Ref."C"or Ftng's Pe Pv *******Notes ****** Point Qt Pf/Ft Eqv.Ln.Total Pf Pn *FLOWING 111H 12.96 1.101 2N 14.0 10.250 7.000 K Factor = 4.90 to 150.0 O 5.0 19.000 -0.217 111 12.96 0.0305 0.0 29.250 0.893 Vel = 4.37 0.0 12.96 7.676 K Factor = 4.68 112H 13.37 1.101 N 7.0 8.500 7.450 K Factor = 4.90 to 150.0 O 5.0 12.000 -0.217 112 13.37 0.0323 0.0 20.500 0.663 Vel = 4.51 0.0 13.37 7.896 K Factor = 4.76 *MAIN 111 12.96 1.101 0.0 10.580 7.676 to 150.0 0.0 0.0 0.0 A1 12.96 0.0305 0.0 10.580 0.323 Vel = 4.37 0.0 12.96 7.999 K Factor = 4.58 112 13.37 1.101 0.0 3.170 7.896 to 150.0 0.0 0.0 0.0 A1 13.37 0.0325 0.0 3.170 0.103 Vel = 4.51 A1 12.97 1.101 N 7.0 19.670 7.999 to 150.0 4O 20.0 27.000 3.898 TOR1 26.34 0.1132 0.0 46.670 5.284 Vel = 8.88 0.0 26.34 17.181 K Factor = 6.35 *RISER TOR1 26.34 1.101 Fsp 0.0 5.500 17.181 to 150.0 0.0 0.0 5.382 * * Fixed Loss = 3 BOR1 26.34 0.1133 0.0 5.500 0.623 Vel = 8.88 BOR1 0.0 1.101 Zaa 0.0 2.500 23.186 to 150.0 0.0 0.0 5.083 * * Fixed Loss = 4 FLG1 26.34 0.1132 0.0 2.500 0.283 Vel = 8.88 FLG1 0.0 1.112 Ball 1.056 75.000 28.552 to 150.0 O 6.0 7.056 -0.217 SRC 26.34 0.1079 0.0 82.056 8.852 Vel = 8.70 0.0 26.34 37.187 K Factor = 4.32 Final Calculations - Hazen-Williams - 2007 Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 Knight Fire Protection Inc. 9702 Lathrop Industrial Dr.SW Olympia, Washington 98512 360 786 8606 Job Name :Stevens 4-Plex Building :1 of 1 Location :xxxx Stevens Ave. NE System :211 Contract :21-005 Data File :21-005 Stevens 4-Plex Hyd Calc 211-1.WXF Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 Knight Fire Protection Inc.Page 1 Stevens 4-Plex Date 1-27-21 HYDRAULIC CALCULATIONS for Project name:Stevens 4-Plex Location:xxxx Stevens Ave. NE Drawing no:2 of 2 Date:1-27-21 Design Remote area number:211 Remote area location:2nd Floor North Bedroom Occupancy classification:Residential Density:.05 - Gpm/SqFt Area of application:512 - SqFt Coverage per sprinkler:256 - SqFt Type of sprinklers calculated:4.9K Res. Conc. Pend No. of sprinklers calculated:2 In-rack demand:N/A - GPM Hose streams:N/A - GPM Total water required (including hose streams):26 - GPM @ 38 - Psi Type of system:Wet Tree Volume of dry or preaction system:N/A - Gal Water supply information Date:7-5-18 Location:Tahoma Blvd. Source:City of Yelm Name of contractor:Knight Fire Protection Address:9702 Lathrop Industrial Drive SE Phone number:360-786-8606 Name of designer:Mark Cantrell Authority having jurisdiction:City of Yelm Notes: (Include peaking information or gridded systems here.) Knight Fire Protection Inc.Page 2 Stevens 4-Plex Date 1-27-21 10 20 30 40 E 50 R 60 U 70 S 80 S 90 E 100 R 110 P 120 130 140 150 200 400 600 800 1000 1200 1400 1600 1800 FLOW ( N ^ 1.85 ) City Water Supply:Demand: C1 C2 C1 - Static Pressure :56 C2 - Residual Pressure:54 C2 - Residual Flow :1130 D1 - Elevation : 6.930 D2 - System Flow :26.032 D2 - System Pressure : 38.046 Hose ( Demand ):_______ D3 - System Demand :26.032 Safety Margin : 17.952 D1 D2 Water Supply Curve C Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 Knight Fire Protection Inc.Page 3 Stevens 4-Plex Date 1-27-21 Fitting Legend Abbrev.Name ½¾1 1¼1½2 2½3 3½4 5 6 8 10 12 14 16 18 20 24 Ball B Ball Milw BB-SC100 2.25 2 2.5 2.25 10 Fsp Flow Switch Potter VSR Fitting generates a Fixed Loss Based on Flow N *CPVC 90'Ell Harvel-Spears 7 7 8 9 11 12 13 0 0 0 0 0 0 0 0 0 0 0 0 O *CPVC Tee - Branch 3 3 5 6 8 10 12 15 0 0 0 0 0 0 0 0 0 0 0 0 Zaa Ames 2000B Fitting generates a Fixed Loss Based on Flow Units Summary Diameter Units Inches Length Units Feet Flow Units US Gallons per Minute Pressure Units Pounds per Square Inch Note: Fitting Legend provides equivalent pipe lengths for fittings types of various diameters. Equivalent lengths shown are standard for actual diameters of Sched 40 pipe and CFactors of 120 except as noted with *. The fittings marked with a * show equivalent lengths values supplied by manufacturers based on specific pipe diameters and CFactors and they require no adjustment. All values for fittings not marked with a * will be adjusted in the calculation for CFactors of other than 120 and diameters other than Sched 40 per NFPA. Fittings Used Summary Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 Knight Fire Protection Inc.Page 4 Stevens 4-Plex Date 1-27-21 Node Elevation K-Fact Pt Pn Flow Density Area Press No.Actual Actual Req. 211H 17.0 4.9 7.11 na 13.07 0.05 256 7.0 212H 17.0 4.9 7.0 na 12.96 0.05 256 7.0 A2 17.5 7.22 na B2 17.5 9.61 na TOR2 8.5 18.25 na BOR2 3.0 24.24 na FLG2 0.5 29.6 na SRC 1.0 38.05 na The maximum velocity is 8.77 and it occurs in the pipe between nodes A2 and B2 Pressure / Flow Summary - STANDARD Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 Knight Fire Protection Inc.Page 5 Stevens 4-Plex Date 1-27-21 Hyd.Qa Dia.Fitting Pipe Pt Pt Ref."C"or Ftng's Pe Pv *******Notes ****** Point Qt Pf/Ft Eqv.Ln.Total Pf Pn *FLOWING 211H 13.07 1.101 O 5.0 5.580 7.112 K Factor = 4.90 to 150.0 0.0 5.000 -0.217 A2 13.07 0.0310 0.0 10.580 0.328 Vel = 4.40 0.0 13.07 7.223 K Factor = 4.86 212H 12.96 1.101 N 7.0 7.420 7.000 K Factor = 4.90 to 150.0 0.0 7.000 -0.217 A2 12.96 0.0305 0.0 14.420 0.440 Vel = 4.37 0.0 12.96 7.223 K Factor = 4.82 *MAIN A2 26.03 1.101 2O 10.0 11.500 7.223 to 150.0 0.0 10.000 0.0 B2 26.03 0.1108 0.0 21.500 2.383 Vel = 8.77 B2 0.0 1.101 N 7.0 20.830 9.606 to 150.0 3O 15.0 22.000 3.898 TOR2 26.03 0.1108 0.0 42.830 4.745 Vel = 8.77 0.0 26.03 18.249 K Factor = 6.09 *RISER TOR2 26.03 1.101 Fsp 0.0 5.500 18.249 to 150.0 0.0 0.0 5.382 * * Fixed Loss = 3 BOR2 26.03 0.1109 0.0 5.500 0.610 Vel = 8.77 BOR2 0.0 1.101 Zaa 0.0 2.500 24.241 to 150.0 0.0 0.0 5.083 * * Fixed Loss = 4 FLG2 26.03 0.1104 0.0 2.500 0.276 Vel = 8.77 FLG2 0.0 1.112 Ball 1.056 75.000 29.600 to 150.0 O 6.0 7.056 -0.217 SRC 26.03 0.1056 0.0 82.056 8.663 Vel = 8.60 0.0 26.03 38.046 K Factor = 4.22 Final Calculations - Hazen-Williams - 2007 Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 Knight Fire Protection Inc. 9702 Lathrop Industrial Dr.SW Olympia, Washington 98512 360 786 8606 Job Name :Stevens 4-Plex Building :1 of 1 Location :xxxx Stevens Ave. NE System :311 Contract :21-005 Data File :21-005 Stevens 4-Plex Hyd Calc 311-1.WXF Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 Knight Fire Protection Inc.Page 1 Stevens 4-Plex Date 1-27-21 HYDRAULIC CALCULATIONS for Project name:Stevens 4-Plex Location:xxxx Stevens Ave. NE Drawing no:2 of 2 Date:1-27-21 Design Remote area number:311 Remote area location:2nd Floor North Bedroom Occupancy classification:Residential Density:.05 - Gpm/SqFt Area of application:512 - SqFt Coverage per sprinkler:256 - SqFt Type of sprinklers calculated:4.9K Res. Conc. Pend No. of sprinklers calculated:2 In-rack demand:N/A - GPM Hose streams:N/A - GPM Total water required (including hose streams):26 - GPM @ 38 - Psi Type of system:Wet Tree Volume of dry or preaction system:N/A - Gal Water supply information Date:7-5-18 Location:Tahoma Blvd. Source:City of Yelm Name of contractor:Knight Fire Protection Address:9702 Lathrop Industrial Drive SE Phone number:360-786-8606 Name of designer:Mark Cantrell Authority having jurisdiction:City of Yelm Notes: (Include peaking information or gridded systems here.) Knight Fire Protection Inc.Page 2 Stevens 4-Plex Date 1-27-21 10 20 30 40 E 50 R 60 U 70 S 80 S 90 E 100 R 110 P 120 130 140 150 200 400 600 800 1000 1200 1400 1600 1800 FLOW ( N ^ 1.85 ) City Water Supply:Demand: C1 C2 C1 - Static Pressure :56 C2 - Residual Pressure:54 C2 - Residual Flow :1130 D1 - Elevation : 6.930 D2 - System Flow :26.032 D2 - System Pressure : 38.046 Hose ( Demand ):_______ D3 - System Demand :26.032 Safety Margin : 17.952 D1 D2 Water Supply Curve C Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 Knight Fire Protection Inc.Page 3 Stevens 4-Plex Date 1-27-21 Fitting Legend Abbrev.Name ½¾1 1¼1½2 2½3 3½4 5 6 8 10 12 14 16 18 20 24 Ball B Ball Milw BB-SC100 2.25 2 2.5 2.25 10 Fsp Flow Switch Potter VSR Fitting generates a Fixed Loss Based on Flow N *CPVC 90'Ell Harvel-Spears 7 7 8 9 11 12 13 0 0 0 0 0 0 0 0 0 0 0 0 O *CPVC Tee - Branch 3 3 5 6 8 10 12 15 0 0 0 0 0 0 0 0 0 0 0 0 Zaa Ames 2000B Fitting generates a Fixed Loss Based on Flow Units Summary Diameter Units Inches Length Units Feet Flow Units US Gallons per Minute Pressure Units Pounds per Square Inch Note: Fitting Legend provides equivalent pipe lengths for fittings types of various diameters. Equivalent lengths shown are standard for actual diameters of Sched 40 pipe and CFactors of 120 except as noted with *. The fittings marked with a * show equivalent lengths values supplied by manufacturers based on specific pipe diameters and CFactors and they require no adjustment. All values for fittings not marked with a * will be adjusted in the calculation for CFactors of other than 120 and diameters other than Sched 40 per NFPA. Fittings Used Summary Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 Knight Fire Protection Inc.Page 4 Stevens 4-Plex Date 1-27-21 Node Elevation K-Fact Pt Pn Flow Density Area Press No.Actual Actual Req. 311H 17.0 4.9 7.11 na 13.07 0.05 256 7.0 312H 17.0 4.9 7.0 na 12.96 0.05 256 7.0 A3 17.5 7.22 na B3 17.5 9.61 na TOR3 8.5 18.25 na BOR3 3.0 24.24 na FLG3 0.5 29.6 na SRC 1.0 38.05 na The maximum velocity is 8.77 and it occurs in the pipe between nodes A3 and B3 Pressure / Flow Summary - STANDARD Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 Knight Fire Protection Inc.Page 5 Stevens 4-Plex Date 1-27-21 Hyd.Qa Dia.Fitting Pipe Pt Pt Ref."C"or Ftng's Pe Pv *******Notes ****** Point Qt Pf/Ft Eqv.Ln.Total Pf Pn *FLOWING 311H 13.07 1.101 O 5.0 5.580 7.112 K Factor = 4.90 to 150.0 0.0 5.000 -0.217 A3 13.07 0.0310 0.0 10.580 0.328 Vel = 4.40 0.0 13.07 7.223 K Factor = 4.86 312H 12.96 1.101 N 7.0 7.420 7.000 K Factor = 4.90 to 150.0 0.0 7.000 -0.217 A3 12.96 0.0305 0.0 14.420 0.440 Vel = 4.37 0.0 12.96 7.223 K Factor = 4.82 *MAIN A3 26.03 1.101 2O 10.0 11.500 7.223 to 150.0 0.0 10.000 0.0 B3 26.03 0.1108 0.0 21.500 2.383 Vel = 8.77 B3 0.0 1.101 N 7.0 20.830 9.606 to 150.0 3O 15.0 22.000 3.898 TOR3 26.03 0.1108 0.0 42.830 4.745 Vel = 8.77 0.0 26.03 18.249 K Factor = 6.09 *RISER TOR3 26.03 1.101 Fsp 0.0 5.500 18.249 to 150.0 0.0 0.0 5.382 * * Fixed Loss = 3 BOR3 26.03 0.1109 0.0 5.500 0.610 Vel = 8.77 BOR3 0.0 1.101 Zaa 0.0 2.500 24.241 to 150.0 0.0 0.0 5.083 * * Fixed Loss = 4 FLG3 26.03 0.1104 0.0 2.500 0.276 Vel = 8.77 FLG3 0.0 1.112 Ball 1.056 75.000 29.600 to 150.0 O 6.0 7.056 -0.217 SRC 26.03 0.1056 0.0 82.056 8.663 Vel = 8.60 0.0 26.03 38.046 K Factor = 4.22 Final Calculations - Hazen-Williams - 2007 Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 Knight Fire Protection Inc. 9702 Lathrop Industrial Dr.SW Olympia, Washington 98512 360 786 8606 Job Name :Stevens 4-Plex Building :1 of 1 Location :xxxx Stevens Ave. NE System :411 Contract :21-005 Data File :21-005 Stevens 4-Plex Hyd Calc 411-1.WXF Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 Knight Fire Protection Inc.Page 1 Stevens 4-Plex Date 1-27-21 HYDRAULIC CALCULATIONS for Project name:Stevens 4-Plex Location:xxxx Stevens Ave. NE Drawing no:2 of 2 Date:1-27-21 Design Remote area number:411 Remote area location:2nd Floor Hallway Occupancy classification:Residential Density:.05 - Gpm/SqFt Area of application:512 - SqFt Coverage per sprinkler:256 - SqFt Type of sprinklers calculated:4.9K Res. Conc. Pend No. of sprinklers calculated:2 In-rack demand:N/A - GPM Hose streams:N/A - GPM Total water required (including hose streams):26 - GPM @ 37 - Psi Type of system:Wet Tree Volume of dry or preaction system:N/A - Gal Water supply information Date:7-5-18 Location:Tahoma Blvd. Source:City of Yelm Name of contractor:Knight Fire Protection Address:9702 Lathrop Industrial Drive SE Phone number:360-786-8606 Name of designer:Mark Cantrell Authority having jurisdiction:City of Yelm Notes: (Include peaking information or gridded systems here.) Knight Fire Protection Inc.Page 2 Stevens 4-Plex Date 1-27-21 10 20 30 40 E 50 R 60 U 70 S 80 S 90 E 100 R 110 P 120 130 140 150 200 400 600 800 1000 1200 1400 1600 1800 FLOW ( N ^ 1.85 ) City Water Supply:Demand: C1 C2 C1 - Static Pressure :56 C2 - Residual Pressure:54 C2 - Residual Flow :1130 D1 - Elevation : 6.930 D2 - System Flow :26.339 D2 - System Pressure : 37.187 Hose ( Demand ):_______ D3 - System Demand :26.339 Safety Margin : 18.811 D1 D2 Water Supply Curve C Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 Knight Fire Protection Inc.Page 3 Stevens 4-Plex Date 1-27-21 Fitting Legend Abbrev.Name ½¾1 1¼1½2 2½3 3½4 5 6 8 10 12 14 16 18 20 24 Ball B Ball Milw BB-SC100 2.25 2 2.5 2.25 10 Fsp Flow Switch Potter VSR Fitting generates a Fixed Loss Based on Flow N *CPVC 90'Ell Harvel-Spears 7 7 8 9 11 12 13 0 0 0 0 0 0 0 0 0 0 0 0 O *CPVC Tee - Branch 3 3 5 6 8 10 12 15 0 0 0 0 0 0 0 0 0 0 0 0 Zaa Ames 2000B Fitting generates a Fixed Loss Based on Flow Units Summary Diameter Units Inches Length Units Feet Flow Units US Gallons per Minute Pressure Units Pounds per Square Inch Note: Fitting Legend provides equivalent pipe lengths for fittings types of various diameters. Equivalent lengths shown are standard for actual diameters of Sched 40 pipe and CFactors of 120 except as noted with *. The fittings marked with a * show equivalent lengths values supplied by manufacturers based on specific pipe diameters and CFactors and they require no adjustment. All values for fittings not marked with a * will be adjusted in the calculation for CFactors of other than 120 and diameters other than Sched 40 per NFPA. Fittings Used Summary Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 Knight Fire Protection Inc.Page 4 Stevens 4-Plex Date 1-27-21 Node Elevation K-Fact Pt Pn Flow Density Area Press No.Actual Actual Req. 411H 17.0 4.9 7.0 na 12.96 0.05 256 7.0 412H 17.0 4.9 7.45 na 13.37 0.05 256 7.0 411 17.5 7.68 na 412 17.5 7.9 na A4 17.5 8.0 na TOR4 8.5 17.18 na BOR4 3.0 23.19 na FLG4 0.5 28.55 na SRC 1.0 37.19 na The maximum velocity is 8.88 and it occurs in the pipe between nodes A4 and TOR4 Pressure / Flow Summary - STANDARD Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 Knight Fire Protection Inc.Page 5 Stevens 4-Plex Date 1-27-21 Hyd.Qa Dia.Fitting Pipe Pt Pt Ref."C"or Ftng's Pe Pv *******Notes ****** Point Qt Pf/Ft Eqv.Ln.Total Pf Pn *FLOWING 411H 12.96 1.101 2N 14.0 10.250 7.000 K Factor = 4.90 to 150.0 O 5.0 19.000 -0.217 411 12.96 0.0305 0.0 29.250 0.893 Vel = 4.37 0.0 12.96 7.676 K Factor = 4.68 412H 13.37 1.101 N 7.0 8.500 7.450 K Factor = 4.90 to 150.0 O 5.0 12.000 -0.217 412 13.37 0.0323 0.0 20.500 0.663 Vel = 4.51 0.0 13.37 7.896 K Factor = 4.76 *MAIN 411 12.96 1.101 0.0 10.580 7.676 to 150.0 0.0 0.0 0.0 A4 12.96 0.0305 0.0 10.580 0.323 Vel = 4.37 0.0 12.96 7.999 K Factor = 4.58 412 13.37 1.101 0.0 3.170 7.896 to 150.0 0.0 0.0 0.0 A4 13.37 0.0325 0.0 3.170 0.103 Vel = 4.51 A4 12.97 1.101 N 7.0 19.670 7.999 to 150.0 4O 20.0 27.000 3.898 TOR4 26.34 0.1132 0.0 46.670 5.284 Vel = 8.88 0.0 26.34 17.181 K Factor = 6.35 *RISER TOR4 26.34 1.101 Fsp 0.0 5.500 17.181 to 150.0 0.0 0.0 5.382 * * Fixed Loss = 3 BOR4 26.34 0.1133 0.0 5.500 0.623 Vel = 8.88 BOR4 0.0 1.101 Zaa 0.0 2.500 23.186 to 150.0 0.0 0.0 5.083 * * Fixed Loss = 4 FLG4 26.34 0.1132 0.0 2.500 0.283 Vel = 8.88 FLG4 0.0 1.112 Ball 1.056 75.000 28.552 to 150.0 O 6.0 7.056 -0.217 SRC 26.34 0.1079 0.0 82.056 8.852 Vel = 8.70 0.0 26.34 37.187 K Factor = 4.32 Final Calculations - Hazen-Williams - 2007 Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087