Longmire Court Sewer ExtensionLONGMIRE COURT SEWER EXTENSION YELM, WA. 98597 SECTION 19, TOWNSHIP 17, RANGE 2E, W.M. "CALL UNDERGROUND LOCATE AT 811 BEFORE YOU DIG" PROJECT SPECIFICATIONS DEWATERING ABBREVIATIONS LEGEND & LINETYPES THE WORK ON THIS PROJECT SHALL BE ACCOMPLISHED IN FOUNDATIONS, UTILITY TRENCHES, AND ALL OTHER PARTS OF THE AC ASPHALT CONCRETE ACCORDANCE WITH THE FOLLOWING: CONSTRUCTION SITE SHALL BE DEWATERED AND KEPT FREE OF STANDING WATER AND SATURATED CONDITIONS AS NECESSARY FOR BCP BEGIN CURB RETURN 1) THE MOST CURRENT VERSION OF THE WASHINGTON STATE THE PROPER EXECUTION OF THE WORK. THE CONTRACTOR SHALL EXISTING PROPOSED if LOCAT" DEPARTMENT OF TRANSPORTATION STANDARD SPECIFICATIONS FOR FURNISH, INSTALL, OPERATE, AND MAINTAIN ALL DRAINS, SUMPS, BM BENCHMARK ROAD, BRIDGE, AND MUNICIPAL CONSTRUCTION PUMPS, AND ALL OTHER EQUIPMENT REQUIRED TO PROPERLY DEWATER RIGHT-OF-WAY LINE THE SITE AS SPECIFIED. DEWATERING SYSTEMS THAT CAUSE A LOSS BVC BEGIN VERTICAL CURB 01" 2) THE MOST CURRENT EDITION OF THE MANUAL ON UNIFORM TRAFFIC OF SOIL FINES FROM FOUNDATION AND HARDSCAPE AREAS WILL NOT ago PROPERTY LINE CONTROL DEVICES FOR STREETS AND HIGHWAYS (MUTCD) BE PERMITTED. CB CATCH BASIN CENTERLINE 3) THE MOST CURRENT EDITION OF THE INTERNATIONAL BUILDING CODE (IBC) OCIP CAST IRON PIPE UTILITIES LCATE NOTE EASEMENT LINE THE LOCATION OF EXISTING UTILITIES SHOWN HEREON IS BASED ON CL CENTERLINE - — --- — — — — — --- — — ®_ - - — — — — — — — — — — — — — - SA WOU T LINE 4) THE MOST CURRENT EDITION OF THE AUTHORITY HAVING CMP CORRUGATED METAL PIPE > JURISDICTION DEVELOPMENT GUIDELINES AND PUBLIC STANDARDS INFORMATION OBTAINED FROM THE TOPOGRAPHIC SURVEY. J.E. GIBSON uj CONSULTING ASSUMES NO RESPONSIBILITY AND/OR LIABILITY OF EXISTING EDGE OF PAVEMENT/CURB LINE THE CONTRACTOR SHALL OBTAIN COPIES OF THESE PUBLICATIONS AT UTILITIES SHOWN OR NOT SHOWN HEREON. CONTRACTOR IS ADVISED TO Co CLEANOUT THE CONTRACTOR'S OWN EXPENSE. VERIFY THE EXACT SIZE, DIAMETER, DEPTH, AND LOCATION OF EXISTING - — — — — — — — — — — — — — - EDGE OF GRAVEL LINE UTILITIES PRIOR TO STARTING CONSTRUCTION ACTIVITIES. CONTRACTOR CATV CATV COMMUNICATIONS THE CONTRACTOR IS RESPONSIBLE FOR PROVIDING ALL LABOR, SHALL CALL FOR UNDERGROUND LOCATES AT 1-800-424-5555 PRIOR SIDEWALK LINE V\N R DIAM DIAMETER MATERIALS, TOOLS, EQUIPMENT, TRANSPORTATION, SUPPLIES, AND TO STARTING CONSTRUCTION ACTIVITIES. y BUILDING LINE WASjj 41 INCIDENTALS REQUIRED TO COMPLETE ALL WORK SHOWN ON THESE DIP DUCTILE IRON PIPE I:r 0 DRAWINGS AND TO OBTAIN ACCEPTANCE BY THE AUTHORITY HAVING VICINITY MAP _x_x_x_x FENCE LINE In z JURISDICTION AND THE PROJECT OWNER. RECORD DRAWINGS EE ELECTRICAL NOT TO SCALE ce J.E. GIBSON CONSULTING IS REQUIRED BY THE THE AUTHORITY HAVING _w w WATER LINE 0 4Q ANY PROPOSED ALTERATIONS BY THE CONTRACTOR AFFECTING THE 10 42010 JURISDICTION TO PROVIDE RECORD DRAWINGS PRIOR TO ACCEPTANCE, ECR END CURB RETURN REQUIREMENTS AND INFORMATION IN THESE DRAWINGS SHALL BE SUBMITTED TO THE ENGINEER OF RECORD IN WRITING FOR APPROVAL. J.E. GIBSON CONSULTING WILL NOT CERTIFY RECORD DRAWINGS UNLESS sl.; SlIs ss ss SEWER LINE jt, A REPRESENTATIVE OF THE COMPANY HAS INSPECTED ACTUAL EL ELEVATION INSTALLATION OF UTILITIES PRIOR TO BACKFILLING. EVC END VERTICAL CURB FM FM FORCE MAIN LINE CONTRACTOR LIABILITY NOTE Vi THE CONTRACTOR SHALL MAINTAIN ONE SET OF THE APPROVED EXIST EXISTING ___sD ----- SD SO ----- SID SD SD STORM LINE DRAWINGS THAT SHALL INCLUDE RED LINE MARKUPS (LEGIBLE) OF ANY THE CONTRACTOR SHALL ASSUME SOLE AND COMPLETE ALTERATIONS TO THE DESIGN. THE RED LINE MARKINGS SHALL BE DI TCH LINE RESPONSIBILITY FOR JOB SITE COND111ONS DURING THE COURSE OF FIFE FINISHED FLOOR ELEVATION co SUBMITTED TO THE ENGINEER OF RECORD UPON PROJECT COMPLETION. CONSTRUCTION OF THIS PROJECT, INCLUDING SAFETY OF ALL CN CD PERSONS AND PROPERTY. THIS REQUIREMENT SHALL APPLY FG FINISH GRADE ROADWAY STRIPE LINE C14 CONTINUOUSLY AND NOT BE LIMITED TO NORMAL WORKING HOURS.6� w IAIODV lki TUC: Din -UT OF lA/AV ui ui THE CONTRACTOR SHALL DEFEND, INDEMNIFY, AND HOLD J.E. GIBSON SHEET INDEX FH FIRE HYDRANT v UA,', LINE 1 CV -01 CONSULTING HARMLESS FROM ANY AND ALL LIABILITY, REAL OR 2 UT -01 STEP SEWER PLAN AND PROFILE 3 UT -02 SEWER NOTES AND DETAILS ALLEGED, IN CONNECTION WITH THE PERFORMANCE OF WORK ON THIS CONTRACTOR SHALL OBTAIN RIGHT-OF-WAY PERMIT AND SHALL SUBMIT FL FLOWLINE / FLANGE p p POWER LINE LINEAL FEET PROJECT, EXCEPTING FOR LIABILITY ARISING FROM THE SOLE A TRAFFIC CONTROL PLAN TO THE AUTHORITY HAVING JURISDICTION FIRE HYDRANT ui NEGLIGENCE OF J.E. GIBSON CONSULTING. PRIOR TO STARTING CONSTRUCTION ACTIVITIES, ALL WORK WITHIN THE FM FORCE MAIN AFI ----`-OH. ---- OH op op OVERHEAD POWER LINE MANHOLE RIGHT-OF-WAY SHALL CONFORM TO THE AUTHORITY HAVING JURISDICTION'S STANDARDS. G GAS _T -0H T -OH OVERHEAD PHONE LINE rr, uj Lu U GRADING NOTEGM SANITARY SEWER: CITY OF YELM PROJECT INFORMATION ANY CUT AND FILL QUANTITIES, IF SHOWN ON THESE DRAWINGS, ARE GASMETER -----T-----T-----T-----T-----T— TELEPHONE LINE -i m LU en ESTIMATED IN-PLACE VOLUMES AND ARE FOR PLANNING PURPOSES SUBMITTING A BID AND SHALL CONTACT THE ENGINEER OF RECORD IF GB GB -------C - c— c CABLE ICOMMUNICATIONS LINE MECHANICAL JOINT ONLY. IT IS THE CONTRACTOR'S RESPONSIBILITY TO VERIFY QUANTITIES APPLICANT, C & E DEVELOPMENTS LLC GATE VALVE I U') ry AND APPLY SHRINK AND /0R SWELL FArTOF?-, THERE IS A DISCREPANCY. HP HIGH POINT STORM CATCH BASIN SHEET INDEX SHEET NO. SHEET REF. SHEET DESCRIPTION 1 CV -01 COVER SHEET 2 UT -01 STEP SEWER PLAN AND PROFILE 3 UT -02 SEWER NOTES AND DETAILS TOPOGRAPHIC NOTE YELM, WA 98597 LF PARCEL NUMBER: 69310100000 (LOT TO BE SERVED) SITE ADDRESS: PRAIRIE MEW ESTATES OPEN SPACE TRACT L M co co U- 0 PARCEL NUMBER: 69310100000 (LOT TO BE SERVED) SITE ADDRESS: PRAIRIE MEW ESTATES OPEN SPACE TRACT L CURVE LENGTH STORM MANHOLE w �-< _j _j co U) co r -- TOPOGRAPHIC NOTE YELM, WA 98597 LF LINEAL FEET FIRE HYDRANT ui z Lo z 0 00 N TOPOGRAPHIC INFORMATION SHOWN ON THESE DRAWINGS WERE PROVIDED BY A THIRD PARTY SURVEYOR. THE CONTRACTOR SHALL PARCEL AREA: 0.33 ACRES MH MANHOLE WATER METER rr, uj Lu U w m cy) CL '�t VERIFY TOPOGRAPHIC INFORMATION IN THE FIELD PRIOR TO SANITARY SEWER: CITY OF YELM -i m LU en < 0 > - SUBMITTING A BID AND SHALL CONTACT THE ENGINEER OF RECORD IF mi MECHANICAL JOINT GATE VALVE I U') ry o < 0 C:) THERE IS A DISCREPANCY. WATER, CITY OF YELM Lu - T_ Ct qt FIRE DISTRICT: SE THURSTON FIRE AUTHORITY PC POINT OF CURVATURE THRUST BLOCKING �> 0 0 0 w (D I c) > z — ro w Z EROSION CONTROL NOTE FLOODZONE: N / A PI POINT OF INTERSECTION WATER BENDS LIJ 0:� n EROSION CONTROL MEASURES ARE NOT LIMITED TO THE TO THE ITEMS PL PROPERTY LINE WATER TEE0 W. 06 m DATUM NOTE ON THESE DRAWINGS. THE CONTRACTOR IS RESPONSIBLE FOR THE INSTALLATION AND MAINTENANCE OF ALL EROSION CONTROL MEASURES. POB POINT OF BEGINNING SEWER MANHOLE z 0 NO SILTATION OF EXISTING OR PROPOSED STORMWATER FACILITIES SHALL BE ALLOWED, CARE SHALL BE TAKEN TO PREVENT MIGRATION POC POINT OF CONNECTION STORM/SEWER CLEANOUT OF SILTS TO OFF-SITE PROPERTIES. ALL DISTURBED EARTH CAUSED BY PT POINT OF TANGENCY CONTRACTOR'S ACTIVITIES SHALL BE RESTORED IN ACCORDANCE WITH THE LANDSCAPING PLANS OR HYDROSEEDED IF NO LANDSCAPING PLANS PVC POLYVINYL CHLORIDE EXIST. R RADIUS IF DISCHARGING TO WATERS OF THE STATE AND DISTURBING MORE THAN ONE (1) OF LAND, THE CONTRACTOR IS RESPONSIBLE FOR RCP REINFORCED CONCRETE PIPE APPLYING AND SECURING COVERAGE UNDER WSDOE'S NPDES, GENERAL PERMIT, THE CONTRACTOR IS HEREBY NOTIFIED THAT IT CAN TAKE UP R/W RIGHT-OF-WAY TO SIXTY (60) DAYS TO ACQUIRE COVERAGE, VERTICAL DATUM. NGVD 29 - TOPOGRAPHIC INFORMATION HAS BEEN OBTAINED FROM THURSTON COUNTY GEODATA.ORG WEBSITE AND CITY OF YELM RECORD DRAWINGS FOR COATES ROADWAY IMPROVEMENTS RD ROOF DRAIN ra REMOVAL & REPLACEMENT OF SS SD SANITARY SEWER STORM SEWER I� Ln Ci UNSUITABLE MATERIALS rn STA STATION WHENEVER EXCAVATING ACTIVITIES ON-SITE EXPOSE PEAT, SOFT LEGAL DESCRIPTION 0 00 CLAY, QUICKSAND, OR OTHER UNSUITABLE FOUNDATION MATERIAL, STEP SEPTIC TANK EFFLUENT PUMP Ln SUCH MATERIAL SHALL BE REMOVED TO THE DEPTH DIRECTED BY THE THIS PROJECT DOES NOT HAVE A LEGAL DESCRIPTION. ALL WORK WILL 0)00 < GEOTECHNICAL ENGINEER AND BACKFILLED WITH SUITABLE FOUNDATION BE DONE WITH IN THE CITY OF YELM LONGMIRE COURT RIGHT OF WAYS. STD DTL STANDARD DETAIL MATERIAL. Q T TELEPHONE UNSUITABLE MATERIAL SHALL BE REMOVED FROM THE SITE AND HAULED TO A CONTRACTOR PROVIDED WASTE SITE, THE CONTRACTOR TB THRUST BLOCK00 SHALL FURNISH AND PLACE SUITABLE MATERIAL MEETING THE F" REQUIREMENTS OF THE STANDARD SPECIFICATIONS AND THE IBC. Tc TYP TOP OF CURB TYPICAL co STORM DRAINAGE NOTE SURVEY UTILITY NOTE UGP UNDERGROUND POWER TO PROTECT STORMWATER FACILITIES FROM SEDIMENTATION, THE UTILITIES SHOWN HEREON ARE FROM MAPPING VISIBLE SURFACE CONTRACTOR SHALL CONNECT THE FACILITY(IES) TO THE STORM APPURTENANCES, MAPPING UTILITY PAINT MARKS FROM A UTILITY W WATER CONVEYANCE SYSTEM AFTER SITE WORK, ROADS, UTILITIES, LOCATING SERVICE, AND USING RECORD UTILITY SYSTEM MAPS DRAWING NO: PERMANENT EROSION CONTROL MEASURES, AND FINAL LANDSCAPING PROVIDED BY OTHERS, BURIED UTILITIES ARE ONLY SHOWN AS wM WATER METER CV -01 ARE IN PLACE. APPROXIMATE AND SHOULD BE VERIFIED BEFORE CONSTRUCTION SHEET ILIO WV WATER VALVE 1 OF 3 RESTORE PIPE TRENCHING AND ASPHALT PATCHING. SEE COY DETAIL 5-3 ON SHEET UT -02 EDGE OF EX. PA VEMEN T 0 20 40 SCALE IN FEETSTA 1+64.54, 2,5' LT BEGIN ASPHALT SAWCUT AND PAVEMENT PATCHING, SEE COY DETAIL 5-3 FOR PATCHING DETAILS CONTRACTOR TO FIELD LOCATE EX. WATER SERVICES AND PROTECT DURING SEWER MAIN INSTALLATION 2,5.0'. tk SEC. 19, T17N., R2E., W.M. it 58! 8!r -`38' 0 0 .00*E 72.00' 25.0 EX. 2" STEP MAIN 2.5' 55' RADIUS 15. 8, EX. FH 41 INSTALL: 231 LF OF 2' STEP SEWEI? MAIN. SEE SANITARY SEWER NOTES FOR EX. 6m WATERMAIN MAIN SPECIFICATIONS. 66.0' STA. 1+66.04, 2.5' LT REMOVE EXIS17NG 2m STEP SEWER MAIN CAP. q°' �, CONNECT.• 2" STEP SEWER MAIN AND INSTALL PER THIS PLAN ry 'A )X", A 4f STA. 3+91.00, 14.58' RT 1" STEP SERVICE BEND SEE COY DETAIL 5-1 FOR PIPE TYPE AND BEND REQUIREMENTS STA. 3+91.00, 25' LT INSTALL: 1-1" STEP SEWER SERVICE. SEE COY DETAIL 5-1 ON SHEET UT -02. STA. 3+95.00, 2.51 LT INSTALL: END OF LINE CLEANOUT SEE COY DETAIL 5-20 ON SHEET UT -02. STA, 3+98.97, 25'LT END ASPHALT SAWCUT AND ASPHALT PATCHING SEE COY DETAIL 5-3 FOR PATCHING DETAILS SIA. 3+95.00, 16.09' RT END ASPHALT SAWCUT AND ASPHALT PATCHING SEE COY DETAIL 5-3 FOR PATCHING DETAILS STA. 4+06.00, 20.25' RT INSTALL: f* SINGLE STEP SERVICE "ONNECTION. SEE COY DETAIL 5 -ION SHEET UT -02, cn cn w �ul V\JV A R 0 C.) y WASy 0 z 42010 E9 Gj sTe?, (0) INV A 4) 5 4� CALL BEFORE YOU DIG z E' °p '� " "- � "-� "'� w� "w,�` �� � .,� ''` THE CONTRACTOR SHALL BE FULLY RESPONSIBLE FOR THE LOCATION 0 AND PROTECTION OF ALL EXISTING UTILITIES. THE CONTRACTOR SHALL Z: VERIFY ALL UTILITY LOCATIONS PRIOR TO CONSTRUCTION BY CALLING 0 uj C.0 THE UNDERGROUND LOCATE LINE AT (800) 424-5555 A MINIMUM OF 0- F- z Lr) 48 HOURS PRIOR TO ANY EXCAVATION. m re Z 0 oo 04 :z ui uj 01) cr) < (L < C) ""t 0- 0 UJI (D uj Lu > Z ro LJJWU) cr CL WUJ 0 t7) oz pd m C) 346.0 — 346.0 344.0---.-: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . EX LONGMIRE ST PAVEMENT GRADE, . . . . . . . . . . . . . . . . . . . . . . . . . . . 7JA A 177. V • STA. 0+00.00, 2.5' LTSTA. 3+91.00, 25' LT. REMOVE EAIS17NG 2- S7gP SEWER I- 'STEP SERVICE CONNECTION SEE GOY DETAIL 5-1 ON SHEET vil 342.0 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . cM . . . . . . . . . . . . . MAINCAP . . . . . . . . . . . . . . . . . . . . . . ttT-02 . .. . . . . 342.0 CONNECT 2" STEP SEWER MAIN AND 5' MIN COVER r4 Ln Ln INSTALL PER THIS PLAN ro 340.0 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 340.0 rn 00 Ln EX. 2* STEP SEWER MAIN- 731 LF 2- STEP SEWER MAIN • 00 p C) STA. 3+95.00, 2.5' LT INSTALL: z 338.0 �EX 2'. �SJEP . . . . . . . . . . . . . . . . . . . . . . . . . . tAID-OF LINE' CLEAROUT -Ste J38.0 iF SEWER MAIN uj 1 !20' HORIZ COY DETAIL 5-20 ON SHEET UT -02. 10 VERT x 0 336.0 1 1 1 336.0 1+50 2+00 2+50 3+00 3+50 44-00 LONGMIRE COURT DRAW14G NO: UT -01 SHEET NO: 2 OF 3 rWON- ll'i 1 li' • �l ■kal i �mw o1 A. ALL WORKMANSHIP AND MATERIALS SHALL BE IN ACCORDANCE WITH CITY OF YELM STANDARDS AND THE MOST CURRENT COPY OF THE STATE OF WASHINGTON STANDARD SPECIFICATIONS FOR ROAD, BRIDGE AND MUNICIPAL CONSTRUCTION (WSOOTIAPWA). B. ALL APPROVALS AND PERMITS REQUIRED BY THE CITY OF YELM SHALL BE OBTAINED BY THE CONTRACTOR PRIOR TO THE START OF CONSTRUCTION. C: IF CONSTRUCTION IS TO TAKE PLACE IN THE COUNTY RIGHT-OF-WAY, THE CONTRACTOR SHALL NOTIFY THE COUNTY AND OBTAIN ALL THE REQUIRED APPROVALS AND PERMITS D. A PRECONSTRUCTION MEETING SHALL BE HELD WITH THE CITY OF YELM PRIOR TO THE START OF CONSTRUCTION. E. THE CITY OF YELM SHALL BE NOTIFIED A MINIMUM OF 48 HOURS IN ADVANCE OF A TAP CONNECTION TO AN EXISTING MAIN. A CITY REPRESENTATIVE SHALL BE PRESENT AT THE TIME OF THE TAP. F. THE CONTRACTOR SHALL BE FULLY RESPONSIBLE FOR THE LOCATION AND PROTECTION OF ALL EXISTING UTILITIES THE CONTRACTOR SHALL VERIFY ALL UTILITY LOCATIONS PRIOR TO CONSTRUCTION BY CALLING THE UNDERGROUND LOCATE LINE AT 1-800-424-5555 A MINIMUM OF 48 HOURS PRIOR TO ANY EXCAVATION. G SIDE SEWER SERVICES SHALL BE PVC, ASTM D 3034 SDR 35 WITH FLEXIBLE GASKETED OR SOLVENT WELD JOINTS. H. ALL PLASTIC PIPE AND SERVICES SHALL BE INSTALLED WITH CONTINUOUS TRACER TAPE, INSTALLED 12" TO 18" UNDER THE PROPOSED SUBGRADE, THE MARKER SHALL BE PLASTIC NON -BIODEGRADABLE, METAL CORE OR BACKING MARKED "SEWER" WHICH CAN BE DETECTED BY A STANDARD METAL DETECTOR. IN ADDITION, STEP SYSTEMS AND FORCE MAINS SHALL BE INSTALLED WITH 14 GAUGE, HEAVY COATED OF DIRECT BURY COPPER WIRE WRAPPED AROUND ALL PLASTIC PIPE, BROUGHT UP AND TIED OFF AT VALVE BODY. TAPE SHALL BE TERRA TAPE "D" OR APPROVED EQUAL. THE TAPE AND WIRE SHALL BE FURNISHED BY THE CONTRACTOR. I. ALL BURIED POWER FOR STEP SYSTEMS SHALL BE INSTALLED WITH CONTINUOUS TRACER TAPE INSTALLED 12 ABOVE THE BURIED POWER. THE MARKER SHALL BE PLASTIC NON -BIODEGRADABLE, METAL CORE BACKING MARKED `POWER". TAPE SHALL BE FURNISHED BY CONTRACTOR. J. BEDDING OF THE SEWER MAIN AND ALL APPURTENANCES SHALL BE SAND AND COMPACTION OF THE BACKFILL MATERIAL SHALL BE REQUIRED IN ACCORDANCE WITH THE ABOVE MENTIONED SPECIFICATION (SEE GENERAL NOTE 5.60-A). K. TEMPORARY STREET PATCHING SHALL BE ALLOWED FOR AS APPROVED BY THE CITY ENGINEER. TEMPORARY STREET PATCHING SHALL BE PROVIDED BY PLACEMENT AND COMPACTION OF 2 INCH MINIMUM ASPHALT CONCRETE COLD MIX. CONTRACTOR SHALL BE RESPONSIBLE FOR MAINTENANCE AS REQUIRED. ENGINEERING SPECIFICATIONS AND STANDARD DETAILS - 1210912019 5 L. EROSION CONTROL MEASURES SHALL BE TAKEN BY THE CONTRACTOR DURING CONSTRUCTION TO PREVENT INFILTRATION OF EXISTING AND PROPOSED STORM DRAINAGE FACILITIES AND ROADWAYS M. PROVIDE TRAFFIC CONTROL PLAN(S) IN ACCORDANCE WITH THE MANUAL ON UNIFORM TRAFFIC CONTROL DEVICES (MUTCD) AS REQUIRED. N. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO HAVE A COPY OF THESE APPROVED PLANS ON CONSTRUCTION SITE AT ALL TIMES 0. ANY CHANGES TO THE DESIGN SHALL FIRST BE REVIEWED AND APPROVED BY THE CITY OF YELM, P. ALL STEP MAINS SHALL BE HYDROSTATICALLY TESTED IN CONFORMANCE WITH THE ABOVE -REFERENCED SPECIFICATION FOR TESTING WATER MAINS (SEE NOTE 1.) IN ADDITION, ALL STEP MAINS SHALL BE PIGGEDICLEANED 1N THE PRESENCE OF THE CITY INSPECTOR PRIOR TO PLACING STEP MAIN IN SERVICE Q. PRIOR TO BACKFILL ALL MAINS AND APPURTENANCES SHALL BE INSPECTED AND APPROVED BY THE CITY OF YELM. APPROVAL SHALL NOT RELIEVE THE CONTRACTOR FOR CORRECTION OF ANY DEFICIENCIES ANDIOR FAILURES AS DETERMINED BY SUBSEQUENT TESTING AND INSPECTIONS IT SHALL BE THE CONTRACTOR'S RESPONSIBILITY TO NOTIFY THE CITY OF YELM FOR THE REQUIRED INSPECTIONS R. PUMP CONTROL PANELS SHALL BE LOCATED ON GARAGE WALL OR REMOTE POST, 5- FEET FROM TOP OF PANEL TO FINISH GRADE, UNLESS OTHERWISE AUTHORIZED BY THE CITY OF YELM. S. IN THE EVENT THAT THE DEPARTMENT OF LABOR AND INDUSTRIES OR THE CITY SHOULD REQUIRE A SEPARATE "ON-OFF" SWITCH CONTROLLING POWER TO THE PUMP CONTROL PANEL, SAID SWITCH SHALL HAVE A LOCKING COVER MODEL 15031-0 RAYNT17F SINGLE GANG WEATHERPROOF COVER 1.406" DIAMETER. T. INSPECTIONS FOR ONSITE STEP INSTALLATIONS ARE REQUIRED. A 48 HOUR N0710E TO THE SEWER DEPARTMENT IS REQUIRED PRIOR TO THE INSPECTION. ITEMS NEEDING INSPECTION ARE. 1. TANK INSTALLATION, IE; BEDDING AND LOCATION 2. TANK INFILTRATION, EXFILTRATION TEST J. S.S. PRESSURE TEST 4. SERVICE UNE PRESSURE TEST 5, FINAL INSPEC71ON U. ALL POSTS USED TO SUPPORT PUMP CONTROL PANELS, MUST BE HOT DIP GALVANIZED UNISTRUT OR APPROVED EQUAL. GENERAL NOTES (STREET CONSTRUCTION: A. ALL WORKMANSHIP AND MATERIALS SHALL BE IN ACCORDANCE WITH CITY OF YELM STANDARDS, AND THE MOST CURRENT COPY OF THE STATE OF WASHINGTON STANDARD SPECIFICATIONS FOR ROAD, BRIDGE, AND MUNICIPAL CONSTRUCTION. N B. THE CONTRACTOR SHALL BE RESPONSIBLE FOR ALL TRAFFIC CONTROL IN ACCORDANCE WITH MUTCD. PRIOR TO 3 DISRUPTION OF ANY TRAFFIC, TRAFFIC CONTROL PLANS SHALL BE PREPARED AND SUBMITTED TO THE CITY FOR APPROVAL. NO WORK SHALL COMMENCE UNTIL ALL APPROVED TRAFFIC CONTROL IS IN PLACE. Q C. ALL CURB AND GUTTER, STREET GRADES, SIDEWALK GRADES, AND ANY OTHER VERTICAL ANDIOR HORIZONTAL CL ALIGNMENT SHALL BE STAKED BY AN ENGINEERING OR SURVEYING FIRM CAPABLE OF PERFORMING SUCH WORK, w uj D. WHERE NEW ASPHALT JOINS EXISTING, THE EXISTING ASPHALT SHALL BE CUT TO A NEAT VERTICAL EDGE AND TACKED m WITH ASPHALT EMULSION TYPE CSSI IN ACCORDANCE WITH THE STANDARD SPECIFICATIONS THE NEW ASPHALT SHALL o BE FEATHERED BACK OVER EXIS7INO TO PROVIDE FOR A SEAL AT THE SAW CUT LOCATION AND THE JOINT SEALED WITH GRADE AR-400OW PAVING ASPHALT. i uj E. COMPACTION OF SUBGRADE, ROCK, AND ASPHALT SHALL BE IN ACCORDANCE WITH THE STANDARD SPECIFICATIONS w m a F. SUBGRADE INSPECTION SHALL BE PERFORMED BY AN APPROVED TESTING FIRM AND FORMS SHALL BE INSPECTED FOR o LINE AND GRADE BY AN ENGINEER BEFORE POURING CONCRETE. Lu G. CERTIFICATION AS TO CONFORMANCE SHALL BE PROVIDED TO THE CITY PRIOR TO ACCEPTANCE OF WORK. 0 p H. THE CONTRACTORIDEVELOPER SHALL FURNISH AND INSTALL ALL PERMANENT SIGNING. �0 E� .� N � �Q r%i U & 4o Q m r . ca g ti SPDC E TO E STING F ISH 14 TfIITG GRADE* E TIT STEP TANK � CONNECT TO EI(ISTING P — 1* OR 2m DIECK VALVE SERVa URE 1* (1R. 2" fS BAU, VALVr, B.. x SL - 1, ALL SERVICE UNE CMS%N( BOXES SHALL L BE LOCATED 4` FROM M:' OF CURB TO CENTER OF CARSON 001 IN PLANWR STRIP ON BOTH SIDES OF ROADWAY, 2, GANG CARSON BOXES SiAL.L BE LOCATED 3' APART TO CENTER OF BOAS 3, BALL AND O CK VALI&S M BE INSMEB W CARSM FOXES ACC"NO TO DRA'O% 4, NO VIED CCINNECTMS N SERV4E LKS MESS PRE -APPROVED BY THE ACTOR Or 14S/10 KSIGNM SERVICE Bp - CARS lNrh;STRIES MODEL NO, 14198 WITH BOLTED KNOW Cpm OR EQUAL COVE' VARKWO TO READ *SS R* (M IN NON -TRAFFIC AREAS) ~14 Ok OF HEAVY INSI,.t(,ATED DRE+CT BART` COPM TMNO ME ALL TANG WRE WCES SHAU IECONNECTED BY USK 0.6,Y. KITS MANUfACrUREp BY SM 1*OR 2" $04EDULEJ 40 PVC SW PVC SWING CHECK_ _ 'ALV° :SE x SL S* Iii: 2" KB BALL VALVE, $1, x SL - 1" OR 2' PVC NIPPLE, SL, x S(.. I' OR 2" x MAIN NX PVC RE.IUCINO TEE $L x SL x SL OR IK SAW * K 5�1 TYI ICAL VAND Z S RVICE Pt.tKIC WORKS NRECTOR DAnDA TECONNECTIONS a e � w, PP �_ PPROVED By I I I I ChD I" .II CLEANOUT PUBLIC SKS. IRECIOR VATS' PES. K(KD 10/2D19 RESTORA71ON SURFACE ' RESt iRATION TABLE ABOVE, SEE PESTORAIRON TABLE— ­7 7 TYP. WISH GRA �. /I �-BACKHLL SEE in K$ ICIRATKIN TA :E MAINTAIN SOE SLOPE AS STEEP AS, pol SEWER LI PIPE DEI,1(1ING FOR T4.EXIBLE PIPE SECAU BE SAND f(1" OR AS MPE ILII, APPROVED BY DRECTpR OR HISA4E;IT ITE R AS STUATIONS MAY REOUIRE4* arm WAM aAwuCOKKK swou FUM 00 got am CS�Cx� = CRUSHED MACE COURSE CSTC - CRIISKD SURFACIE. TOP CARS. A w BY D ;. No, ,... TYPICAL PIPE TRENCH PI CK WORKS DIRECTOR ISA DAA �d�Kil 1AKp 1(T2GT9 'V.AL* NUT E'.KTENSIONS' RENT T4 MG gId UT TO YAI'Ii�It+ ,* OF CE /Vy�'7#�E.Fi�. {�4lwPA�'+,�,ryI�1gF6-aiCgi �8d'fyW�y,4�@0e O^p�k T -HE SM EQUAL / 4+t. VER RRI"bi'If(ING O READ 'SEWER* ; ,gym * «� x * t e � 1 1 2'" �CLR, ASF'I(AI T AVER 4 . ► : T C IC'RETE SLAB 2' z 2"-TINII�C, ,BRING TO SURFACE CENTERED ON VALVE rw f IN VALVE BOX -KS EACH WAY TOP NIL 1/2' H OR $LOT F' ME !aT'"t«yf0�14 (007E) OATS 7�pp6yy,NM1E, Vii x MJ PVC S«� MAII'9' ..M,•., 2. .. 4 BARS DO NOT COWR TS TA/ C.I3FImTE # 4INMAM0 SUL w� CM SUPPORT COCK FOR VALVES 2« AND LARGER ""NON" APPROVED OY DWG, NO ryTYPICAL SEWER SAN LINE GATE Pueoc. � owc A 1 VALVE DAIE A2p1R RESTORATION TA .I1N15T eII T� � #k.Fr, R . �INtiG t�dt ,�tAV€'l. BNS, PA" UYl;� �F" dIFd} .' i3 E�"w St14�'Ai� �IAFCtI T!�16 sF sir ss wr�A � ►�tAa 4* UK, �pWARQ � wC444 , T'FI'E A F4Jix °,WWF i� '��y'pQ�FN �gi,�iD�1�tS$A�EF 0