Loading...
The URL can be used to link to this page
Your browser does not support the video tag.
2021.0008 21-005 Stevens 4-Plex Equip Sub
KNIGHT FIRE PROTECTION, INC. 9702 LATHROP INDUSTRIAL DR. SW OLYMPIA, WA 98512-9188 (360) 786-8606 FAX 786-8722 LICENSE NO. KNIGHFP044LK Fire Sprinkler System Equipment Submittal Stevens 4-Plex xxxx Stevens Ave. NE Yelm, WA 98597 KFP Job #21-005 KFP Job #12-113 APRIL 2019 GFS-360 PAGE 1 of 4 SERIES GL-RES/INCH RESIDENTIAL ADJUSTABLE FLAT PLATE THE INCH® CONCEALED PENDENT K-FACTOR 4.9 TECHNICAL DATA Approvals • cULus - EU K-Factor • K4.9 gpm/psi½ (70.6 lpm/bar½) Temperature Rating • Sprinkler: 155°F (68°C) • Cover Plate: 135°F (57°C) Cover Plate Finishes • Chrome/White Painted (For painted plates other than white, contact Customer Service) Caution: Cover Plates must have factory applied finishes. Never paint/coat plates in field. Thread Size • 1/2” NPT (15mm) Vertical Adjustment • 1” (25mm) Nominal Maximum Working Pressure • 175 psi (12 bar) Materials of Construction • Frame - bronze • Deflector - brass • Screw - brass • Lodgement Wire - stainless steel • Bulb seat - copper • Spring - nickel alloy • Seal - teflon • Bulb (3mm) - glass • Cover Plate - brass • Concealed Cup - carbon steel 4077 Airpark Dr. Standish, MI 48658 • 989-846-4583 • www.globesprinkler.com Technical Support • 989-414-2600 • techservice@globesprinkler.com NOTE: Users should refer to Globe’s web site (www.globesprinkler.com) to assure that the most recent technical literature is being utilized. GENERAL DESCRIPTION The GL4906 Adjustable Flat Plate Concealed pendent sprinkler is a decorative fast response glass bulb sprinkler specifically tested and Listed for use in residential applica- tions such as homes, apartments, hotels, and dormitories to provide control of these residential type fires and to improve the chance for occupants to escape. The GL4906 utilizes a 3mm frangible glass bulb as its heat sensing operating ele- ment. While providing the optimal aesthetic appeal with the low profile flat cover plate, the GL4906 additionally provides the largest vertical adjustment in the industry of a nominal 1”. This nominal 1” adjustment allows for previously unrec- ognized installation flexibility resulting in a clean and tight final “fit” to the ceiling. This sprinkler may be installed within dwelling occupancies as allowed by NFPA 13, 13D, 13R and any other related documents as appropriate. OPERATION The soldered cover plate drops off the retainer assembly when exposed to heat, as from a fire, that has reached the plate’s Listed temperature rating exposing the sprinkler above. Upon the releasing of the cover plate, the deflector, which is connected to two guide pins, drops down below the ceiling into its intended position. As heat encompasses the glass bulb operating element of the sprinkler, the fluid in the bulb expands, compressing the air bubble within the bulb. When the air bubble can no longer compress, the fluid expansion causes breakage of the glass bulb, resulting in release of the water seat assembly, and discharge of water from the sprinkler. SERIES GL-RES/INCH GL4906 APRIL 2019 GFS-360 PAGE 2 of 4 D D 1 1/4" MAX. 1/4" MIN.CEILING DESIGN CRITERIA The Globe Concealed Pendent Sprinkler (GL4906) is cULus Listed for installation in accordance with this data sheet as well as the applicable installation Standard being utilized. Globe Residential Sprinkler Installation Guide When conditions exist that are outside the scope of the pro- vided criteria, refer to the Globe Residential Sprinkler Instal- lation Guide (Document GFS-380) for recommendations that may be acceptable to the authority having jurisdiction. Hydraulic Design (NFPA 13D and 13R) For systems designed to NFPA 13D or NFPA 13R, the mini- mum required sprinkler flow rate is given in TABLE A for the coverage areas shown. The sprinkler flow rate is the min- imum required discharge from each of the total number of “design sprinklers” as specified in NFPA 13D or NFPA 13R. Hydraulic Design (NFPA 13) The minimum required discharge from each design area sprinkler shall be the greater of the following: (1) In accordance with minimum flow rates indicated in TABLE A. (2) In rooms or compartments greater than 800 ft2 (74.3 m2), calculated based on delivering a minimum of 0.1 gpm/ft2 (4.1 mm/min) over the coverage area of each sprinkler, calculated in accordance with the S x L Rules for density area sprinklers. (3) In rooms or compartments 800 ft2 (74.3 m2) or less (Defined as “Small Rooms”) calculated based on de- livering a minimum of 0.1 gpm/ft2 (4.1 mm/min) over the room or compartment using the area of the room divided by the number of sprinklers in the room. (7 psi minimum) FIGURE 1: GL4906 INSTALLED POSITION FIGURE 2: GL4906 ACTIVATED POSITION 3 5/16" DIA. 2 3/4" MAX. 1 7/8" MIN. 1/8"CEILING COVER PLATE SUPPORT SHELL CUP DEFLECTOR DROP PIN 1" x 1/2" REDUCER 2 3/8" DIA. CEILING 2 3/4" DIA. MIN. HOLE IN CEILING SIN STYLE MAX.AREA OF COVERAGE FEET (m) MINIMUM PRESSURE PSI (bar) MINIMUM FLOW GPM (L/min.) DEFLECTOR TO CEILING DISTANCE INCHES (mm) MINIMUM DISTANCE BETWEEN SPRINKLERS FEET (m) GL4906 THE INCH® ADJUSTABLE CONCEALED PENDENT 12 (3.7) x 12 (3.7)7.0 (.48)13 (49)Smooth Ceilings1/4 (6) to 1-1/4 (32) Max.(When sprinkler is in activated position) Beamed Ceilings - Adjacent Allowed in ceiling. Beamed Ceilings - In Beam 4” Maximum Beam Depth 1/4 (6) to 1-1/4 (32) Max. (When sprinkler is in activated position) 9 (2.7) 14 (4.3) x 14 (4.3)7.0 (.48)13 (49) 16 (4.9) x 16 (4.9)7.0 (.48)13 (49) 18 (5.5) x 18 (5.5)12.0 (.83)17 (64) 20 (6.1) x 20 (6.1)16.7 (1.15)20 (76) TABLE A: NFPA 13, 13R, AND 13D HYDRAULIC AND INSTALLATION DESIGN CRITERIA FOR GL4906 CONCEALED SPRINKLER NOTE: Deflector-to-Ceiling Distance Criteria reflects 2019 Edition of NFPA 13D and 13R. APRIL 2019 GFS-360 PAGE 3 of 4 CARE AND MAINTENANCE Step 1. Install pendent sprinklers in the pendent position, with the centerline of the sprinkler perpendicular to the mounting surface. Step 2. Remove the Protective Cap. Step 3. With pipe-thread sealant applied to the pipe threads, and using the Concealed Sprinkler Wrench P/N 332765 (FIGURE 6), install and tighten the Sprinkler/Concealed Cup Assembly into the fitting. Step 4. Replace the Protective Cap by pushing it upwards until it bottoms out against the Sup- port Cup. The Protective Cap helps prevent damage to the Deflector and Drop Pins during ceiling installation and/or during application of the finish coating of the ceiling. NOTICE: The system is considered Out of Service when the protective caps are in place. Step 5. After the ceiling has been completed with the 2-3/4” (70mm) diameter hole, remove and discard the Protective Cap and verify that the Deflector moves up and down freely. If the sprinkler has been damaged or the deflector does not move up and down freely, replace the entire sprinkler assembly. Do not attempt to modify or repair. Step 6. Push on the Cover Plate Assembly until its flange contacts the ceiling. Never attempt to screw on the Cover Plate Assembly such that it lifts a ceiling panel out of its normal posi- tion. If the Cover Plate Assembly cannot be engaged with the Mounting Cup or the Cover Plate Assembly cannot be engaged sufficient- ly to contact the ceiling, the Sprinkler Fitting must be repositioned. Always obtain permission from the proper authorities to shut down the affected fire protection system and notify all personnel who may be affected by this action before closing a fire protection system main control valve for maintenance work on the system that it controls. Sprinklers should only be cleaned by means of gently dusting with a feather dust- er; otherwise, non-operation in the event of a fire or inadver- tent operation may result. When properly installed, there is a nominal 1/8” (3mm) air gap between the Cover Plate and the ceiling (FIGURE 1). This air gap is necessary for proper operation of the sprin- kler by allowing heat flow from a fire to pass below and above the Cover Plate to help assure appropriate release of the Cover Plate in a fire situation. This annular “gap” must be maintained and should never be sealed or caulked. Factory painted Cover Plates must not be repainted. In accordance with NFPA 25, Sprinklers which are found to be leaking or exhibiting visible signs of corrosion must be replaced. Automatic sprinklers must never be painted, plated, coated, or otherwise altered after leaving the factory. Care must be exercised to avoid damage to the sprinklers– before, during, and after installation. Sprinklers damaged by dropping, striking, wrench slippage, or similar incidents, must be replaced. The owner is responsible for the inspection, testing, and maintenance of their fire protection system and devices in compliance with this document, as well as with the appli- cable standards of the National Fire Protection Association (e.g. NFPA 25), in addition to the standards of any other authorities having jurisdiction. Refer to Globe’s Residential Installation Guide for further Care and Maintenance information. NOTICE Do not install any bulb-type sprinkler if the bulb is cracked or there is loss of liquid from the bulb. Sprinklers should be tightened enough to obtain a leak-tight joint when water pressure is applied and/or hydrostatic test is performed. Sprinklers should not be overtightened as this can result in distortion and subsequent leak-age. It is recommended not to exceed 14 ft.-lb. (19.0 Nm) torque for 1/2 inch NPT sprinkler threads. INSTALLATION FIGURE 3: HAND HELD INSTALLATION TOOL P/N 332875 FIGURE 4: INSTALLATION TOOL USED WITH EXTENSION P/N 332876 FIGURE 5: PROTECTIVE CAP P/N 332871 FIGURE 6: CONCEALED WRENCH P/N 332765 APRIL 2019 GFS-360 PAGE 4 of 4 ORDERING INFORMATION GLOBE® PRODUCT WARRANTY Globe agrees to repair or replace any of its manufactured products found to be defective in material or workmanship for a period of one year from date of shipment. For specific details of our warranty please refer to Price List Terms and Conditions of Sale (Our Price List). 4077 Airpark Dr. Standish, MI 48658 • 989-846-4583 • www.globesprinkler.com Technical Support • 989-414-2600 • techservice@globesprinkler.com Sprinkler/Cup Assembly Specify: Qty. • P/N . . . . . . . . . . . . . . . . . . . . . GL490615501 Cover Plate Assembly Finish Specify: Qty. • P/N 135°F (57°C) Chrome . . . . . . . . . . . . . . . 332891 135°F (57°C) White . . . . . . . . . . . . . . . . 332892 Custom Painted: Contact Customer Service Sprinkler Wrench Specify: Qty. • P/N Concealed Wrench . . . . . . . . . . . . . . . . .332765 The Inch Installation Tool Specify: Qty. • P/N Hand Held . . . . . . . . . . . . . . . . . . . . . 332875 Used with Extension . . . . . . . . . . . . . . . . 332876 Protective Caps Specify: Qty. • P/N . . . . . . . . . . . . . . . . . . . . . 332871 APRIL 2019 REV.A GFS-302 PAGE 1 of 4 SERIES GL-RES RESIDENTIAL PENDENT AND RECESSED PENDENT K-FACTOR: 3.0, 4.1, 4.9, 5.6 4077 Airpark Dr. Standish, MI 48658 • 989-846-4583 • www.globesprinkler.com Technical Support • 989-414-2600 • techservice@globesprinkler.com NOTE: Users should refer to Globe’s web site (www.globesprinkler.com) to assure that the most recent technical literature is being utilized. GENERAL DESCRIPTION The series GL-RES pendent sprinklers are decorative fast response glass bulb sprinklers specifically tested and List- ed for use in residential applications such as homes, apart- ments, hotels, and dormitories to provide control of these residential type fires and to improve the chance for occu- pants to escape. They utilize a 3mm frangible glass bulb as its heat sensing operating element. The recessed version of each of these Residential Sprinklers is intended for use in areas with finished ceilings. It employs a two-piece Re- cessed Escutcheon. The Recessed Escutcheon provides a total adjustment of 1/2 inch (12.7mm) from the flush ceiling position or ±1/4 inch (6.4mm) of recessed adjustment. The adjustment provided by the Recessed Escutcheon reduces the accuracy to which the pipe drops to the sprinklers must be cut. This sprinkler may be installed within dwelling occupancies as allowed by NFPA 13, 13D, 13R and any other related documents as appropriate. The GL3010 is typically utilized when maximum coverag- es are not needed, thereby reducing flow demands. The GL5610 is typically the sprinkler of choice when utilizing Residential Sprinklers within an NFPA 13 Occupancy. The larger K-factor can be advantageous when needed to con- form to the NFPA 13 hydraulic Special Design Approach for Residential Sprinklers. OPERATION Upon exposure to heat such as from a fire, the fluid in the bulb expands, compressing the air bubble within the bulb. When the air bubble can no longer compress, the fluid ex- pansion causes breakage of the glass bulb, resulting in re- lease of the water seat assembly, and discharge of water from the sprinkler. TECHNICAL DATA Approvals • See TABLE A Maximum Working Pressure • 175 psi (12 bar) Temperature Rating • See TABLE A K-Factor • GL3010 K3.0 gpm/psi½ (43.2 lpm/bar½) • GL4110 K4.1 gpm/psi½ (59.0 lpm/bar½) • GL4910 K4.9 gpm/psi½ (70.6 lpm/bar½) • GL5610 K5.6 gpm/psi½ (80.6 lpm/bar½) Thread Size • 1/2” NPT (15 mm) Length • 2-1/2” (6.3 cm) Materials of Construction • Frame - bronze • Deflector - brass • Screw - brass • Lodgement Wire (GL5610 only) - stainless steel • Bulb seat - copper • Spring - nickel alloy • Seal - teflon • Bulb - glass with alcohol based solution, 3mm • Escutcheon Assembly - carbon steel FINISHES AND ACCESSORIES Finishes • Factory Bronze • Chrome • White Polyester • Black Polyester - special order Escutcheons • Brass • Chrome • White Polyester • Black Polyester Wrenches • Standard • Recess • 1/2” NPT SERIES GL-RES GL3010, GL4110, GL4910, GL5610 SERIES GL-RES RESIDENTIAL PENDENT AND RECESSED PENDENT K-FACTOR: 3.0, 4.1, 4.9, 5.6 SERIES GL-RES RESIDENTIAL PENDENT AND RECESSED PENDENT K-FACTOR: 3.0, 4.1, 4.9, 5.6GFS-302 GFS-302 APRIL 2019 REV.A GFS-302 PAGE 2 of 4 DESIGN CRITERIA The Globe Residential Pendent Sprinkler Series GL-RES is cULus Listed for installation in accordance with this data sheet as well as the applicable installation Standard being utilized. Globe Residential Sprinkler Installation Guide When conditions exist that are outside the scope of the pro- vided criteria, refer to the Globe Residential Sprinkler Instal- lation Guide (Document GFS-380) for recommendations that may be acceptable to the authority having jurisdiction. Hydraulic Design (NFPA 13D and 13R) For systems designed to NFPA 13D or NFPA 13R, the min- imum required sprinkler flow rate is given in Table A for the coverage areas shown. The sprinkler flow rate is the min- imum required discharge from each of the total number of “design sprinklers” as specified in NFPA 13D or NFPA 13R. Hydraulic Design (NFPA 13) The minimum required discharge from each design area sprinkler shall be the greater of the following: (1) In accordance with minimum flow rates indicated in TABLE A. (2) In rooms or compartments greater than 800 ft2 (74.3 m2), calculated based on delivering a minimum of 0.1 gpm/ft2 (4.1 mm/min) over the coverage area of each sprinkler, calculated in accordance with the S x L Rules for density area sprinklers. (3) In rooms or compartments 800 ft2 (74.3 m2) or less (Defined as “Small Rooms”) calculated based on de- livering a minimum of 0.1 gpm/ft2 (4.1 mm/min) over the room or compartment using the area of the room divided by the number of sprinklers in the room. (7psi minimum) SIN K FACTOR GPM/PSI½ (lpm/bar½) TEMPERATURE MAX.AREA OF COVERAGE FEET (m) MINIMUM PRESSURE PSI (bar) MINIMUM FLOW GPM (L/min.) DEFLECTOR TO CEILING/ MOUNTING SURFACE DISTANCE INCHES (mm) MINIMUM DISTANCE BETWEEN SPRINKLERS FEET (m)155°F (68°C)175°F (79°C)200°F (93°C) GL3010 3.0 (43.2) cULus EU(1)cULus cULus 12 (3.6) x 12 (3.6)7.1 (.49)8.0 (30.3) Smooth Ceilings Recessed 1-1/8 (29) to 1-5/8 (41) Smooth Ceilings Exposed Max. 4 (101.6) Beamed Ceilings Adjacent per NFPA 13, 13D, or 13R as appropriate Beamed Ceilings In Beam 14” Max. Beam Depth 1-1/8 (29) to 1-5/8 (41) 8 (2.4) cULus EU(1)cULus cULus 14 (4.3) x 14 (4.3)11.1 (.765)10.0 (37.8) GL4110 4.1 (59) cULus EU(1)cULus EU(1)NA 12 (3.6) x 12 (3.6)7.2 (.5)11.0 (42) cULus EU(1)NA NA 14 (4.3) x 14 (4.3)8.6 (.59)12.0 (45) cULus EU(1)cULus NA 16 (4.9) x 16 (4.9)11.7 (.81)14.0 (53) GL4910 4.9 (70.6) cULus EU(1)cULus EU(1)NA 12 (3.6) x 12 (3.6)7.0 (.48)13.0 (49) cULus EU(1)cULus EU(1)NA 14 (4.3) x 14 (4.3)8.2 (.57)14.0 (53) cULus EU(1)cULus EU(1)NA 16 (4.9) x 16 (4.9)8.2 (.57)14.0 (53) cULus EU(1)cULus EU(1)NA 18 (5.5) x 18 (5.5)12.0 (.83)17.0 (64) cULus EU(1)cULus EU(1)NA 20 (6.1) x 20 (6.1)16.7 (1.15)20.0 (76) GL5610 5.6 (80.6) cULus NA NA 12 (3.6) x 12 (3.6)7.2 (.5)15.0 (57) cULus NA NA 16 (4.9) x 16 (4.9)11.5 (.79)19.0 (72) cULus NA NA 18 (5.5) x 18 (5.5)14.1 (.97)21.0 (79) cULus NA NA 20 (6.1) x 20 (6.1)18.4 (1.27)24.0 (91) TABLE A: NFPA 13, 13R, AND 13D HYDRAULIC AND INSTALLATION DESIGN CRITERIA (1)LISTED BY UNDERWRITERS LABORATORIES, INC. FOR USE IN THE U.S., CANADA, AND EUROPEAN UNION. NOTE: Deflector-to-Ceiling Distance Criteria reflects 2019 Edition of NFPA 13D and 13R. APRIL 2019 REV.A GFS-302 PAGE 3 of 4 4077 Airpark Dr. Standish, MI 48658 • 989-846-4583 • www.globesprinkler.com Technical Support • 989-414-2600 • techservice@globesprinkler.com NOTICE Do not install any bulb-type sprinkler if the bulb is cracked or there is loss of liquid from the bulb. Sprinklers should be tightened enough to obtain a leak-tight joint when water pressure is applied and/or hydrostatic test is performed. Sprinklers should not be overtightened as this can result in distortion and subsequent leak-age. It is recommended not to exceed 14 ft.-lb. (19.0 Nm) torque for 1/2 inch NPT sprinkler threads. Step1. Sprinklers must be properly oriented. Step2. With pipe thread sealant applied to the pipe threads, hand tighten the sprinkler into the sprin- kler fitting. Note: Do not grasp the sprinkler by the deflector. Step3. Wrench-tighten the sprinkler using only the appropriate wrench. Wrenches are only to be applied to the sprinkler wrench flats or wrench hex as applicable. Note: Do not apply wrench to frame arms. INSTALLATION CARE AND MAINTENANCE Prior to installation, it is important to read and follow the “Sprinkler Caution” sheet (GFS-840) included within each box of sprinklers. This sheet is available on Globe’s web site (www.globesprinkler.com). Always obtain permission from the proper authorities to shut down the affected fire protection system and notify all personnel who may be affected by this action before closing a fire protection system main control valve for maintenance work on the system that it controls. Sprinklers should only be cleaned by means of gently dust- ing with a feather duster; otherwise, non-operation in the event of a fire or inadvertent operation may result. Store sprinklers in a cool, dry place. Exposure to extreme heat will damage the thermal sensing element, possibly re- sulting in premature activation. Avoid direct sunlight. Replace any sprinkler that shows any corrosion, damage, or loss of liquid from the glass bulb. Do not attempt to paint or alter the sprinkler’s coating in any manner after leaving the manufacturing plant. Do not attach wiring, ropes, decorations or fixtures to a sprinkler. Absence of an escutcheon, used to cover a ceiling hole, may delay sprinkler operation in a fire situation. It is the owner’s responsibility for inspection, testing and maintenance of the fire sprinkler system with all components and devices in accordance with the National Fire Protection Association Pamphlet 25 as well as any other requirements as set forth by the local Authority Having Jurisdiction (AHJ). FIGURE 1: STANDARD WRENCH P/N 325390 FIGURE 2: RECESSED WRENCH P/N 325391 FIGURE 3: 1/2” ADJUSTMENT RECESSED PENDENT APRIL 2019 REV.A GFS-302 PAGE 4 of 4 GLOBE® PRODUCT WARRANTY Globe agrees to repair or replace any of its manufactured products found to be defective in material or workmanship for a period of one year from date of shipment. For specific details of our warranty please refer to Price List Terms and Conditions of Sale (Our Price List). ORDERING INFORMATION SPECIFY: • WRENCH • Quantity • Part Number 1/2” NPT Standard . . . . . . . . . . . 325390 1/2” NPT Recess . . . . . . . . . . . . 325391 • Quantity • Part Number Cap . . . . . . . . . . . . . . . . . . . 327109-Cap • PROTECTIVE CAPS • SPRINKLER • ESCUTCHEON • Quantity • Finish • Part Number (See TABLE C) • Quantity • SIN • Temperature Rating • Finish • Part Number (See TABLE B) TABLE B: PART NUMBER SELECTION PART NUMBER SIN + TEMPERATURE + FINISH XXXX XXX XX SIN TEMPERATURE FINISH GL3010 3010 155 155°F (68°C)01 BRONZE GL4110 4110 175 175°F (79°C)02 CHROME GL4910 4910 200 200°F (93°C)03 WHITE POLYESTER GL5610 5610 04 BLACK POLYESTER Note: All combinations may not be available. Refer to TABLE A for available listed combinations 1/2" (13mm) ADJUSTABLE RECESSED ESCUTCHEON FINISH FRICTION FIT 1/2” NPT THREADED 1/2” NPT Chrome 332071 329301 White Polyester 332073-W 329303-W Brass 332072 NA Black Polyester 332073-B NA TABLE C: ESCUTCHEONS APRIL 2019 REV. A GFS-332 PAGE 1 of 4 SERIES GL-RES/SW RESIDENTIAL HORIZONTAL SIDEWALL K-FACTOR: 4.2, 4.4 4077 Airpark Dr. Standish, MI 48658 • 989-846-4583 • www.globesprinkler.com Technical Support • 989-414-2600 • techservice@globesprinkler.com NOTE: Users should refer to Globe’s web site (www.globesprinkler.com) to assure that the most recent technical literature is being utilized. GENERAL DESCRIPTION The series GL-RES/SW sprinkler is a decorative fast re- sponse glass bulb sprinkler specifically tested and Listed for use in residential applications such as homes, apart- ments, hotels, and dormitories to provide control of these residential type fires and to improve the chance for occu- pants to escape. It utilizes a 3mm frangible glass bulb as its heat sensing operating element. The recessed version of each of these Residential Sprinklers is intended for use in walls or soffits as appropriate. It employs a two-piece Re- cessed Escutcheon. The Recessed Escutcheon provides a total adjustment of 1/2 inch (12.7mm) from the flush ceiling position or ±1/4 inch (6.4mm) of recessed adjustment. The adjustment provided by the Recessed Escutcheon reduces the accuracy to which the pipe drops to the sprinklers must be cut. This sprinkler may be installed within dwelling occupancies as allowed by NFPA 13, 13D, 13R and any other related documents as appropriate. OPERATION Upon exposure to heat such as from a fire, the fluid in the bulb expands, compressing the air bubble within the bulb. When the air bubble can no longer compress, the fluid ex- pansion causes breakage of the glass bulb, resulting in re- lease of the water seat assembly, and discharge of water from the sprinkler. TECHNICAL DATA Approvals • See TABLE A Maximum Working Pressure • 175 psi (12 bar) Temperature Rating • See TABLE A K-Factor • GL4231 K4.2 gpm/psi½ (60.5 lpm/bar½) • GL4431 K4.4 gpm/psi½ (63.4 lpm/bar½) Thread Size • 1/2” NPT (15 mm) Length • 2-1/2” (6.3 cm) Materials of Construction • Frame - bronze • Deflector - brass • Screw - brass • Lodgement Wire - stainless steel • Bulb seat - copper • Spring - nickel alloy • Seal - teflon • Bulb - glass with alcohol based solution, 3mm • Escutcheon Assembly - steel FINISHES AND ACCESSORIES Finishes • Factory Bronze • Chrome • White Polyester • Black Polyester - special order Escutcheons • Brass • Chrome • White Polyester • Black Polyester Wrenches • Standard • Residential Sidewall Recess • 1/2” NPT SERIES GL-RES/SW GL4231, GL4431 FIGURE 1: 1/2” ADJUSTMENT RECESSED SIDEWALL SERIES GL-RES/SW RESIDENTIAL HORIZONTAL SIDEWALL K-FACTOR: 4.2, 4.4 SERIES GL-RES/SW RESIDENTIAL HORIZONTAL SIDEWALL K-FACTOR: 4.2, 4.4GFS-332 GFS-332 APRIL 2019 REV. A GFS-332 PAGE 2 of 4 DESIGN CRITERIA The Globe Residential Horizontal Sidewall Sprinkler Series GL-RES/SW is cULus Listed for installation in accordance with this data sheet as well as the applicable installation Standard being utilized. Globe Residential Sprinkler Installation Guide When conditions exist that are outside the scope of the pro- vided criteria, refer to the Globe Residential Sprinkler Instal- lation Guide (Document GFS-380) for recommendations that may be acceptable to the authority having jurisdiction. Hydraulic Design (NFPA 13D and 13R) For systems designed to NFPA 13D or NFPA 13R, the min- imum required sprinkler flow rate is given in Table A for the coverage areas shown. The sprinkler flow rate is the min- imum required discharge from each of the total number of “design sprinklers” as specified in NFPA 13D or NFPA 13R. Hydraulic Design (NFPA 13) The minimum required discharge from each design area sprinkler shall be the greater of the following: (1) In accordance with minimum flow rates indicated in TABLE A. (2) In rooms or compartments greater than 800 ft2 (74.3 m2), calculated based on delivering a minimum of 0.1 gpm/ft2 (4.1 mm/min) over the coverage area of each sprinkler, calculated in accordance with the S x L Rules for density area sprinklers. (3) In rooms or compartments 800 ft2 (74.3 m2) or less (Defined as “Small Rooms”) calculated based on de- livering a minimum of 0.1 gpm/ft2 (4.1 mm/min) over the room or compartment using the area of the room divided by the number of sprinklers in the room. (7 psi minimum) SIN K FACTOR GPM/PSI½ (lpm/bar½) TEMPERATURE MAX.AREA OF COVERAGE WIDTH x LENGTH (2) FEET (m) MINIMUM PRESSURE PSI (bar) MINIMUM FLOW GPM (L/min.) DEFLECTOR TO CEILING DISTANCE INCHES (mm) MINIMUM DISTANCE BETWEEN SPRINKLERS FEET (m)155°F (68°C)175°F (79°C) GL4231 4.2 (60.5) cULus EU(1)cULus 12 (3.6) x 12 (3.6)9.6 (.66)13.0 (49) 4 (101.6) to 6 (152.4) 8 (2.4) cULus EU(1)cULus 14 (4.3) x 14 (4.3)12.8 (.88)15.0 (57) cULus EU(1)cULus 16 (4.9) x 16 (4.9)14.5 (1.0)16.0 (61) cULus EU(1)cULus 16 (4.9) x 18 (5.5)20.5 (1.41)19.0 (72) cULus EU(1)cULus 16 (4.9) x 20 (6.1)30.0 (2.07)23.0 (87) GL4431 4.4 (63.4) cULus EU(1)NA 12 (3.6) x 12 (3.6)8.7 (.6)13.0 (49) cULus EU(1)NA 14 (4.3) x 14 (4.3)11.6 (.80)15.0 (57) cULus EU(1)NA 16 (4.9) x 16 (4.9)13.2 (.91)16.0 (61) cULus EU(1)NA 16 (4.9) x 18 (5.5)18.7 (1.41)19.0 (72) cULus EU(1)NA 16 (4.9) x 20 (6.1)27.3 (1.88)23.0 (87) TABLE A: NFPA 13, 13R, AND 13D HYDRAULIC AND INSTALLATION DESIGN CRITERIA (1)LISTED BY UNDERWRITERS LABORATORIES, INC. FOR USE IN THE U.S., CANADA, AND EUROPEAN UNION. (2)WIDTH REFERS TO LATERAL DISTANCE BETWEEN SPRINKLERS ALONG A WALL OR TWICE THE DISTANCE OFF AN END WALL IN THE CASE OF AN END SPRINKLER, WHICHEVER IS GREATER. LENGTH REFERS TO THE INTENDED COVERAGE AREA OUT FROM THE SPRINKLER (FORWARD THROW). APRIL 2019 REV. A GFS-332 PAGE 3 of 4 NOTICE Do not install any bulb-type sprinkler if the bulb is cracked or there is loss of liquid from the bulb. Sprinklers should be tightened enough to obtain a leak-tight joint when water pressure is applied and/or hydrostatic test is performed. Sprinklers should not be overtightened as this can result in distortion and subsequent leak-age. It is recommended not to exceed 14 ft.-lb. (19.0 Nm) torque for 1/2 inch NPT sprinkler threads. FIGURE 2: STANDARD WRENCH P/N 325390 4077 Airpark Dr. Standish, MI 48658 • 989-846-4583 • www.globesprinkler.com Technical Support • 989-414-2600 • techservice@globesprinkler.com CARE AND MAINTENANCE Step1. Sprinklers must be properly oriented. Step2. With pipe thread sealant applied to the pipe threads, hand tighten the sprinkler into the sprin- kler fitting. Note: Do not grasp the sprinkler by the deflector. Step3. Wrench-tighten the sprinkler using only the appropriate wrench. Wrenches are only to be applied to the sprinkler wrench flats or wrench hex as applicable. Note: Do not apply wrench to frame arms. INSTALLATION Prior to installation, it is important to read and follow the “Sprinkler Caution” sheet (GFS-840) included within each box of sprinklers. This sheet is available on Globe’s web site (www.globesprinkler.com). Always obtain permission from the proper authorities to shut down the affected fire protection system and notify all personnel who may be affected by this action before closing a fire protection system main control valve for maintenance work on the system that it controls. Sprinklers should only be cleaned by means of gently dust- ing with a feather duster; otherwise, non-operation in the event of a fire or inadvertent operation may result. Store sprinklers in a cool, dry place. Exposure to extreme heat will damage the thermal sensing element, possibly re- sulting in premature activation. Avoid direct sunlight. Replace any sprinkler that shows any corrosion, damage, or loss of liquid from the glass bulb. Do not attempt to paint or alter the sprinkler’s coating in any manner after leaving the manufacturing plant. Do not attach wiring, ropes, decorations or fixtures to a sprinkler. Absence of an escutcheon, used to cover a ceiling hole, may delay sprinkler operation in a fire situation. It is the owner’s responsibility for inspection, testing and maintenance of the fire sprinkler system with all components and devices in accordance with the National Fire Protection Association Pamphlet 25 as well as any other requirements as set forth by the local Authority Having Jurisdiction (AHJ). FIGURE 3: RESIDENTIAL SIDEWALL RECESSED WRENCH P/N 327102 APRIL 2019 REV. A GFS-332 PAGE 4 of 4 GLOBE® PRODUCT WARRANTY Globe agrees to repair or replace any of its manufactured products found to be defective in material or workmanship for a period of one year from date of shipment. For specific details of our warranty please refer to Price List Terms and Conditions of Sale (Our Price List). ORDERING INFORMATION SPECIFY: • SPRINKLER • ESCUTCHEON • Quantity • Finish • Part Number (See TABLE C) • Quantity • SIN • Orientation • Temperature Rating • Finish • Part Number (See TABLE B) • WRENCH • Quantity • Part Number 1/2” NPT Standard . . . . . . . . . . . . . 325390 1/2” NPT Residential Sidewall Recess . . . 327102 • Quantity • Part Number Cap . . . . . . . . . . . . . . . . . . . . . 327109-Cap • PROTECTIVE CAPS TABLE B: PART NUMBER SELECTION PART NUMBER SIN + TEMPERATURE + FINISH XXXX XXX XX SIN TEMPERATURE FINISH GL4231 4231 155 155°F (68°C)01 BRONZE GL4431 4431 175 175°F (79°C)02 CHROME 03 WHITE POLYESTER 04 BLACK POLYESTER Note: All combinations may not be available. Refer to TABLE A for available listed combinations. 1/2" (13mm) ADJUSTABLE RECESSED ESCUTCHEON FINISH FRICTION FIT 1/2” NPT THREADED 1/2” NPT Chrome 332071 329301 White Polyester 332073-W 329303-W Brass 332072 NA Black Polyester 332073-B NA TABLE C: ESCUTCHEONS Series 2000B Double Check Valve Assemblies shall be installed at ref er enced cross- con nec tions to prevent the backflow of polluted water into the po ta ble water supply. Only those cross-con nec tions identified by local in spec tion au thor i ties as non-health hazard shall be allowed the use of an ap proved double check valve as sem bly. Check with local authority having jurisdiction regarding ver ti cal ori en ta tion, fre quen cy of test ing or other in stal la tion re quire ments. These valves meet the requirements of ASSE Std. 1015 and AWWA Std. C510 and are approved by the Foun da tion for Cross-Con nec tion Control and Hy drau lic Re search at the University of South ern California. Specifications A Double Check Valve Assembly shall be installed at each not ed lo ca tion. The as sem bly shall con sist of two positive seat ing check mod ules with cap tured springs and rubber seat discs. The check module seats and seat discs shall be re place able. Ser vice of all internal com po nents shall be through a sin gle ac cess cover se cured with stainless steel bolts. The as sem bly shall also in clude two resilient seat ed iso la tion valves and four top mount ed, re sil ient seat ed test cocks. The as sem bly shall meet the re quire ments of ASSE Std. 1015 and AWWA Std. C510. Ap proved by the Foun da tion for Cross-Con nec tion Control and Hy drau lic Re search at the Uni ver si ty of South ern Cal i for nia. As sem bly shall be an Ames Company Series 2000B. Approvals Approved by the Foundation for Cross-Connection Control and Hy drau lic Research at the University of Southern California. LBV models not listed. Horizontal and vertical "flow up" approval on all sizes. ES-A-2000B 3⁄4" 2000B (20mm) 2" 2000B HC (50mm) Series 2000B Double Check Valve Assemblies Sizes: 1⁄2" – 2" (15 – 50mm) Job Name ________________________________________________Contractor ______________________________________________ Job Location ______________________________________________Approval _______________________________________________ Engineer _________________________________________________Contractor’s P.O. No. ______________________________________ Approval _________________________________________________Representative ___________________________________________ Ames product specifications in U.S. customary units and metric are ap prox i mate and are pro vid ed for ref er ence only. For precise mea sure ments, please contact Ames Technical Ser vice. Ames reserves the right to change or modify prod uct de sign, con struc tion, spec i fi ca tions, or ma te ri als with out prior notice and without in cur ring any ob li ga tion to make such chang es and mod i fi ca tions on Ames products previously or sub se quent ly sold.www.amesfirewater.com Features • Ease of maintenance with only one cover • Top entry • Replaceable seats and seat discs • Modular construction • Compact design • 1⁄2" – 2" (15 – 50mm) Cast bronze body construction • Top mounted ball valve test cocks • Low pressure drop • No special tools required • 1⁄2" – 1" (15 – 25 mm) have tee handles Available Models Suffix: B - Quarter turn ball valves LBV - less ball valves SH - stainless steel ball valve handles HC - 21⁄2" inlet/outlet fire hydrant fit ting (2" valve) Pressure — Temperature Temperature Range: 33°F – 140°F (0.5°C – 60°C) Maximum Working Pressure: 175psi (12.1 bar) Standards AWWA Std. C510, IAPMO PS31 1015 B64.5 3⁄4" - 2"(LBV Models Only) Capacities As compiled from documented Foundation for Cross-Connection Control and Hydraulic Research at the University of Southern California lab tests. ∆Typical maximum system flow rate (7.5 feet/sec., 2.3 meters/sec.) kPa psi 83 12 69 10 55 8 41 6 28 4 14 2 0 0 ∆P 0 2 4 6 8 10 12 gpm 0 7.6 15.2 22.8 30.4 38 45.6 lpm 5 7.5 10 fps 1.5 2.3 3.0 mps ∆ ∆P * ∆P ∆ kPa psi 110 16 83 12 69 10 55 8 41 6 28 4 14 2 0 5 10 15 20 25 30 35 40 45 50 55 60 gpm 0 19 38 57 76 95 114 133 152 171 190 209 228 lpm 5 7.5 10 15 fps 1.5 2.3 3.0 4.6 mps ∆P ∆ kPa psi 96 14 83 12 69 10 55 8 41 6 28 4 14 2 0 0 0 10 20 30 40 50 60 70 80 90 100 110 120 gpm0 38 76 114 152 190 228 266 304 342 380 418 456 lpm 5 7.5 10 15 fps 1.5 2.3 3.0 4.6 mps kPa psi 83 12 69 10 55 8 41 6 28 4 14 2 0 0 ∆P 0 10 20 30 40 50 60 70 80 90 100 110 120 gpm 0 38 76 114 152 190 228 266 304 342 380 418 456 lpm 5 7.5 10 15 fps 1.5 2.3 3.0 4.6 mps ∆ ∆P ∆ kPa psi 83 12 69 10 55 8 41 6 28 4 14 2 0 0 0 25 50 75 100 125 150 175 200 gpm0 95 190 285 380 475 570 665 760 lpm 5 7.5 10 15 fps 1.5 2.3 3.0 4.6 mps 1⁄2" (15mm) 1" (25mm) 11⁄4" (32mm) 11⁄2" (40mm) 2" (50mm) kPa psi 152 22 124 18 96 14 69 10 41 6 14 2 3⁄4" (20mm) 0 5 10 15 20 25 30 35 40 45 50 gpm0 19 38 57 76 95 114 133 152 171 190 lpm 7.5 15 fps 2.3 4.6 mps ∆ Dimensions – Weights Size (dn) diMenSiOnS WeigHt A B C F G H I in. mm in. mm in. mm in. mm in. mm in. mm in. mm in. mm lbs. kgs. 1⁄2 15 10 254 45⁄8 117 27⁄16 62 5 127 33⁄8 85 25⁄16 59 21⁄16 52 4.5 2 3⁄4 20 111⁄8 282 4 102 31⁄8 79 63⁄16 157 37⁄16 87 21⁄8 54 15⁄16 33 5 2.3 1 25 131⁄4 337 51⁄8 130 4 102 71⁄2 191 33⁄8 85 111⁄16 43 111⁄16 43 12 5.4 11⁄4 32 163⁄8 416 5 127 35⁄16 84 91⁄2 241 5 127 3 76 2 50 15 6.8 11⁄2 40 163⁄4 425 47⁄8 124 31⁄2 89 93⁄4 248 513⁄16 148 31⁄8 79 211⁄16 68 15.86 7.2 2 50 191⁄2 495 61⁄4 159 4 102 133⁄8 340 61⁄8 156 37⁄16 87 211⁄16 68 25.75 11.7 H g iSuffix HC — Fire Hydrant Fittings dimension "A" = 231⁄2" (594mm) C B F A Strainer sold separately Pressure LossPressure LossPressure LossPressure LossPressure LossPressure LossFlow Rate Flow Rate Flow Rate Flow Rate Flow Rate Flow Rate ES-A-2000B 1322 © 2013 Ames Fire & Waterworks www.amesfirewater.com A Watts Water Technologies Company USA: Backflow- Tel: (916) 928-0123 • Fax: (916) 928-9333 Control Valves- Tel: (713) 943-0688 • Fax: (713) 944-9445 Canada: Tel: (905) 332-4090 • Fax: (905) 332-7068 5401152 - REV K • 2/15 PAGE 1 OF 3 Potter Electric Signal Company, LLC • St. Louis, MO • Tech Support: 866-956-0988 / Customer Service: 866-572-3005 • www.pottersignal.com RD13 Residential Riser Description The RD13 Riser (with NPT connectors) is constructed from Listed CPVC products suitable for fire sprinkler services subject to the limitations and installation requirements of Flameguard® CPVC pipe and Spears® CPVC fittings. The RD13 Riser incorporates a VSR-SG flow switch, gauge, and drain/test valve. The VSR-SG flow switch is equipped with union connection to facilitate the installation and removal of the switch in confined spaces. Installation 1. Using appropriate sealant, thread the female adapter on to the main water supply. Then glue the riser assembly to the female adapter. Pipe the drain connection to an adequate drain location capable of handling the drain discharge. The riser can be mounted in the horizontal or vertical position. Direction of flow is indicated in Fig. 1. The waterflow switch must be located on the top or on the side of the pipe when installed in the horizontal position. This will prevent debris from entering the throat of the waterflow switch which could interfere with proper operation. 2. Following CPVC manufacturer’s instructions for preparation and gluing of CPVC piping systems, glue the main riser to the main supply line for the sprinkler heads. NOTE: All glued connections must be completed and cured before the flowswitch is installed. (Continued on page 2). Features • Pre-assembled and pressure tested • Available in 1”,1 1/4”, 1 1/2”, & 2” nominal pipe size models • Female adapter ships loose so riser can be installed in a confined space • Fits in standard 2X4 construction walls Specifications subject to change without notice Do not over-tighten the union nut, hand tighten only. Use of a wrench may cause damage to the union nut. • Installation must be performed by qualified personnel and in accordance with all national and local codes and ordinances. • Shock hazard. Disconnect power source before servicing. Serious injury or death could result. • Risk of explosion. Not for use in hazardous locations. Serious injury or death could result. Flow Switch Technical Specifications Dimensions See Fig 2 Service Pressure 175 PSI (12,07 BAR) - UL Flow Sensitivity Range for Signal 4-10 GPM (15-38 LPM) - UL Maximum Surge 18 FPS (5.5 m/s) Contact Ratings Two sets of SPDT (Form C) 10.0 Amps at 125/250VAC 2.0 Amps at 30VDC Resistive 10 mAmps min. at 24VDC Resistive 10 m Amps min. at 24V DC Environmental Limitations Temperature range: 40°F-120°F (4.5°C-49°C)-UL Conduit Entrances Two knockouts provided for 1/2” conduit Listings UL, CUL CSFM Listed, and CE Marked Service Use Automatic Sprinkler NFPA-13 One or two family dwelling NFPA-13D Residential occupancy up to four stories NFPA-13R National Fire Alarm Code NFPA-72British Standard BS9251 5401152 - REV K • 2/15 PAGE 2 OF 3 Potter Electric Signal Company, LLC • St. Louis, MO • Tech Support: 866-956-0988 / Customer Service: 866-572-3005 • www.pottersignal.com RD13 Residential Riser Maintenance The VSR-SG waterflow switch should provide years of trouble-free service. The retard and switch assembly are easily field replaceable. In the unlikely event that either component does not perform properly, please order replacement retard switch assembly stock number 1029030. There is no maintenance required, only periodic testing and inspection.. Removal • To prevent accidental water damage, all control valves should be shut tight and the system completely drained before waterflow detectors are removed or replaced. • Turn off electrical power to the detector, then disconnect wiring. • Loosen nut on union fitting. • Lift detector clear of pipe. Retard Adjustment The delay can be adjusted by rotating the retard adjustment knob from 0 to the max setting (60-90 seconds). The time delay should be set at the minimum required to prevent false alarms. Important: The paddles have raised lettering that show the pipe size and the TEE manufacturer they are to be used with. The proper paddle must be used. The paddle must be properly attached and the screw that holds the paddle must be securely tightened. Fig 1 Installation (Continued) 3. A thread sealant shall be used in making threaded connections. Teflon® thread tape is the recommended sealant. Some thread sealants other than Teflon thread tape contain solvents or other materials that may be damaging to CPVC. For other types of thread sealants, which have been specifically investigated and confirmed to be “System Compatible”, refer to www.spearsmfg.com. Attach gauge to riser. Apply Teflon® tape to male fitting of gauge only. See Fig 1. 4. Check to make sure the proper paddle is installed on the switch. (Paddle size must match the riser pipe size and Tee manufacture.) 5. Install the flow switch to the RD13 Riser. Verify that the o-ring is properly positioned in its groove. Hand tighten the nut to the union after orienting the flow switch in the appropriate direction to detect waterflow. The paddle must not rub the inside of the Tee or bind in any way. The stem should move freely when operated by hand. See Fig. 1. NOTE: Do not leave switch cover off for an extended period of time. 6. The side of flow switch must be perpendicular with the riser piping. See Fig. 3. Testing The frequency of inspection and testing for the Model VSR-SG and its associated protective monitoring system, should be in accordance with applicable Codes and Standards and/or the authority having jurisdiction (manufacturer recommends quarterly or more frequently.) If provided, the inspector’s test valve (usually located at the end of the most remote branch line) should be used for test purposes. If there is no remote inspection test connection; a short length of hose may be connected to the discharge of the 1” drain line valve, or if the drain line is connected to a drain such as a slop sink or storm drain that will sufficiently handle the discharge of the main drain valve. The drain valve can be used to test the operation of the VSR-SG switch. A minimum flow of 10 GPM (38 LPM) is required to activate this switch. An orifice equal to the smallest sprinkler head orifice used in the system shall be attached to the drain line for testing purposes. Optional Cover Tamper Switch Mount so arrow on base points in direction of waterflow DO NOT LEAVE COVER OFF FOR EXTENDED PERIOD OF TIME Retard Adjusting Knob 1” Male Fitting on All Sizes Riser may be 1”, 1/4”, 1 1/2”, or 2” Waterfl o w 5401152 - REV K • 2/15 PAGE 3 OF 3 Potter Electric Signal Company, LLC • St. Louis, MO • Tech Support: 866-956-0988 / Customer Service: 866-572-3005 • www.pottersignal.com RD13 Residential Riser Dimensions Orientation Fig 2 Fig 3 D C B A E F 90° 3 1/2” Gauge (Shipped Loose) 1” NPT Drain Valve VSR-SG Flow Switch NPT Adaptor (Shipped Loose) (See Chart Below) *RD13 Risers (ASSEMBLED DIMENSIONS) Riser Size Model Number Part Number Dimension “A” Dimension “B” Dimension "C" Dimension "D"Dimension "E" Dimension "F" (in.)(mm.)(in.)(mm.)(in.)(mm.)(in.)(mm.)(in.)(mm.)(in.)(mm.) 1"RD13-100-1 1119067 16 406 15 3/4 400 14 7/8 378 14 5/8 371 12 1/4 311 10 1/2 267 1 1/4"RD13-125-1 1119077 16 5/8 422 16 1/2 419 15 1/2 394 15 3/8 391 12 1/2 318 10 5/8 270 1 1/2"RD13-150-1 1119087 N/A N/A 16 3/4 425 N/A N/A 15 5/8 397 12 3/4 324 10 3/4 273 2"RD13-200-1 1119097 N/A N/A 18 1/4 464 N/A N/A 16 7/8 429 13 3/8 340 11 1/8 283 Flow switch must be properly orientated. Side of cover must be perpendicular with the pipe. Improper orientation could delay or prevent notification of waterflow. Ordering Information Ordering Information Nominal Pipe Size Model Part Number 1"RD13 Riser 1119067 1 1/4"RD13 Riser 1119077 1 1/2"RD13 Riser 1119087 2"RD13 Riser 1119097 Optional: Cover Tamper Switch Kit, stock no. 0090148 Replaceable Components: Retard/Switch Assembly, stock no. 1029030 Gauge, Flow Switch, and NPT Adapter shipped loose in box. PRINTED IN USA PAGE 1 OF 4 VSR VANE TYPE WATERFLOW ALARM SWITCH WITH RETARD MFG. #5401146 - REV M 11/15 UL, CUL and CSFM Listed, FM Approved, LPCB Approved, For CE Marked (EN12259-5) / VdS Approved model use VSR-EU Service Pressure: 450 PSI (31 BAR) - UL Flow Sensitivity Range for Signal: 4-10 GPM (15-38 LPM) - UL Maximum Surge: 18 FPS (5.5 m/s) Contact Ratings: Two sets of SPDT (Form C) 10.0 Amps at 125/250VAC 2.0 Amps at 30VDC Resistive 10 mAmps min. at 24VDC Conduit Entrances: Two knockouts provided for 1/2" conduit. Individual switch compartments suitable for dissimilar voltages. Environmental Specifications: • NEMA 4/IP54 Rated Enclosure suitable for indoor or outdoor use with factory installed gasket and die-cast housing when used with appropriate conduit fitting. • Temperature Range: 40°F - 120°F, (4.5°C - 49°C) - UL • Non-corrosive sleeve factory installed in saddle. Service Use: Automatic Sprinkler NFPA-13 One or two family dwelling NFPA-13D Residential occupancy up to four stories NFPA-13R National Fire Alarm Code NFPA-72 • Installation must be performed by qualified personnel and in accordance with all national and local codes and ordinances. • Shock hazard. Disconnect power source before servicing. Serious injury or death could result. • Risk of explosion. Not for use in hazardous locations. Serious injury or death could result. Ordering Information Nominal Pipe Size Model Part Number 2"DN50 VSR-2 1144402 2 1/2"DN65 VSR-2 1/2 1144425 3"DN80 VSR-3 1144403 3 1/2"-VSR-3 1/2 1144435 4"DN100 VSR-4 1144404 5"-VSR-5 1144405 6"DN150 VSR-6 1144406 8"DN200 VSR-8 1144408 Specifications subject to change without notice. Optional: Cover Tamper Switch Kit, stock no. 0090148 Replaceable Components: Retard/Switch Assembly, stock no. 1029030 Waterflow switches that are monitoring wet pipe sprinkler systems shall not be used as the sole initiating device to discharge AFFF, deluge, or chemical suppression systems. Waterflow switches used for this application may result in unintended discharges caused by surges, trapped air, or short retard times. Potter Electric Signal Company, LLC • St. Louis, MO • Phone: 866-956-1211/Canada 888-882-1833 • www.pottersignal.com General Information The Model VSR is a vane type waterflow switch for use on wet sprinkler systems. It is UL Listed for use on a steel pipe; schedules 5 through 40, sizes 2" - 6" and is UL Listed and FM Approved for use on steel pipe; schedules 10 through 40, sizes 2" thru 8" (50 mm thru 200 mm). LPC approved sizes are 2" thru 8" (50 mm thru 200 mm). See Ordering Information chart. The VSR may also be used as a sectional waterflow detector on large systems. The VSR contains two single pole, double throw, snap action switches and an adjustable, instantly recycling pneumatic retard. The switches are actuated when a flow of 10 GPM (38 LPM) or more occurs downstream of the device. The flow condition must exist for a period of time necessary to overcome the selected retard period. Enclosure The VSR switches and retard device are enclosed in a general purpose, die-cast housing. The cover is held in place with two tamper resistant screws which require a special key for removal. A field installable cover tamper switch is available as an option which may be used to indicate unauthorized removal of the cover. See bulletin number 5401103 for installation instructions of this switch. Important: This document contains important information on the installation and operation of the VSR waterflow switches. Please read all instructions carefully before beginning installation. A copy of this document is required by NFPA 72 to be maintained on site. PRINTED IN USA MFG. #5401146 - REV M 11/15 PAGE 2 OF 4 VSR VANE TYPE WATERFLOW ALARM SWITCH WITH RETARD Installation (see Fig. 1) These devices may be mounted on horizontal or vertical pipe. On horizontal pipe they shall be installed on the top side of the pipe where they will be accessible. The device should not be installed within 6" (15 cm) of a fitting which changes the direction of the waterflow or within 24" (60 cm) of a valve or drain. NOTE: Do not leave cover off for an extended period of time. Drain the system and drill a hole in the pipe using a hole saw in a slow speed drill (see Fig. 1). Clean the inside pipe of all growth or other material for a distance equal to the pipe diameter on either side of the hole. Roll the vane so that it may be inserted into the hole; do not bend or crease it. Insert the vane so that the arrow on the saddle points in the direction of the waterflow. Take care not to damage the non-corrosive bushing in the saddle. The bushing should fit inside the hole in the pipe. Install the saddle strap and tighten nuts alternately to required torque (see the chart in Fig. 1). The vane must not rub the inside of the pipe or bind in any way. ADAPTER USE (2) 5180162 ADAPTERS AS SHOWN ABOVE DN50 ONLY ADAPTER 50mm 20mm ±2mm MAX. DWG# 1146-1F Fig. 1 NOTE: For copper or plastic pipe use Model VSR-CF. Retard Adjustment The delay can be adjusted by rotating the retard adjustment knob from 0 to the max setting (60-90 seconds). The time delay should be set at the minimum required to prevent false alarms (Flowing water activates device in one direction only.) DO NOT LEAVE COVER OFF FOR AN EXTENDED PERIOD OF TIME TIGHTEN NUTS ALTERNATELY MOUNT ON PIPE SO ARROW ON SADDLE POINTS IN DIRECTION OF WATERFLOW ROLL PADDLE IN OPPOSITE DIRECTION OF WATERFLOWDIRECTION OF WATERFLOW Hole must be drilled perpendicular to the pipe and vertically centered. Refer to the Compatible Pipe/Installation Requirements chart for size. Correct Incorrect Compatible Pipe/ Installation Requirements Model Nominal Pipe Size Nominal Pipe O.D. Pipe Wall Thickness Hole Size U-Bolt Nuts TorqueLightwallSchedule 10 (UL)Schedule 40 (UL)BS-1387 (LPC)DN (VDS) inch mm inch mm inch mm inch mm inch mm inch mm inch mm inch mm ft-lb n-m VSR-2 2 DN50 2.375 60.3 .065 1.651 0.109 2.77 0.154 3.91 0.142 3.6 0.091 2.3 1.25 + .125/- .062 33.0 ± 2.0 20 27 VSR-2 1/2 2.5 -2.875 73.0 .084 2.134 0.120 3.05 0.203 5.16 ---- VSR-2 1/2 -DN65 3.000 76.1 ------0.142 3.6 0.102 2.6 VSR-3 3 DN80 3.500 88.9 .083 2.108 0.120 3.05 0.216 5.49 0.157 4.0 0.114 2.9 2.00 ± .125 50.8 ± 2.0 VSR-3 1/2 3.5 -4.000 101.6 --0.120 3.05 0.226 5.74 ---- VSR-4 4 DN100 4.500 114.3 .084 2.134 0.120 3.05 0.237 6.02 0.177 4.5 0.126 3.2 VSR-5 5 -5.563 141.3 --0.134 3.40 0.258 6.55 ---- VSR-6 6 DN150 6.625 168.3 .115 2.921 0.134 3.40 0.280 7.11 0.197 5.0 0.157 4.0 VSR-8 8 DN200 8.625 219.1 --0.148 3.76 0.322 8.18 0.248 6.3 0.177 4.5 Do not trim the paddle. Failure to follow these instructions may prevent the device from operating and will void the warranty. Do not obstruct or otherwise prevent the trip stem of the flow switch from moving when water flows as this could damage the flow switch and prevent an alarm. If an alarm is not desired, a qualified technician should disable the alarm system. PRINTED IN USA PAGE 3 OF 4 VSR VANE TYPE WATERFLOW ALARM SWITCH WITH RETARD MFG. #5401146 - REV M 11/15 To remove knockouts: Place screwdriver at inside edge of knockouts, not in the center. DWG 1146-4 Fig. 2 Do not drill into the base as this creates metal shavings which can create electrical hazards and damage the device. Drilling voids the warranty. Fig. 4 Switch Terminal Connections Clamping Plate Terminal Fig. 3 Break out thin section of cover when wiring both switches from one conduit entrance. Testing The frequency of inspection and testing for the Model VSR and its associated protective monitoring system shall be in accordance with applicable NFPA Codes and Standards and/or the authority having jurisdiction (manufacturer recommends quarterly or more frequently). If provided, the inspector’s test valve shall always be used for test purposes. If there are no provisions for testing the operation of the flow detection device on the system, application of the VSR is not recommended or advisable. A minimum flow of 10 GPM (38 LPM) is required to activate this device. Advise the person responsible for testing of the fire protection system that this system must be tested in accordance with the testing instructions. Fig. 6 Mounting Dimensions DWG. 1146-14 3.50 in (89.0 mm) 2.34 in (59.4 mm) PIPE DIA. + 5.25 in (+ 133.4 mm) 5.56 in (141.2 mm)2.00 in (50.8 mm) U-BOLT NUT U-BOLT WASHER PIPE SADDLE PIPE PLASTIC PADDLE U-BOLT NOMINAL PIPE DIA. +1.75 in (+44.5 MM) FOR DN 50 – DN 65 2–2.5 in NOMINAL PIPE DIA. +2.125 in (+54.0 MM) FOR DN 80 – DN 200 3–8 in DWG 1146-15 GREEN GROUND SCREWS Fig. 7 An uninsulated section of a single conductor should not be looped around the terminal and serve as two separate connections. The wire must be severed, thereby providing supervision of the connection in the event that the wire become dislodged from under the terminal. Failure to sever the wire may render the device inoperable risking severe property damage and loss of life. Do not strip wire beyond 3/8" of length or expose an uninsulated conductor beyond the edge of the terminal block. When using stranded wire, capture all strands under the clamping plate. Notes: 1. The Model VSR has two switches, one can be used to operate a central station, proprietary or remote signaling unit, while the other contact is used to operate a local audible or visual annunciator. 2. For supervised circuits, see “Switch Terminal Connections” drawing and warning note (Fig. 4). Fig. 5 Typical Electrical Connections LOAD TO BELLNEUTRAL FROM BELL CONNECTOR EOL (End Of Line Resistor) BELLNEUTRAL FROM BREAKER BREAKER LINE FROM BREAKER NOTE: When connecting to a UL Listed control panel, use the panel’s resistor value for circuit supervision. PRINTED IN USA MFG. #5401146 - REV M 11/15 PAGE 4 OF 4 VSR VANE TYPE WATERFLOW ALARM SWITCH WITH RETARD Removal of Waterflow Switch • To prevent accidental water damage, all control valves should be shut tight and the system completely drained before waterflow detectors are removed or replaced. • Turn off electrical power to the detector, then disconnect wiring. • Loosen nuts and remove U-bolts. • Gently lift the saddle far enough to get your fingers under it. With your fingers, roll the vane so it will fit through the hole while continuing to lift the waterflow detector saddle. • Lift detector clear of pipe. Fig. 8 Retard/Switch Assembly Replacement (See Fig. 8) The Retard/Switch Assembly is field-replaceable without draining the system or removing the waterflow switch from the pipe 1. Make sure the fire alarm zone or circuit connected to the waterflow switch is bypassed or otherwise taken out of service. 2. Disconnect the power source for local bell (if applicable). 3. Identify and remove all wires from the waterflow switch. 4. Remove the (2) mounting screws holding retard/switch assembly to the base. Do not remove the (2) retard housing screws. 5. Remove the retard assembly by lifting it straight up over the tripstem. 6. Install the new retard assembly. Make sure the locating pins on the retard/switch assembly fit into the locating pin bosses on the base. 7. Re-install the (2) original mounting screws. 8. Reconnect all wires. Perform a flow test and place the system back in service. Maintenance Inspect detectors monthly. If leaks are found, replace the detector. The VSR waterflow switch should provide years of trouble-free service. The retard and switch assembly are easily field replaceable. In the unlikely event that either component does not perform properly, please order replacement retard switch assembly stock #1029030 (see Fig. 8). There is no maintenance required, only periodic testing and inspection. DWG# 1146-10 BREAK OUT THIN SECTION OF COVER WHEN WIRING BOTH SWITCHES FROM ONE CONDUIT ENTRANCE. DO NOT REMOVE (2) RETARD HOUSING SCREWS REMOVE (2) ORIGINAL MOUNTING SCREWS HOLDING RETARD/SWITCH ASSEMBLY TO BASE RETARD/SWITCH ASSEMBLY (2) ORIGINAL MOUNTING SCREWS (2) LOCATING PINS (2) LOCATING PIN BOSSES IN BASE BASE BELLS PBA-AC & MBA-DC 5400776 - REV Z • 11/17 PAGE 1 OF 2 Potter Electric Signal Company, LLC • St. Louis, MO • Phone: 800-325-3936 • www.pottersignal.com Description These vibrating type bells are designed for use as fire or general signaling devices. They have low power consumption and high decibel ratings. The unit mounts on a standard 4” (101mm) square electrical box for indoor use or on a model BBK-1 or HC-BB weatherproof backbox for outdoor applications. Weatherproof backbox model BBK- 1 or HC-BB, Stock No. 1500001. Notes 1. Minimum dB ratings are calculated from integrated sound pressure measurements made at Underwriters Laboratories as specified in UL Standard 464. UL temperature range is -30° to 150°F (-34° to 66°C) 2. Typical dB ratings are calculated from measurements made with a conventional sound level meter and are indicative of output levels in an actual installation. 3. ULC only applies to MBA DC bells. Technical Specifications Dimensions 6” (150mm), 8” (200mm) and 10” (250mm) Enclosure Cover: Steel Finish: Red Powder Coat Base: non-corrosive composite material All parts have corrosion resistant finishes Model BBK-1 or HC-BB weatherproof backbox (optional) Voltages Available 24VAC 120VAC 12VDC (10.2 to 15.6) Polarized 24VDC (20.4 to 31.2) Polarized Environmental Limitations Indoor or outdoor use (See Note 1) -40° to 150°F (-40° to 66°C) (Outdoor use requires weatherproof backbox.) Termination AC Bells - 4 No. 18 AWG stranded wires DC Bells - Terminal strip Service Use NFPA 13, 72, local AHJ *Specifications subject to change without notice. Features • Listed for indoor and outdoor use • Outdoor use requires BBK-1 or HC-BB weatherproof back box • Indoor use mounts directly to standard 4” box • Low current draw • High dB output • AC and DC models • DC models are motor driven, polarized, and have built in transient protection for supervised alarm circuits • Available in 6”, 8” and 10” sizes In outdoor or wet installations, bell must be mounted with weatherproof backbox, BBK-1 or HC-BB. Standard electrical boxes will not provide a weatherproof enclosure. If the bell and/or assembly is exposed to moisture, it may fail or create an electrical hazard. • Installation must be performed by qualified personnel and in accordance with all national and local codes and ordinances. • Shock hazard. Disconnect power source before servicing. Serious injury or death could result. • Risk of explosion. Not for use in hazardous locations. Serious injury or death could result. R * ULC on MBA-DC Only Size inches (mm) Voltage Model Number Stock Number Current (Max.) Typical dB at 10 ft. (3m) (2) Minimum dB at 10 ft. (3m) (1) 6 (150)12VDC MBA-6-12 1750070 .12A 85 76 8 (200)12VDC MBA-8-12 1750080 .12A 90 77 10 (250)12VDC MBA-10-12 1750060 .12A 92 78 6 (150)24VDC MBA-6-24 1750100 .06A 87 77 8 (200)24VDC MBA-8-24 1750110 .06A 91 79 10 (250)24VDC MBA-10-24 1750090 .06A 94 80 6 (150)24VAC PBA246 1806024*.17A 91 78 8 (200)24VAC PBA248 1808024*.17A 94 77 10 (250)24VAC PBA2410 1810024*.17A 94 78 6 (150)120VAC PBA1206 1806120*.05A 92 83 8 (200)120VAC PBA1208 1808120*.05A 99 84 10 (250)120VAC PBA12010 1810120*.05A 99 86 All DC bells are polarized and have built-in transient protection. * Does not have ULC listing. * 5400776 - REV Z • 11/17 PAGE 2 OF 2 Potter Electric Signal Company, LLC • St. Louis, MO • Phone: 800-325-3936 • www.pottersignal.com BELLS PBA-AC & MBA-DC Wiring Rear View Installation Bell Dimension Inches (mm) Fig 1 Fig 3 2 11/16” (68 mm)DWG# 776-1 10” (250 mm)8” (200 mm)6” (150 mm) 5 3/4” (146 mm) 1 5/8” (41 mm) DWG# 776-2 3 3/8” (86 mm) 4 1/4” (108 mm) 3 3/8” (86 mm) 5” (127 mm) Weatherproof Backbox Dimensions Inches (mm) Fig 2 The bell shall be installed in accordance with NFPA 13, 72, or local AHJ. The top of the device shall be no less than 90” AFF and not less than 6” below the ceiling. 1. Remove the gong. 2. Connect wiring (see Fig. 3). 3. Mount bell mechanism to backbox (bell mechanism must be mounted with the striker pointing down). 4. Reinstall the gong (be sure that the gong positioning pin, in the mechanism housing, is in the hole in the gong). 5. Test all bells for proper operation and observe that they can be heard where required (bells must be heard in all areas as designated by the authority having jurisdiction). MODEL BBK-1 OR HC-BBFailure to install striker down will prevent bell from ringing. NOTES: 1. OBSERVE POLARITY TO RING D.C. BELLS.2. RED WIRES POSITIVE (+).3. BLACK WIRES NEGATIVE (-).4. EOL RESISTOR IS SUPPLIED BY FIRE ALARM CONTROL PANEL. NOTES: 1. WHEN USING A.C. BELLS, TERMINATE EACH EXTRA WIRE SEPERATELY AFTER LAST BELL.2. END-OF-LINE RESISTOR IS NOT REQUIRED ON AC BELLS . NOTES: 1. OBSERVE POLARITY TO RING D.C. BELLS.2. RED WIRES POSITIVE (+).3. BLACK WIRES NEGATIVE (-).4. EOL RESISTOR IS SUPPLIED BY FIRE ALARM CONTROL PANEL. NOTES: 1. WHEN USING A.C. BELLS, TERMINATE EACH EXTRA WIRE SEPERATELY AFTER LAST BELL.2. END-OF-LINE RESISTOR IS NOT REQUIRED ON AC BELLS .